![Mitsubishi Electric Melsec iQ-R60AD16-G User Manual Download Page 43](http://html.mh-extra.com/html/mitsubishi-electric/melsec-iq-r60ad16-g/melsec-iq-r60ad16-g_user-manual_239145043.webp)
APPENDICES
Appendix 1 I/O Conversion Characteristics
41
A
*1 Set the offset value and gain value in the user range setting within a range satisfying the following conditions. Failure to satisfy the
conditions may not result in proper A/D conversion.
Setting range of the offset value and gain value: -10 to 10V
((Gain value) - (Offset value))
1.6V
*2 Maximum resolution in the user range setting.
*3 If an analog input value exceeds the range of digital output value, the digital output value is fixed to the maximum or minimum value.
• Set values within the practical range of the analog input and the digital output at each input range. If the
range is exceeded, the resolution and accuracy may not fall within the range of the performance
specifications. (Do not use the values in the dotted line region in the graph of voltage input characteristics.)
• Do not set the voltage over
15V. Doing so can cause breakdown of the elements.
Input range setting
Digital output value
Minimum
Maximum
1 to 5V
-768
32767
0 to 5V
-10 to 10V
-32768
0 to 10V
-768
1 to 5V (extended mode)
-8768
36767
User range setting
-32768
32767
Summary of Contents for Melsec iQ-R60AD16-G