306
APPX
Appendix 7 Processing Time
*1 The switching hub delay time changes depending on the hub models and settings.
*2 Total number of points is the smallest value set in "Start" to the largest value set in "End" of "Network Configuration Settings".
*3 This is the slave station with the largest calculation value when, for each slave station (including extension modules), (("RX setting" +
"LB setting")/8) + (("RWr setting" + "LW setting")
2) is calculated.
*4 Calculate by rounding up each calculation result in brackets.
*5 In "Inter-module Synchronization Setting" under "System Parameter" of the master station, "Use Inter-module Synchronization Function
in System" is set to "Not Use" or "Select Inter-module Synchronization Target Module" is set to "Do Not Synchronize".
p1: RX/RY/RWr/RWw
processing time
{((Total number of points of "RX setting") + (Total number of points of "RY setting"
))/8 + ((Total number of points of "RWr setting")
+ (Total number of points of "RWw setting"
))
2}
5 + (Sn
3300)
However, if Total number of points of "RY setting"
= Total number of points of "RX setting" = Total number of points of "RWr
setting" = Total number of points of "RWw setting"
= 0, then p1 = 0.
p2: LB/LW processing
time
{(Total number of points of "LB setting" excluding master station)/8) + (Total number of points of "LW setting" excluding master
station)
2 + (Number of points of "LB setting" set in the master station)/8 + (Number of points of "LW setting" set in the master
station)
2}
5 + Sn
6000
However, if Total number of points of "LB setting" = Total number of points of "LW setting" = 0, then p2 = 0.
p3: Diagnostic
information processing
time
Sn
40
p4: Safety input/output
processing time
7000
(The number of connections of "Safety Communication Setting" in "Basic Settings" set in the master station) + 20000
However, if the number of connections of "Safety Communication Setting" in "Basic Settings" set in the master s 0, then p4
= 0.
kp
78000
kum: Inter-module
synchronous processing
time (multicast)
2000
(Number of slave stations) +18000
However, if the inter-module synchronization is not performed in the master station
, then kum=0.
Name of variable
Description