37 FUNCTIONS
37.14 Remote Operation
663
37
37.14
Remote Operation
In a system using the SIL2 Process CPU, the behavior of a remote operation (with the engineering tool) differs for each
operation.
*1 When the safety operation mode is SAFETY MODE, the safety global devices, safety global labels, safety local labels, and standard/
safety shared labels are not cleared.
Remote RUN/Remote STOP/Remote PAUSE
The CPU module operating status of a system specified in the transfer setup of the engineering tool or both systems can be
changed.
Remote operation performed on the system specified in the engineering tool
When the following item is selected in "Execution Target", the remote operation is performed only on the CPU module of a
system specified in the transfer setup of the engineering tool.
• Currently Specified Station
[Online]
[Remote Operation]
Remote operation performed on both systems
When the following item is selected in "Specify Execution Target", the remote operation is performed on the CPU modules of
both systems.
• Specify Both Systems
[Online]
[Remote Operation]
When "Specify Redundant CPU" is set to "Not Specified" in the transfer setup, select "All Stations Specified" or
"Specified Group" to perform a remote operation on the CPU modules of both systems.
Operation
Behavior
Remote RUN
/Remote STOP/Remote PAUSE
The CPU module operating status of a system specified in the transfer setup of the engineering tool or
both systems can be changed.
Remote RESET
The CPU modules of both systems can be reset by performing the remote RESET operation on the
control system CPU module. Only the standby system CPU module can be reset by performing the
remote RESET operation on the standby system CPU module.
Summary of Contents for MELSEC iQ-R-R00CPU
Page 2: ......
Page 151: ...9 MONITOR FUNCTION 9 1 Real Time Monitor Function 149 9 MEMO ...
Page 323: ...18 SEQUENCE SCAN SYNCHRONIZATION SAMPLING FUNCTION 321 18 MEMO ...
Page 330: ...328 20 ROUTING SETTING 20 3 Precautions MEMO ...
Page 423: ...26 BASIC CONCEPT 26 8 State Transition of the Redundant System 421 26 MEMO ...
Page 1014: ...1012 APPX Appendix 15 Added and Enhanced Functions MEMO ...
Page 1027: ......