background image

10

If no buttons are touched for 

10 minutes, the screen will au-

tomatically return to the Main 

display. Any settings that have 

not been saved will be lost.

Press [F3] to go to the previous 

page.

Press [F4] to go to the next 

page.

Select the desired item, and 

press the [SELECT] button.

The screen to set the selected 

item will appear.

Press the [RETURN] button to 

exit the Main menu and return to 

the Main display. 

<Navigating through the pages>

F1

F2

F3

F4

Main

Main display:

Cursor

Page

Main menu

Vane·Louver·Vent. (Lossnay)

High power

Timer

Weekly timer

OU silent mode

page

<Saving the settings>

F1

F2

F3

F4

OU silent mode

Mon

 Tue Wed Thu Fri Sat Sun 

 Start         Stop     Silent

             -

Setting display:

day

<Exiting the Main menu screen>

F1

F2

F3

F4

Cool

Room

Auto

Set temp.

Mode

Temp.

Fan

Fri

3.5.2 Vane·Vent. (Lossnay)

<Accessing the menu>

F1

F2

F3

F4

Main

Main display:

Cursor

Page

Main menu

Vane·Louver·Vent. (Lossnay)

High power

Timer

Weekly timer

OU silent mode

<Vane setting>

F1

F2

F3

F4

Fri

Swing

Off

Off

Louver

Vent.

Vane

The message at left will appear 

if the user selects a function not 

supported by the corresponding 

indoor unit model.

Select “Vane·Louver·Vent. (Loss-

nay)” from the Main menu (refer to 

page 9), and press the [SELECT]  

button.

<Vent. setting>

F1

F2

F3

F4

Fri

Low

Vent.

Press the [F1] or [F2] button to go 

through the vane setting options: 

“Auto”, “Step 1”, “Step 2”, “Step 3”, 

“Step 4”, “Step 5” and “Swing”. 

Select the desired setting.

Auto

Auto

Swing

Step 1

Step 2

Step 4

Step 3

Swing

Step 5

Select “Swing” to move the vanes 

up and down automatically.

When set to “Step 1” through “Step 

5”, the vane will be fixed at the se

-

lected angle.

 • 

 under the vane setting icon

  This icon will appear during cool-

ing or dry operation (depends on 

the model).

  The icon will go off in an hour, and 

the vane setting will automatically 

change.

Press the [F3] button to go through 

the ventilation setting options in the 

order of “Off”, “Low”, and “High”.

* Settable only when LOSSNAY unit 

is connected.

Off

Low

High

Off

Low

High

•  The fan on some models of indoor 

units may be interlocked with cer-

tain models of ventilation units.

<Returning to the Main menu>

Press the [RETURN] button to go 

back to the Main menu.

3. Operation

Cool

Room

Auto

Set temp.

Mode

Temp.

Fan

Fri

F1

F2

F3

F4

Main

Main display:

Cursor

Page

Main menu

Vane·Louver·Vent. (Lossnay)

High power

Timer

Weekly timer

OU silent mode

<Display of unsupported functions>

F1

F2

F3

F4

Title

Not available

Unsupported function

Return:

RG79F397H01_01En.indd   10

2018/09/19   11:21:44

Summary of Contents for Mr.SLIM PCA-M-KA Series

Page 1: ...al de operação antes de pôr a funcionar a unidade de ar condicionado DRIFTSMANUAL Læs venligst denne driftsmanual grundigt før airconditionanlægget betjenes af hensyn til sikker og korrekt brug ΕΓΧΕΙΡΙΔΙΟ ΟΔΗΓΙΩΝ ΧΡΗΣΕΩΣ Για ασφάλεια και σωστή χρήση παρακαλείστε διαβάσετε προσεχτικά αυτό το εγχειρίδιο χρήσεως πριν θέσετε σε λειτουργία τη μονάδα κλιματισμού Işletme Elkitabı Emniyetli ve doğru biçim...

Page 2: ...лі а потім мову BG Посетете горепосочения уебсайт за да изтеглите ръководства като изберете име на модел и след това език PL Odwiedź powyższą stronę internetową aby pobrać instrukcje wybierz nazwę modelu a następnie język CS Příručky naleznete ke stažení na internetové stránce zmíněné výše poté co zvolíte model a jazyk SK Na webovej stránke vyššie si môžete stiahnuť návody Vyberte názov modelu a z...

Page 3: ...ther hazards The use of any refrigerant other than that specified for the system will cause mechanical failure or system malfunction or unit breakdown In the worst case this could lead to a serious impediment to securing product safety This unit should be installed in rooms which exceed the floor space specified in outdoor unit installation manual Refer to outdoor unit installation manual Do not u...

Page 4: ... 1 Safety Precautions PCA M KA Ceiling Suspended Vane Air outlet Air intake Filter Inside of Air intake Louver Caution Do not use any sharp object to push the buttons as this may damage the remote controller Never block or cover the indoor or outdoor unit s intakes or outlets Disposing of the unit When you need to dispose of the unit consult your dealer PKA M HA L Wall Mounted Air outlet Louver Va...

Page 5: ...5 Backlit LCD Operation settings will appear When the backlight is off pressing any button turns the backlight on and it will stay lit for a certain period of time depending on the screen When the backlight is off pressing any button turns the backlight on and does not perform its function except for the ON OFF button 6 ON OFF lamp This lamp lights up in green while the unit is in operation It bli...

Page 6: ...ons are displayed for explanation Fri Mode Temp Fan Room Cool Set temp Basic mode Fri Cool Mode Temp Fan Set temp 4 3 2 1 5 6 7 8 9 0 1 3 4 7 2 3 4 5 6 8 9 2 1 5 3 Appears when the On Off timer Night setback or Auto off timer func tion is enabled appears when the timer is disabled by the centralized control system 4 Appears when the Weekly timer is enabled 5 Appears while the units are operated in...

Page 7: ... wet or leave it in a location with high humid ity To avoid misplacing the remote controller install the holder included with the remote controller on a wall and be sure to always place the remote controller in the holder after use Battery installation replacement 1 Remove the top cover insert 2 AAA batter ies and then install the top cover 2 Press the Reset button Outdoor unit Two AAA batteries I...

Page 8: ...ode In the same way if the room temperature remains 2 0 C or more below the set temperature for 15 minutes the air conditioner switches to heat mode Cool mode 15minutes switchesfrom heating to cooling Set temperature 2 0 C Set temperature Set temperature 2 0 C 15minutes switchesfrom cooling to heating F1 F2 F3 F4 Cool Room Auto Set temp Mode Temp Fan Fri Dual set point Note This function cannot be...

Page 9: ...ng sharp at the end MODELSELECT and Model No are lighted for 3 seconds then turned off ON OFF TEMP RESET SET CLOCK MODELSELECT FAN VANE TEST RUN AUTO STOP AUTO START h min LOUVER MODE CHECK B A 3 2 14 3 3 Temperature setting Cool Dry Heat and Auto Cool Room28 5 Auto Set temp Mode Temp Fan Fri 28 5 Example display Centigrade in 0 5 degree increments F1 F2 F3 F4 Cool Room Auto Set temp Mode Temp Fan...

Page 10: ... Louver Vent Loss nay from the Main menu refer to page 9 and press the SELECT button Vent setting F1 F2 F3 F4 Fri Low Vent Press the F1 or F2 button to go through the vane setting options Auto Step 1 Step 2 Step 3 Step 4 Step 5 and Swing Select the desired setting Auto Auto Swing Step 1 Step 2 Step 4 Step 3 Swing Step 5 Select Swing to move the vanes up and down automatically When set to Step 1 th...

Page 11: ...tion Monitor Display GREEN ORANGE STOP The orange lamp follows the switch operation as indicated at the left for 5 seconds and then it will return to the normal display COOL HEAT Turning off Lighting Heat pump type Cooling only type Cooling Heating Stop Cooling Stop For PKA M HA L B A D C E O SW Fig 5 2 Note During swing operation the directional indication on the screen does not change in sync wi...

Page 12: ...the cumulative operation time of all units will be reset The icon is scheduled to appear after a certain duration of operation based on the premise that the indoor units are installed in a space with ordinary air quality Depending on the air quality the filter may require more frequent cleaning The cumulative time at which filter needs cleaning depends on the model This indication is not available...

Page 13: ...the intake grille 2 Hold the knob on the filter then pull the filter up in the direction of an arrow To replace the filter after cleaning be sure to insert the filter far enough until it fits into the stopper B A D C PCA M KA PKA M HA L A Filter B Intake Grille C Knob D Stopper RG79F397H01_01En indd 13 2018 09 19 11 21 45 ...

Page 14: ...indoor unit If the indoor temperature and the humidity are high this condition may occur when operation starts During defrosting mode cool airflow may blow down and appear like a mist Water or vapor is emitted from the outdoor unit During cooling mode water may form and drip from the cool pipes and joints During heating mode water may form and drip from the heat exchang er During defrosting mode w...

Page 15: ... function has operated to protect the air conditioner Do not attempt to repair this equipment by yourself Turn off the power switch immediately and consult your dealer Be sure to provide the dealer with the model name 7 Trouble Shooting Model PKA M35HA L PKA M50HA L Power source voltage V Frequency Hz N 230 50 Rated Input Indoor only kW 0 04 0 03 0 04 0 03 Rated Current Indoor only A 0 40 0 30 0 4...

Page 16: ...power input Pelec kW 0 040 0 050 0 060 0 090 0 110 0 140 Sound power level per speed setting if applicable LWA dB 52 54 57 60 53 55 57 60 56 58 60 62 57 59 61 63 59 61 63 65 61 63 65 68 EU 2016 2281 Model PKA M35HA L PKA M50HA L Cooling Capacity sensible Prated c kW 2 83 3 60 latent Prated c kW 0 67 1 40 Heating Capacity Prated h kW 4 00 5 70 Total electric power input Pelec kW 0 040 Sound power l...

Page 17: ...son traducciones del original CUIDADO Las pérdidas de refrigerante pueden causar asfixia Se debe proporcionar la ventilación de terminada en EN378 1 Asegúrese de colocar el aislante alrededor de las tuberías El contacto directo con la tubería puede ocasionar quemaduras o congelación Para evitar una ingestión accidental no coloque las pilas en su boca bajo ningún concepto La ingestión de las pilas ...

Page 18: ...дный календарь 2014 4 2015 5 The serial number is indicated on the SPEC NAME PLATE Sequential number for each unit 00001 99999 A indoor unit Month of manufacture 4 5 6 7 8 9 X 10 Y 11 Z 12 1 2 3 Last digit of the company s fiscal year western calendar 2014 4 2015 5 Название Компании ООО Мицубиси Электрик РУС Адрес 115114 Российская Федерация г Москва ул Летниковская д 2 стр 1 5 этаж RG79F397H01_ba...

Page 19: ...Norwegian Branch Gneisveien 2D 1914 Ytre Enebakk Norway Portuguese Branch Avda do Forte 10 2799 514 Carnaxide Lisbon Portugal Spanish Branch Carretera de Rubi 76 80 Apdo 420 08173 Sant Cugat del Valles Barcelona Spain Scandinavian Branch Hammarbacken 14 P O Box 750 SE 19127 Sollentuna Sweden UK Branch Travellers Lane Hatfield Herts AL10 8XB England U K Polish Branch Krakowska 50 PL 32 083 Balice P...

Reviews: