6 OPTIONS AND PERIPHERAL EQUIPMENT
6.4 Multifunction regeneration converter (FR-XC-(H))
207
6
Wiring and peripheral options
Wire size
Selection requirements for the wire size are as follows.
Wire type: 600 V Grade heat-resistant polyvinyl chloride insulated wire (HIV wire)
Construction requirements: Single wire set in midair
■
Between P/+ to P4 and N/- to N-
The following table shows the size of the wire between the FR-XC-(H) and servo amplifier.
■
Grounding
The following table shows the size of the grounding wire for the FR-XC-(H). Use the shortest size wire possible.
Total capacity of servo amplifiers [kW]
Wire size [mm
2
]
200 V class
400 V class
1 or less
2 (AWG 14)
2 (AWG 14)
2
3.5 (AWG 12)
2 (AWG 14)
3.5
5.5 (AWG 10)
3.5 (AWG 12)
5
5.5 (AWG 10)
5.5 (AWG 10)
7
8 (AWG 8)
5.5 (AWG 10)
11
14 (AWG 6)
8 (AWG 8)
15
22 (AWG 4)
8 (AWG 8)
18.5
38 (AWG 2)
8 (AWG 8)
22
50 (AWG 1/0)
14 (AWG 6)
27.5
50 (AWG 1/0)
22 (AWG 4)
30
60 (AWG 2/0)
22 (AWG 4)
37
80 (AWG 3/0)
38 (AWG 2)
45
100 (AWG 4/0)
38 (AWG 2)
55
100 (AWG 4/0)
50 (AWG 1/0)
Multifunction regeneration converter
Wire size [mm
2
]
Rated capacity of multifunction
regeneration converter
≥
Total capacity of
connected servo amplifiers × 2
Rated capacity of multifunction
regeneration converter < Total capacity of
connected servo amplifiers × 2
FR-XC-7.5K
8 (AWG 8)
8 (AWG 8)
FR-XC-11K
8 (AWG 8)
14 (AWG 6)
FR-XC-15K
8 (AWG 8)
22 (AWG 4)
FR-XC-22K
22 (AWG 4)
38 (AWG 2)
FR-XC-30K
22 (AWG 4)
38 (AWG 2)
FR-XC-37K
38 (AWG 2)
60 (AWG 2/0)
FR-XC-55K
38 (AWG 2)
80 (AWG 3/0)
FR-XC-H7.5K
3.5 (AWG 12)
3.5 (AWG 12)
FR-XC-H11K
3.5 (AWG 12)
5.5 (AWG 10)
FR-XC-H15K
3.5 (AWG 12)
8 (AWG 8)
FR-XC-H22K
8 (AWG 8)
14 (AWG 6)
FR-XC-H30K
8 (AWG 8)
22 (AWG 4)
FR-XC-H37K
14 (AWG 6)
22 (AWG 4)
FR-XC-H55K
14 (AWG 6)
38 (AWG 2)