background image

•  Make earth wire a little longer 

than others. (More than 60 mm)

•  For future servicing, give extra 

length to the connecting wires.

3.  OUTDOOR UNIT INSTALLATION

3-1. CONNECTING WIRES FOR OUTDOOR UNIT

1) Open the service panel.
2) Loosen terminal screw, and connect indoor/outdoor unit connecting wire (A) from the 

indoor unit correctly on the terminal block. Be careful not to make mis-wiring. Fix the 
wire to the terminal block securely so that no part of its core is appeared, and no ex-
ternal force is conveyed to the connecting section of the terminal block. 

3) Firmly tighten the terminal screws to prevent them from loosening. After tightening, 

pull the wires lightly to confirm that they do not move.

4) Connect power supply cord (K).
5) Fix indoor/outdoor unit connecting wire (A) and power supply cord (K) with the cord 

clamp.

6) Close the service panel securely.

3-2. FLARING WORK

1) Cut the copper pipe correctly with pipe cutter.  

(Fig. 1, 2)

2) Completely remove all burrs from the cut cross sec-

tion of pipe. (Fig. 3)
•  Put the end of the copper pipe to downward direc-

tion as you remove burrs in order to avoid to let 
burrs drop in the piping.

3) Remove flare nuts attached to indoor and outdoor 

units, then put them on pipe having completed burr 
removal. (Not possible to put them on after flaring 
work.) 

4) Flaring work (Fig. 4, 5). Firmly hold copper pipe in 

the dimension shown in the table. Select 

 

A mm from the table according to the tool you use.

Copper 
pipe

Good

Tilted Uneven Burred

No good

Fig. 1

Fig. 2

Lead wire

Terminal block

Cord clamp

Power supply 
cord (K)

Indoor/outdoor unit 
connecting wire (A)
Power supply cord (K)

35 mm

15 mm

Burr

Copper pipe

Spare reamer

Pipe cutter

Clutch type

Flaring tool

Fig. 4

Fig. 3

Wing nut type

Pipe diameter 

(mm)

Nut 

(mm)

A (mm)

Tightening torque

Clutch type 

tool  

for R410A

Clutch type 

tool  

for R22

Wing nut 

type tool  

for R22

N•m

kgf•cm

ø 6.35  (1/4”)

17

0 to 0.5

1.0 to 1.5

1.5 to 2.0

13.7 to 17.7 140 to 180

ø 9.52  (3/8”)

22

34.3 to 41.2 350 to 420

ø12.7  (1/2”)

26

2.0 to 2.5

49.0 to 56.4 500 to 575

ø15.88  (5/8”)

29

73.5 to 78.4 750 to 800

Smooth all 
around

Even length 
all around

Inside is shin-
ing without any 
scratches.

Flare nut

Die

Fig. 5

Fig. 6

Copper pipe

Do not make drain piping as shown below.

Accumulated 
drain water

Air

Waving

Water 
leakage

Do not raise

Water 
leakage

Water 
leakage

Tip of drain 
hose dipped 
in water

Ditch

At least 
50 mm 
gap

Downward 
slope

Drain 
hose

Soft hose 
I.D. 15 mm

Drain hose

Hard vinyl chloride 
pipe I.D. 30 mm

Insert  
securely

Different 
diameter joint

70 cm or 
more

Fig. 1

Fig. 2

Fig. 3

2-8. DRAIN PIPING

•  If the extension drain hose has to pass through a room, be sure to wrap it with com-

mercially sold insulation. 

•  The drain hose should point downward for easy drain flow. (Fig. 1)
•  If the drain hose provided with the indoor unit is too short, connect it with drain hose (I) 

that should be provided at your site. (Fig. 2)

•  When connecting the drain hose to the hard vinyl chloride pipe, be sure to insert it 

securely into the pipe. (Fig. 3)

200

50

Fig. 4

Fig. 5

The catch should be 
located on the under-
side of the hose.

Projection
*  This projection is located on the 

underside of the hose fitting.

Make sure to hook the catch.

Drain hose

Pull the hose to 
confirm it is con-
nected securely.

2-9. FRONT PANEL INSTALLATION

1) Open the horizontal vane for the upper air outlet.
2) Fit the front panel onto the indoor unit from the front, and then push the upper and 

lower areas that are marked with arrows.

3) Push the areas below the upper air outlet and the areas above and below the lower air 

outlet that are marked with arrows.

4) After installing the front panel, install the 2 screws below the upper air outlet.

5) Check 

•  Compare the flared work with Fig. 6.
•  If flare is noted to be defective, cut off the flared section and do flaring work again.

The Drain hose is removed at installation.

•  When routing the drain piping, make sure that the drain hose (1) is routed as shown. 

(Fig. 4)

•  Insert the drain hose all the way to the base of the drain pan (end connection). (Fig. 5) 
 

Make sure that the catch of the drain hose is securely hooked onto the projection 
on the hose fitting of the drain pan. 

•  After connecting the drain hose, be sure to pull the hose to confirm that it is con-

nected securely. 

JG79A145H05

Summary of Contents for MFZ-FB50VA

Page 1: ...ompressor If the compressor is started before the refrigerant pipes are connected and when the stop valve is open air could be drawn in and the pressure in the refrigeration cycle could be come abnormally high This could cause the pipes to burst or injury N Fasten a flare nut with a torque wrench as specified in this manual If fastened too tight a flare nut may break after a long period and cause ref...

Page 2: ...inutes and pump down before removing the old air conditioner Remake flare accord ing to the dimension for new refrigerant 2 INDOOR UNIT INSTALLATION Note Place indoor outdoor unit connecting wire A and power supply cord K at least 1 m away from the TV antenna wire Air inlet Air outlet Outdoor unit installation 4 10 mm 21 mm slot 840 mm 500 mm 169 mm 40 mm 392 mm 330 mm 360 mm IMPORTANT NOTES To com...

Page 3: ...If the horizontal bars will block the lower air outlet use a stand etc to adjust the height of the indoor unit If the upper or lower air outlet is blocked the air conditioner will not be able to cool or warm the room well Do not block the receiver with the grating Otherwise the grating will interfere with the remote controller signal and significantly reduce the distance and area angle from which t...

Page 4: ... pipes Make sure that the drain hose is not routed upward and that there are no waves in the hose Do not pull the hose when applying the tape Route the piping so that it does not project past the rear of the indoor unit Refer to the figure to the right Connecting Pipe Installation Install the connecting pipes so that the piping can move slightly to the front back left and right Piping tape Drain ho...

Page 5: ...75 ø15 88 5 8 29 73 5 to 78 4 750 to 800 Smooth all around Even length all around Inside is shin ing without any scratches Flare nut Die Fig 5 Fig 6 Copper pipe Do not make drain piping as shown below Accumulated drain water Air Waving Water leakage Do not raise Water leakage Water leakage Tip of drain hose dipped in water Ditch At least 50 mm gap Downward slope Drain hose Soft hose I D 15 mm Drai...

Page 6: ...remote controller how to remove the air filters how to remove or put the remote controller in the remote controller holder how to clean precautions for operation etc Recommend the user to read the OPERATING INSTRUCTIONS carefully Emergency operation switch E O SW Caution After test run or remote signal reception check turn off the unit with the E O SW or the remote controller before turning off the...

Page 7: ... to the indoor control board of an air conditioner with a connect ing cable Cutting or extending the connecting cable of the interface results in defects in connecting Do not bundle the connecting cable together with power supply cord indoor outdoor connecting wire and or earth wire Keep as much distance as pos sible between the connecting cable and those wires The thin part of the connecting cabl...

Page 8: ...HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN ...

Reviews: