4 ADVANCED POSITIONING CONTROL
4.1 Overview of Advanced Positioning Control
155
4
Data required for advanced positioning control
Advanced positioning control is performed by setting the required items in Block start data and Condition data, and starting
the block start data. Whether or not the operations can be executed is judged at the execution of the control according to the
condition data specified in the block start data.
Block start data can be set for each number from 7000 to 7004 (called block No.), and up to 50 points can be set for each axis.
(This data is controlled with numbers called Points to distinguish it from the positioning data. For example, the 1st point block
start data item is called 1st point block start data or Point No. 1 block start data.)
Condition data can be set for each number from 7000 to 7004 (called block No.), and up to 10 data items can be set for each
block No.
Block start data and Condition data are set as one for each block No.
The following table shows the overview of Block start data and Condition data stored in the RD75.
Setting item
Setting detail
Block start data
[Da.11]
Shape
Set whether to end the control after only the block start data of the shape itself is executed, or to
continue executing the block start data set in the next point.
[Da.12]
Start data No.
Set Positioning data No. to be executed.
[Da.13]
Special start
instruction
Set the method by which the positioning data set in [Da.12] will be started.
[Da.14]
Parameter
Set the conditions by which the start will be executed according to the commands set in [Da.13].
(Specify Condition data No. or No. of repetitions.)
Condition data
[Da.15]
Condition target
Select Device, Stored contents in buffer memory, and Positioning data No. elements for which the
conditions are set.
[Da.16]
Condition operator
Set the judgment method performed for the target set in [Da.15].
[Da.17]
Address
Set the buffer memory address in which the condition judgment is performed (only when the element
set in [Da.15] is Stored contents in buffer memory).
[Da.18]
Parameter 1
Set the required conditions according to the elements set in [Da.15] and [Da.16].
[Da.19]
Parameter 2
Set the required conditions according to the elements set in [Da.15] and [Da.16].
Summary of Contents for MELSEC iQ-R RD75P4
Page 1: ...MELSEC iQ R Positioning Module User s Manual Application RD75P2 RD75P4 RD75D2 RD75D4 ...
Page 2: ......
Page 13: ...11 MEMO ...
Page 19: ...17 CONTENTS INDEX 588 REVISIONS 592 WARRANTY 593 TRADEMARKS 594 ...
Page 498: ...496 13 PROGRAMMING 13 2 List of Labels Used ...
Page 503: ...13 PROGRAMMING 13 4 Program Example 501 13 ...
Page 514: ...512 13 PROGRAMMING 13 4 Program Example Restart program Parameter data initialization program ...
Page 515: ...13 PROGRAMMING 13 4 Program Example 513 13 Flash ROM write program Error reset program ...
Page 516: ...514 13 PROGRAMMING 13 4 Program Example Stop program ...
Page 565: ...APPENDICES Appendix 4 Operation Examples of When the Remote Head Module Is Mounted 563 A ...
Page 597: ......