3. Setting
30
3.5. Setting Menu 2: Communication Settings (Setting the MODBUS
®
TCP communication)
Set the Default gateway existence.
If the default gateway exists on the Ethernet,
select “on” to communicate with other network.
oFF
on
④
MODBUS®TCP
Default gateway
existence
SET
DISPLAY
When the changed above settings of MODBUS® TCP are enabled,
set to "on."
(
When it is not set to “on,” the changed settings of MODBUS®TCP
do not become effective.
)
⑥
Communication
reset
oFF
on
SET
DISPLAY
SET
Set the Default gateway address.
If select “oFF” in
④
MODBUS®TCP Default gateway existence,
this display will be skipped.
⑤
MODBUS
®
TCP
Default gateway
address
* If invalid default gateway address is set, error code E05
is appears.
If that happens, press and set again after review
the default gateway address.
The following default gateway addresses cannot be configured.
・
0.0.0.0
・
xxx.xxx.xxx.255 (xxx are any values)
000.000.000.000 to 127.0.0.1 to 255.255.255.255
SET
According to the setting flow (page 16 to 21), save the changed
contents, or continue to the other setting menu.
If it is needed to set the MODBUS®RTU communication setting,
Select the menu number “2” again, and select “Mb.rtu” at
①
Communication setting selection.
Setting Menu