6 OPTIONS AND PERIPHERAL EQUIPMENT
6.10 Molded-case circuit breakers, fuses, magnetic contactors
219
6
6.10
Molded-case circuit breakers, fuses, magnetic
contactors
When using a fuse instead of the molded-case circuit breaker, use the one having the specifications given in this section.
Precautions
• Select the molded-case circuit breakers specified in this section.
• Wire the molded-case circuit breaker and magnetic contactor as recommended.
For main circuit power supply [G] [A]
■
200 V class
*1 Refer to the following page for compliance with IEC/EN/UL/CSA standards.
Page 229 Example settings that comply with IEC/EN/UL 61800-5-1 and CSA C22.2 No.274
*2 Use the magnetic contactor with an operation delay time (interval between current being applied to the coil until closure of contacts) of
80 ms or less.
*3 Use a molded-case circuit breaker that has operation characteristics equal to or higher than Mitsubishi Electric general-purpose
products.
■
400 V class
*1 Refer to the following page for compliance with IEC/EN/UL/CSA standards.
Page 229 Example settings that comply with IEC/EN/UL 61800-5-1 and CSA C22.2 No.274
*2 Use the magnetic contactor with an operation delay time (interval between current being applied to the coil until closure of contacts) of
80 ms or less.
*3 Use a molded-case circuit breaker that has operation characteristics equal to or higher than Mitsubishi Electric general-purpose
products.
Servo
amplifier
Molded-case circuit breaker
Fuse
Magnetic
contactor
Frame, rated current
Voltage AC
[V]
Class
Current
[A]
Voltage AC
[V]
Power factor
improving reactor is
not used
Power factor
improving reactor is
used
MR-J5-10_
30 to 125 A frame 5 A
30 to 125 A frame 5 A
240
T
10
300
S-T10
MR-J5-20_
30 to 125 A frame 5 A
30 to 125 A frame 5 A
MR-J5-40_
30 to 125 A frame 10 A
30 to 125 A frame 5 A
15
MR-J5-60_
30 to 125 A frame 15 A
30 to 125 A frame 10 A
20
MR-J5-70_
30 to 125 A frame 15 A
30 to 125 A frame 10 A
MR-J5-100_
(3-phase power
supply input)
30 to 125 A frame 15 A
30 to 125 A frame 10 A
MR-J5-100_
(1-phase power
supply input)
30 to 125 A frame 15 A
30 to 125 A frame 15 A
30
MR-J5-200_
30 to 125 A frame 20 A
30 to 125 A frame 20 A
40
S-T21
MR-J5-350_
30 to 125 A frame 30 A
30 to 125 A frame 30 A
70
MR-J5-500_
50 to 125 A frame 50 A
50 to 125 A frame 50 A
125
S-T25
MR-J5-700_
100 to 125 A frame 75 A
60 to 125 A frame 60 A
150
S-T35
Servo
amplifier
Molded-case circuit breaker
Fuse
Magnetic
contactor
Frame, rated current
Voltage AC
[V]
Class
Current
[A]
Voltage AC
[V]
Power factor
improving reactor is
not used
Power factor
improving reactor is
used
MR-J5-60_4_
30 to 125 A frame 5 A
30 to 125 A frame 5 A
480
T
10
600
S-T10
MR-J5-100_4_
30 to 125 A frame 10 A
30 to 125 A frame 5 A
15
MR-J5-200_4_
30 to 125 A frame 15 A
30 to 125 A frame 10 A
25
MR-J5-350_4_
30 to 125 A frame 20 A
30 to 125 A frame 15 A
35
S-T21