6 OPTIONS AND PERIPHERAL EQUIPMENT
6.10 Molded-case circuit breakers, fuses, magnetic contactors
223
6
Using servo amplifier with DC power supply input
When using a fuse instead of the molded-case circuit breaker, use the one having the specifications given in this section.
■
For main circuit power supply [G] [A]
*1 Use a molded-case circuit breaker that has operation characteristics equal to or higher than Mitsubishi Electric general-purpose
products.
*2 Use the magnetic contactor with an operation delay time (interval between current being applied to the coil until closure of contacts) of
80 ms or less.
Servo
amplifier
Molded-case circuit breaker
Fuse
Magnetic
contactor
Frame, rated current
Voltage AC
[V]
Class
Current [A]
Voltage DC
[V]
Power factor
improving
reactor is not
used
Power factor
improving
reactor is used
MR-J5-10_
30 A frame 5 A
30 A frame 5 A
240
T
10
400
DUD-N30
MR-J5-20_
30 A frame 5 A
30 A frame 5 A
MR-J5-40_
30 A frame 10 A
30 A frame 5 A
15
MR-J5-60_
30 A frame 15 A
30 A frame 10 A
20
MR-J5-70_
30 A frame 15 A
30 A frame 10 A
MR-J5-100_
(3-phase power
supply input)
30 A frame 15 A
30 A frame 10 A
MR-J5-100_
(1-phase power
supply input)
30 A frame 15 A
30 A frame 15 A
MR-J5-200_
30 A frame 20 A
30 A frame 20 A
30
MR-J5-350_
30 A frame 30 A
30 A frame 30 A
40
MR-J5-500_
50 A frame 50 A
50 A frame 50 A
60
DUD-N60
MR-J5-700_
100 A frame 75 A
60 A frame 60 A
80