18
VG79D920H01
9-3. Twinning kit selection
9-3-1. Indoor unit twinning kit
Refer to the manual for the connected indoor unit.
9-3-2. Outdoor unit twinning kit
Select a proper outdoor unit twinning kit (sold separately) based on the outdoor unit configuration, using the table
below as a reference.
Configuration
Kit model
Single-outdoor-unit system
-
Two-outdoor-unit system
CMY-Y200VBK2
9-4. Pipe connection example
・
Example of pipe connection between outdoor units
Ⓐ
Ⓐ
Ⓑ
Ⓒ
Ⓐ
On-site piping
Ⓑ
Twinning Kit
Ⓒ
The pipe section before the twinning pipe must
have at least 500 mm (19-11/16 in) of straight
section.
・
Example of pipe connection between outdoor units and indoor units
Single-outdoor-unit system
Ⓐ
Outdoor unit
Ⓑ
1st branching (Refer to the manual for the connected
indoor unit.)
Ⓒ
Indoor unit
Ⓓ
Outdoor unit twinning kit
Ⓔ
Deformed pipe (Refer to the manual for the connected
indoor unit.)
*The total length of A
1
and A
2
is less than 10 m (32 ft).
Ⓑ
Ⓒ
Ⓒ
Ⓒ
Ⓒ
Ⓒ
Ⓐ
Two-outdoor-unit system
Ⓑ
Ⓒ
Ⓒ
Ⓒ
Ⓒ
Ⓒ
Ⓐ
Ⓐ
Ⓓ
Ⓔ
Unit 1
Unit 1
Unit 2