![Mitsubishi Electric MELSEC iQ-R C R12CCPU-V User Manual Download Page 66](http://html.mh-extra.com/html/mitsubishi-electric/melsec-iq-r-c-r12ccpu-v/melsec-iq-r-c-r12ccpu-v_user-manual_239137066.webp)
64
4 BASIC FUNCTIONS
4.12 RAS Function
Operation at error detection of an intelligent function module
If an error is detected with the self-diagnostic function, C Controller module operates in accordance with the setting of "CPU
Module Operation Setting at Error Detected" as follows. (
Page 65 Operation setting when an error is detected in an
■
When "Stop" is selected in "CPU Module Operation Setting at Error Detected"
When an error is detected, the operation depends on the setting of "Output Mode upon CPU Error" in the Module Parameter
of each module.
• When "Clear" is set: Output to the corresponding module is turned OFF.
• When "Hold" is set: Output to the corresponding module is retained.
For the setting method of module parameter, refer to the manual for each module.
■
When "Continue" is selected in "CPU Module Operation Setting at Error Detected"
The operation of the C Controller module does not stop.
Error detection setting
Set whether to detect errors.
[CPU Parameter]
[RAS Setting]
[Error Detections Setting]
Window
Displayed items
*1 If an operating module in which "Not Detected" is selected in the parameter is removed, a module verification error is not detected;
however, a stop error may occur if accessing the removed module by using programs, etc. Since the removed module is not accessible
even if it is mounted again, accessing the module by changing the module status from STOP to RUN may result in a stop error.
Item
Description
Setting
range
Default
Module Verify Error
Set whether to detect the module verification error.
• Detect
• Not
Detected
Detect
Fuse Blown
Set whether to detect the fuse blown in the controlled
module.
Synchronous Interrupt
Program (I44, I45)
Executing Time
Excessive
Execution Interval Exceed (I44, I45)
Set whether to detect the excessive execution time (I44,
I45).
Not Detected
Program Execution Section Exceed
(I45)
Set whether to detect the program execution section
exceed errors (I45).
Summary of Contents for MELSEC iQ-R C R12CCPU-V
Page 1: ...MELSEC iQ R C Controller Module User s Manual Application R12CCPU V ...
Page 2: ......
Page 23: ...1 EXECUTING PROGRAMS 1 3 I O Access Timing 21 1 MEMO ...
Page 32: ...30 3 MEMORY CONFIGURATION OF C Controller Module 3 4 Files MEMO ...
Page 257: ...I 255 MEMO ...
Page 261: ......