background image

 

 

 

 
 

 

Energy Saving Data Collecting Server 
EcoWebServerIII 

MODEL

 

MES3-255C-EN 

User’s Manual (Hardware) 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

Before  operating  the  instrument,  you  should  first  read  thoroughly  this  operation 
manual for safe operation and optimized performance of the product. 
Deliver this user’s manual to the end user.

 

Summary of Contents for MES3-255C-EN

Page 1: ...WebServerIII MODEL MES3 255C EN User s Manual Hardware Before operating the instrument you should first read thoroughly this operation manual for safe operation and optimized performance of the product Deliver this user s manual to the end user ...

Page 2: ... Manual Operating IB63918 Packing materials and instruction manual To reduce the load on the environment Packing materials use corrugated cardboard The instruction manual uses recycled paper Packaged contents Make sure all the following items are in the package Product name Qty Product name Qty Energy saving data collecting server main unit 1 Black 110Ω1 2W White 130Ω1 2W CC Link terminal resistor...

Page 3: ...18 6 Battery Installation and Replacement 20 6 1 Installing battery 20 6 2 Replacing battery 20 7 IP Address Setting 21 7 1 Setting IP address 21 7 2 Checking IP address 26 8 Connection Diagram 27 8 1 Power supply section Section de l alimentation électrique 27 8 2 Ethernet communication section Section de communication Ethernet 27 8 2 1 For initial setting IP address setting Pour les réglages ini...

Page 4: ...If inappropriate size of electric wire is used it may cause fire due to generated heat Use an appropriate size of solderless terminal which fits the wire If inappropriate solderless terminal is used wire breakage or contact failure may occur which may cause the device malfunction failure burnout or fire For UL c UL standard please use the copper conductors wire which temperature rating is 60 ºC 75...

Page 5: ...ge line are parallel as a guide Excluding terminal block input section CC Link communication signal line Condition Distance All power lines More than 100mm Other signal line auxiliary power line power frequency input line Condition Distance Power line of 600V or less More than 300mm Other power lines More than 600mm Please connect the shield wire of the CC Link communication cable to the SLD termi...

Page 6: ...uration software Refer to IP Setting of Setting manual The product is configured as follows when shipped from the factory IP address 192 168 10 1 subnet mask 255 255 255 0 gateway nothing When you connect the product directly to a single PC you do not have to change these settings The product has a built in clock Before use set the current date using the supplied configuration software Before oper...

Page 7: ...ttery s accumulated backup time for electric blackout is 13 700 hours 1 57 years Failure to use a battery over backup time may cause a data clear of the product For long time storage avoid the following places Failure to follow this instruction may cause failure and reduced life of the product Ambient temperature exceeds 25ºC to 75ºC Daily average ambient temperature exceeds 35ºC Relative humidity...

Page 8: ...arising from illegal access We recommend users to note the followings 1 Use LAN for preventing illegal access from outside 2 Take measures like firewall and VPN when connecting internet 3 Before using change the default account login ID password Set the account so as not to leak the accont information according to the following precautions Avoid using simple string like Name birth date and numbers...

Page 9: ... transfer EcoMonitorPro 電子式マルチ 指示計器 EMU3 シリーズ 接点入力 アナログ入力 温度入力 MELSEC Q 電力計測ユニット CC Linkローカル局経由 CC Link MDU ブレーカ EcoWebServerIII This Product Ethernet Ethernet View the graph Internet Explorer EcoWebServerIII setting software CC Link terminals PLC data collecting Write collected data to PLC device Transfer collected file Report by Email EcoWebServerIII Time adjustment Client PC Output the alarm st...

Page 10: ... section CC Link communication section Contact output section Contact output terminal block Contacts are closed when monitoring conditions are satisfied Connect external devices such as buzzers or lamps CC Link station number setup switch CC Link transmission speed setup switch LED display LAN interface CH2 Connect to PLC GOT or MODBUS terminal Power supply terminal block Connect a power supply 2 ...

Page 11: ... SD CC Link communication status Blinks green Transmitting through CC Link communication RD Blinks green Receiving through CC Link communication L RUN CC Link link status Blinks green Linking through CC Link communication Off No link through CC Link communication S MST CC Link standby master Off During normal operation This light is off all the time because the product stays in CC Link master mode...

Page 12: ...l block CC Link communication section Terminal symbol Function DA CC Link communication line A DB CC Link communication line B DG CC Link communication line ground SLD CC Link communication line shield NC Not used Both ends of the shield line for CC Link dedicated cable should be connected to SLD of the units Perform D type Type 3 grounding work dedicated for the FG terminal of each unit SLD and F...

Page 13: ...Setting The following explains the preparation for operating the product after it is installed 1 Use the supplied CD to install the setting software on your PC See 2 3 Installation of the software in User s Manual Setting 2 Use the configuration software to set an IP address for the product See 7 IP Address Setting of this instruction manual When you use the factory default setting 192 168 10 1 fo...

Page 14: ...small 2 and large 1 on the back of the main unit Montez adaptateurs pour monter sur IEC rail petits 2 et grand 1 sur le dos de l unité principale Place the hook of the adaptor small into the lower hole Placez le crochet de l adaptateur petit dans le trou plus bas Push the upper part of the adaptor small until you hear it click Appuyez supérieur de l adaptateur petit jusqu à vous l entendez claquem...

Page 15: ...ew A Vue A View A Vue A Mounting screw Borne de montage Square washer Rondelle carrée Installation side board etc IEC rail IEC rail Keep 80 to 90 mm between the square washers Maintenez de 80 à 90 mm entre des rondelle carrées 80 90mm IEC rail fixing square washer Rondelle carrée pour fixer IEC rail IEC rail IEC rail 35mm Make sure to place the square washers parallel to the IEC rail Assurez vous ...

Page 16: ...ook the adaptor into the IEC rail Accrochez l adaptateur à l IEC rail Push the lower part of the main unit until you hear it click Appuyez inférieur de l unité principale jusqu à vous l entendez claquement ...

Page 17: ...ixing metal bracket to come into intimate contact with the main unit and tighten the screw on the top with a screwdriver Tightening torque 1 00 to 1 35 N m Glissez la ferrure en métal de fixation pour toucher étroitement à l unité principale et serrez le vis supérieur avec un tournevis Couple de serrage 1 00 à 1 35 N m IEC rail IEC rail Left side Fixing metal bracket Ferrure en métal de fixation 5...

Page 18: ...outonnez les vis pour fixation l unité qui sont supérieurs de l unité pour la section d alimentation électrique et de l unité pour la section de contact sortie 2 Remove the unit for the power supply section and the unit for the contact output section Retirez l unité pour la section d alimentation électrique et de l unité pour la section de contact Raise Relevez Push Appuyez Unit fixing hook Croche...

Page 19: ...ge 7 Mount the unit for the power supply section and the unit for the contact output section Montez l unité pour la section d alimentation électrique et l unité pour la section de contact de sortie Unit fixing hook Crochet pour fixation l unité Unit fixing protrusion Saillie de fixation l unité Unit fixing lever Levier de fixation l unité Unit fixing hole L unité a arrangé le trou 8 Tighten the un...

Page 20: ...duct off 3 Open the battery cover on the bottom of the server section 4 Remove the battery from the holder 5 Insert a new battery into the holder in the right direction and connect the lead connector to the connector 6 Close the battery cover 7 Turn this product on Caution Make sure to perform battery replacement with electricity off Perform battery replacement within 3 minutes If 3 minutes passes...

Page 21: ... set in the product IP address to be set to the PC 192 168 10 1 192 168 10 xx xx is a value from 2 to 254 The upper 3 digits should be consistent with those for the product 5 Use the setting software to set an IP address for EcoWebServer III Launch the EcoWebServerIII setting software Start menu All Programs Mitsubishi Energy Saving Management Assistance EcoWebServer III MES3 255C EN Click Model M...

Page 22: ...ject management window Or Select Double click here to create a new project and click Open Configure the following settings in the Create New Project window and click OK Project name Optional Specify a name such as Factory A or Floor B so that you can recognize it as a project for EcoWebServer III IP address 192 168 10 1 Specify the factory default IP address Subnet mask 255 255 255 0 Default gatew...

Page 23: ...uration window Click IP address in the tree menu 8 Clicking the button displays the network information read confirmation message Yes Executes network information reading No Cancels network information reading After reading is completed the messsage below is displayed ClickOK 画像差し替え必要 ...

Page 24: ...he following figure shows an example of changing the IP address to 10 123 234 10 Type an IP address subnet mask and default gateway to be used for operation 10 Type a maintenance password factory default ecopass in Password and click Apply In the confirmation dialog box that appears after you click Change click Yes When the IP address configuration is complete the following dialog box appears Clic...

Page 25: ...es to complete Check to see that resetting is complete and the STA LED on the EcoWebServer III main unit turns on before starting communications 3 The values of IP address Subnet mask and Default gateway in the project information are also automatically updated with the new values 11 After changing the IP address for the product return the PC s IP address to its original address ...

Page 26: ...rn off return the RESET SELECT switch to the central position 5 Wait until the product starts up and the IP address is displayed on the 7 segment LED at the front IP address display Display example of 192 168 10 1 set in the product Hexadecimal C0 Decimal 192 Hexadecimal A8 Decimal 168 Hexadecimal 0A Decimal 10 Hexadecimal 01 Decimal 1 Hexadecimal C0 Decimal 192 Hexadecimal A8 Decimal 168 Hexadeci...

Page 27: ...P address setting Pour les réglages initiaux adresse IP fixation LAN cable Straight or crossover Droit ou métissé PC Supplied CD Setting software Logiciel de réglages CH 1 CH 2 Noise filter Filtre de bruit Note See more notice in page 3 Live wire fortifications is NOT allowed Wire size refers to page 3 FG LG is exclusive for D class grounding Please connect L N over a noise filter Note Voyez les r...

Page 28: ...28 8 2 2 For operation Pour opération Hub Hub Client PC PC clientèle LAN cable Straight Câble de LAN Droit Hub Hub Intranet LAN network Réseau d intranet LAN CH 1 CH 2 ...

Page 29: ... Ethernet de la terminal MODBUS TCP MODBUS TCP MODBUS RTU convertor Convertisseur MODBUS TCP MODBUS RTU LAN cable Straight or crossover Câble de LAN Droit ou métissé Connect to MODBUS RTU terminal Connectez vous à la terminal MODBUS RTU LAN cable Straight or crossover Câble de LAN Droit ou métissé CH1 CH2 Please see the details in PLC s instruction manual Voyez le mode d emploi de PLC en détail FX...

Page 30: ...he following table so that it will not exceed the maximum transmission distance Réalisez le câblage selon la table suivante afin qu il n excède pas la distance de transmission maximale Communication speed Vitesse de la communication 156 kbps 625 bps 2 5 Mbps 5 Mbps 10 Mbps Cable length between stations Vitesse de la communication 20 cm or longer 20 cm ou plus 20 cm or longer 20 cm ou plus 20 cm or...

Page 31: ...érieur au courant de charge maximum de la section de contact de sortie If the inrush current is large perform any one of the following to reduce the impact of the inrush current Si le courant d afflux est grand réalisez l un des suivants pour diminuer l impact du courant d afflux Contact output section Resisor Load Contact output section Load Inductance Section de sortie contact Résistance Charge ...

Page 32: ...ach XYZ direction Operating environment No corrosive gas Operating altitude 2000 m or below Installation area Inside a board Overvoltage category 1 II or below Contamination level 2 2 or below Mass 0 9 kg Fuse Built in unchangeable by user ERR terminal Application Off when no power is input the product is reset or fuse blows Rated switching voltage current 24 V DC 0 5 A Min switching load 5 V DC 1...

Page 33: ...RC X 16 X 12 X 5 1 Connection cable Ver 1 10 compatible CC Link dedicated cable Contact output section Number of output points 16 points Insulation method Relay insulation Rated switching voltage current 24 V DC 2 A resistance load 240 V AC 2 A COSφ 1 24 V DC 2 A charge de résistance 240 V AC 2 A COSφ 1 1 point 8 A 1 common 1 point 8 A 1 commun Min switching load 5 V DC 1 mA Max switching load 264...

Page 34: ...cturer Distance from the terminal EMI FILTER NF2060A RQ 2 SOSHIN ELECTRIC CO LTD 100mm CLAMP FILTER ZCAT2235 1030A 3 TDK 100mm L N LG FG ERR ERR D class grounding 1 3 5 7 9 B D F 0 2 4 6 8 A C E 0 1 2 3 4 5 6 7 8 9 A B C D E F COM CLAMP FILTER EMI FILTER EMI FILTER LAN cable straight or crossover CC Link terminal CC Link CC Link terminal CLAMP FILTER 0 to F COM output section CLAMP FILTER NC DA DB...

Page 35: ...ay color 65 536 colors or more Input device A mouse and a keyboard English input system The system included in OS English version only External interface 10BASE T 100BASE TX Memory card reader when writing reading confirming a project via drive by setting software Web browser 2 Microsoft Internet Explorer 9 32 bit 10 32 bit or 11 32 bit Microsoft Edge Google Chrome 1 Note that the required memory ...

Page 36: ...36 10 External Dimensions 10 1 External dimonsions 104 114 97 5 122 5 111 5 122 5 4 5 Side Front Bottom Unit mm ...

Page 37: ...lace 1 It is no problem to remove the LAN port cap during the operating Over 30mm Over 30mm Over 17mm Over 5mm Position of ceiling of the board trunking or other parts When trunking is less than 50mm In other cases is over Over 80mm door 11 Options Product name Model name Replacement battery Q6BAT ...

Page 38: ...r is normally running or settings in the SNTP server are correct E4 is displayed on the 7 segment LED on the server section File transfer to the FTP server has failed Check whether communication with the FTP server is normally running or settings in the FTP server are correct The indication rotates on the 7 segment LED on the server section Is any CompactFlash card other than that supplied with th...

Page 39: ...39 MEMO ...

Page 40: ...40 MEMO ...

Page 41: ...to the user or any third party s claim against the user arising from the execution of the license of use granted to the user under the Agreement Article 5 Alteration of the Software by user Any modification of the Software by the user shall not be allowed without written permission from Mitsubishi Electric Mitsubishi Electric shall assume no responsibility for the Software that has been modified b...

Page 42: ...n on the place of the rating label 定格銘板例 额定铭板参考例 Example of the rating label MES3 255C EN の例です 以 MES3 255C EN 为例 Example of MES3 255C EN is shown below 定格銘板位置 关于额定铭板的位置 The place of the rating label MES3 255B MES3 255C CN 本製品の定格銘板は右側面にあります 本产品的额定铭板在产品的右侧面 MES3 255C MES3 255C EN 本製品の定格銘板は右側面にあります The rating label can be found on the right side of the product 额定铭板 the rating label 定格銘板 定格銘板 形名 型号 Mo...

Page 43: ...d trademark of Cisco Corporation in the United States Android Chrome is a registered trademark of Google Inc Safari is a registered trademark of Google Inc Ethernet is a registered trademark of Xerox Corporation in the United States MODBUS is a registered trademark of Schneider Automation Inc QR Code is a registered trademark of Denso Wave Incorporated EcoWebServer is a registered trademark of Mit...

Page 44: ... 82 2 3660 9572 Laos AROUNKIT CORPORATION IMPORT EXPORT SOLE CO LTD SAPHANMO VILLAGE SAYSETHA DISTRICT VIENTIANE CAPITAL LAOS 856 20 415899 Lebanon Comptoir d Electricite Generale Liban Cebaco Center Block A Autostrade Dora P O Box 11 2597 Beirut Lebanon 961 1 240445 Lithuania Rifas UAB Tinklu 29A LT 5300 Panevezys Lithuania 370 0 45 582 728 Malaysia Mittric Sdn Bhd No 5 Jalan Pemberita U1 49 Tema...

Reviews: