6 WIRING
6.1 Terminal Block
25
6
6
WIRING
This chapter describes the wiring of the D/A converter module.
6.1
Terminal Block
Precautions
Tighten the module fixing screws and others within the specified torque range.
*1 The hook on the top of the module allows the module to be fixed to a base unit easily. In a place where there is a lot of vibration,
however, fixing with module fixing screws is recommended.
The following table lists an applicable solderless terminal to be connected to the terminal block. When wiring, use applicable
wires and an appropriate tightening torque. Use UL listed solderless terminals and, for processing, use a tool recommended
by their manufacturer. Note that a solderless terminal with an insulation sleeve cannot be used.
Signal names of the terminal blocks
The following table shows signal names of the terminal blocks.
■
R60DA4
Screw type
Tightening torque range
Module fixing screw (M3)
0.37 to 0.48N
m
Terminal screw (M3)
0.42 to 0.58N
m
Terminal block mounting screw (M3.5)
0.66 to 0.89N
m
Solderless terminal
Wire
Model
Applicable
tightening torque
Diameter
Type
Material
Temperature rating
R1.25-3
0.42 to 0.58N
m
0.3 to 0.75
(22 to 18 AWG)
Stranded
Copper
75
or greater
Terminal block
Terminal number
Signal name
1
CH1
V+
2
COM
3
I+
4
NC
5
CH2
V+
6
COM
7
I+
8
NC
9
CH3
V+
10
COM
11
I+
12
NC
13
CH4
V+
14
COM
15
I+
16
+24V
17
24G
18
FG
CH1
COM
CH1
V+
NC
CH1
I+
CH2
COM
CH2
V+
NC
CH2
I+
CH3
COM
CH3
V+
NC
CH3
I+
CH4
COM
CH4
V+
+24V
CH4
I+
FG
24G
Summary of Contents for MELSEC iQ-R60DA4
Page 1: ...MELSEC iQ R Digital Analog Converter Module User s Manual Startup R60DA4 R60DAV8 R60DAI8 ...
Page 2: ......
Page 17: ...1 PART NAMES 15 1 MEMO ...
Page 22: ...20 3 FUNCTION LIST MEMO ...
Page 24: ...22 4 PROCEDURES BEFORE OPERATION MEMO ...
Page 26: ...24 5 SYSTEM CONFIGURATION MEMO ...
Page 61: ...APPX Appendix 3 External Dimensions 59 A MEMO ...
Page 63: ...I 61 MEMO ...
Page 67: ......