442
12 DATA USED FOR POSITIONING CONTROL
12.6 Condition Data
[Da.19] Parameter 2
Set the parameters according to the value set in [Da.16] Condition operator.
■
Buffer memory address
For the buffer memory address of this area, refer to the following.
■
Default value
The default value is 0 for all the axes.
Setting of [Da.16] Condition
operator
Setting
value
Description
01H: ** = P1
Not used. (Setting this item is not required.)
02H: **
P1
03H: **
P1
04H: **
P1
05H: P1
**
P2
Numerical
value
(Bit number)
Set the value of P2 to be equal to or greater than the value of P1 (P1
P2).
If P1 is greater than P2 (P1>P2), Condition data error (Error code: 1A04H) occurs.
06H: **
P1, P2
**
07H: DEV = ON
Not used. (Setting this item is not required.)
08H: DEV = OFF
10H: Axis 1 specification
20H: Axis 2 specification
30H: Axis 1 and axis 2 specification
40H: Axis 3 specification
Numerical
value
(Positioning
data No.)
Set the positioning data number for starting the axis 3 and/or axis 4.
• Lower 16 bits: Positioning data No. 1 to 600 for the axis 1 (01H to 258H)
• Upper 16 bits: Positioning data No. 1 to 600 for the axis 2 (01H to 258H)
to
E0H: Axis 2, axis 3, and axis 4
specification
Summary of Contents for MELSEC iQ-R RD75P4
Page 1: ...MELSEC iQ R Positioning Module User s Manual Application RD75P2 RD75P4 RD75D2 RD75D4 ...
Page 2: ......
Page 13: ...11 MEMO ...
Page 19: ...17 CONTENTS INDEX 588 REVISIONS 592 WARRANTY 593 TRADEMARKS 594 ...
Page 498: ...496 13 PROGRAMMING 13 2 List of Labels Used ...
Page 503: ...13 PROGRAMMING 13 4 Program Example 501 13 ...
Page 514: ...512 13 PROGRAMMING 13 4 Program Example Restart program Parameter data initialization program ...
Page 515: ...13 PROGRAMMING 13 4 Program Example 513 13 Flash ROM write program Error reset program ...
Page 516: ...514 13 PROGRAMMING 13 4 Program Example Stop program ...
Page 565: ...APPENDICES Appendix 4 Operation Examples of When the Remote Head Module Is Mounted 563 A ...
Page 597: ......