(3) Output status for each status
Depending on the states of the data link and head module, data may not be able to be output.
The following table shows how the states of the data link and head module affect the output (Y).
-: Not dependent on the status
Switch
Head module status
Data link status
Output (Y) status
RUN
Operating normally
Cyclic
transmission in
progress
Varies depending on the status and settings of the Motion controller. (
User's manual for the
Motion controller used)
(1)
If the Motion controller is in the stop error status:
The output (Y) status follows the "Error Time Output Mode" setting in the PLC Parameter.
(
The analog output status of the digital-analog converter module and analog input/output
module follows the setting of the analog output HOLD/CLEAR function.
MELSEC-L Digital-Analog Converter Module User's Manual
MELSEC-L Analog Input/Output Module User's Manual
(2)
When the Motion controller is in the STOP status:
The output (Y) turns off.
The analog output status of the digital-analog converter module and analog input/output
module follows the setting of the analog output HOLD/CLEAR function.
MELSEC-L Digital-Analog Converter Module User's Manual
MELSEC-L Analog Input/Output Module User's Manual
The refresh device status of the Motion controller is as follows:
• Turns off if "Y" is specified for the CPU side device.
• Holds its status if "other than Y (M, L, etc.)" is specified for the CPU side device.
RUN
Operating normally
Cyclic
transmission
stopped
The output (Y) status follows the "Error Time Output Mode" setting in the PLC Parameter. (
Page 63, Section 7.1 (6))
The analog output status of the digital-analog converter module and analog input/output module
follows the setting of the analog output HOLD/CLEAR function.
MELSEC-L Digital-Analog Converter Module User's Manual
MELSEC-L Analog Input/Output Module User's Manual
RUN
Operating normally
Disconnected
The output (Y) status is held for 3.5ms after the communication with the Motion controller is
terminated due to a break in the SSCNET III cable or other possible causes.
The output (Y) status after disconnection follows the "Error Time Output Mode" setting in the PLC
Parameter. (
Error
The output (Y) status follows the "Error Time Output Mode" setting in the PLC Parameter. (
STOP
Operating normally
The output (Y) turns off.
The analog output status of the digital-analog converter module and analog input/output module
follows the setting of the analog output HOLD/CLEAR function.
MELSEC-L Digital-Analog Converter Module User's Manual
MELSEC-L Analog Input/Output Module User's Manual
Summary of Contents for MELSEC-L SSCNETIII/H
Page 1: ...MELSEC L SSCNET H Head Module User s Manual LJ72MS15 ...
Page 2: ......
Page 11: ...9 Memo ...
Page 17: ...15 Memo ...
Page 21: ...19 CHAPTER 1 HEAD MODULE 1 Memo ...
Page 30: ...28 Memo ...
Page 36: ...34 Memo ...
Page 54: ...52 Memo ...
Page 78: ...76 Memo ...
Page 82: ...80 Memo ...
Page 102: ...100 Memo ...
Page 106: ...104 Memo ...
Page 110: ...108 Memo ...
Page 112: ...110 Memo ...
Page 114: ...112 Memo ...
Page 125: ...123 APPENDICES A Appendix 7 Special Register SD List Memo ...
Page 137: ...135 APPENDICES A Appendix 9 General Safety Requirements Memo ...
Page 141: ...139 APPENDICES A Appendix 11 Processing Time Memo ...
Page 145: ...143 APPENDICES A Appendix 12 Checking Serial Number and Function Version Memo ...
Page 147: ...145 APPENDICES A Appendix 13 External Dimensions Memo ...
Page 153: ......