136
2 PARAMETER SETTINGS
2.3 Basic Settings
Network Topology
Select the topology type according to the actual network configuration.
Submaster Parameters
Configure the setting for the submaster station. Select whether to set the network configuration or other parameters for the
submaster station, or to read parameters of the master station.
Operation of Master Station after Reconnection
When using the submaster function, select the operation of the master station for when it returned after disconnection.
*1 When "RJ71GF11-T2 (LR)" is selected for the module model name of the master station, the setting is fixed to "Return as Master
Operation Station".
*2 When "RJ71GF11-T2 (MR)" is selected for the module model name of the master station, the setting is fixed to "Return as Sub-master
Operation Station".
Item
Description
Setting range
Network Topology
Select the topology type according to the actual network configuration.
To use the loopback function, select "Ring". (
• Line/Star
• Ring
(Default: Line/Star)
Item
Description
Setting range
Submaster
Parameters
When the submaster station will be powered on earlier than the master station,
select "Operate with Parameter of Host Station" and set the following
parameters. Configure the same settings as those of the master station.
• "Network Configuration Settings" in "Basic Settings"
• "Network Topology" in "Basic Settings"
• "Link Scan Mode" under "Supplementary Cyclic Settings" in "Application
Settings"
• "Station-based Block Data Assurance" under "Supplementary Cyclic Settings"
in "Application Settings"
• "IP Address" in "Application Settings"
When "Read Parameters of the Master Station" is selected, the submaster
station operates according to the parameters set for the master station.
• Read Parameters of the Master Station
• Operate with Parameter of Host Station
(Default: Read Parameters of the Master Station)
Item
Description
Setting range
Operation of Master
Station after
Reconnection
When using the submaster function, select the operation of the master station
for when it returned after disconnection.
• Return as Master Operation Station
• Return as Submaster Operation Station
(Default: Return as Master Operation Station)