background image

Left or left-rear piping

Note:

Be sure to reattach the drain 
hose and the drain cap in case 
of left or left-rear piping.
Otherwise, it could cause drops 
of water to drip down from the 
drain hose.

1) Put the refrigerant piping and the drain hose together, 

then firmly apply felt tape (7) from the end. 

  Felt tape (7) overlap width should be 1/3 the tape 

width. Use a bandage stopper at the end of felt tape (7).

2) Pull out the drain cap at the rear right of the indoor unit. 

(Fig. 1)
•  Hold the convex section at the end and pull the 

drain cap.

3) Pull out the drain hose at the rear left of the indoor unit. 

(Fig. 2)
•  Hold the claw marked by the arrows and pull out the 

drain hose forward.

4) Put the drain cap into the section to which the drain 

hose is to be attached at the rear of the indoor unit.  
(Fig. 3)
•  Insert not sharp-edged tools such as screwdrivers 

into the hole at the end of the cap and insert the cap 
fully into the drain pan.

5) Insert the drain hose fully into the drain pan at the rear 

right of the indoor unit. (Fig. 4)
•  Check if the hose is hooked securely to the projec-

tion of its inserting part at the drain pan.

6) Insert the drain hose into wall hole sleeve (C), and 

hook the upper part of indoor unit on installation plate 
(1). Then, move the indoor unit completely to the left in 
order to make placing the piping in the back space of 
the unit easier.

7) Cut out a piece of cardboard from the shipping box, roll 

it up, hook it onto the back rib, and use it as a spacer 
to lift the indoor unit. (Fig. 5)

8) Connect the refrigerant piping with the extension pipe (B).
9) Thrust the lower part of the indoor unit into the installation plate (1).

3-2. FLARING WORK

1) Cut the copper pipe correctly with pipe cutter.  

(Fig. 1, 2)

2) Completely remove all burrs from the cut cross sec-

tion of pipe. (Fig. 3)
•  Put the end of the copper pipe to downward direc-

tion as you remove burrs in order to avoid to let 
burrs drop in the piping.

3) Remove flare nuts attached to indoor and outdoor 

units, then put them on pipe having completed burr 
removal. (Not possible to put them on after flaring 
work.) 

4) Flaring work (Fig. 4, 5). Firmly hold copper pipe in 

the dimension shown in the table. Select A mm from 
the table according to the tool you use.

5) Check 

•  Compare the flared work with Fig. 6.
•  If flare is noted to be defective, cut off the flared section and do flaring work 

again.

3-3. PIPE CONNECTION

•  Fasten flare nut with a torque wrench as specified in the table.
•  When fastened too tight, flare nut may break after a long period and cause refrigerant 

leakage.

•  Be sure to wrap insulation around the piping. Direct contact with the bare piping may re-

sult in burns or frostbite.

Indoor unit connection

Connect both liquid and gas pipings to indoor unit.
•  Apply a thin coat of refrigeration oil (J) on the flared ends of the pipes. Do not apply re-

frigeration oil on screw threads. Excessive tightening torque will result in damage on the 
screw.

•  For connection, first align the center, then tighten the first 3 to 4 turns of flare nut.
•  Use tightening torque table above as a guideline for indoor unit side union joint section, 

and tighten using two wrenches. Excessive tightening damages the flare section.

Outdoor unit connection

Connect pipes to stop valve pipe joint of the outdoor unit in the 
same manner applied for indoor unit.
•  For tightening, use a torque wrench or spanner and use the 

same tightening torque applied for indoor unit.

Rear, right, or downward piping

1) Put the refrigerant piping and the drain hose 

together, then firmly apply piping tape (G) 
from the end.

2) Insert the piping and the drain hose into the 

wall hole sleeve (C), and hook the upper part 
of the indoor unit on the installation plate (1).

3) Check if the indoor unit is hooked securely on the installation plate (1) by moving 

the unit to left and right.

4) Thrust the lower part of the indoor unit into the installation plate (1).

Pipe diameter 

(mm)

Nut 

(mm)

A (mm)

Tightening torque

Clutch type 

tool  

for R410A

Clutch type 

tool  

for R22

Wing nut 

type tool  

for R22

N•m

kgf•cm

ø 6.35  (1/4”)

17

0 to 0.5

1.0 to 1.5

1.5 to 2.0

13.7 to 17.7 140 to 180

ø 9.52  (3/8”)

22

34.3 to 41.2 350 to 420

ø12.7  (1/2”)

26

2.0 to 2.5

49.0 to 56.4 500 to 575

ø15.88  (5/8”)

29

73.5 to 78.4 750 to 800

Drain Piping

•  If the extension drain hose has to pass through a room, be sure to wrap it with com-

mercially sold insulation. 

•  The drain hose should point downward for easy drain flow. (Fig. 1)
•  If the drain hose provided with the indoor unit is too short, connect it with drain hose (I) 

that should be provided at your site. (Fig. 2)

•  When connecting the drain hose to the hard vinyl chloride pipe, be sure to insert it 

securely into the pipe. (Fig. 3)

Do not make drain piping as shown below.

Do not raise

Accumulated 
drain water

Air

Waving

Water 
leakage

Water 
leakage

Water 
leakage

Tip of drain 
hose dipped 
in water

Ditch

At least 
50 mm 
gap

Cut off in case of 
right piping.

Cut off in case of 
downward piping.

Copper 
pipe

Good

Tilted Uneven Burred

No good

Fig. 1

Fig. 2

Smooth all 
around

Even length 
all around

Inside is shin-
ing without any 
scratches.

Flare nut

Die

Fig. 5

Fig. 6

Downward 
slope

Drain 
hose

Soft hose 
I.D. 15 mm

Drain hose

Hard vinyl chloride 
pipe I.D. 30 mm

Insert  
securely

Different 
diameter joint

70 cm or 
more

Fig. 1

Fig. 2

Fig. 3

Drain cap

Drain cap

Drain hose

Cut off in case of left 
piping.

Drain cap

Piping tape (G)

Drain hose

Fig. 1

Fig. 2

Fig. 3

Fig. 4

Fig. 5

Felt tape (7)

3.  OUTDOOR UNIT INSTALLATION

Copper pipe

3-1. CONNECTING WIRES FOR OUTDOOR UNIT

1) Open the service panel.
2) Loosen terminal screw, and connect indoor/outdoor unit connecting wire (A) from 

the indoor unit correctly on the terminal block. Be careful not to make mis-wiring. Fix 
the wire to the terminal block securely so that no part of its core is appeared, and no 
external force is conveyed to the connecting section of the terminal block. 

3) Firmly tighten the terminal screws to prevent them from loosening. After tightening, 

pull the wires lightly to confirm that they do not move.

4) Connect power supply cord (K).
5) Fix indoor/outdoor unit connecting wire (A) and power supply cord (K) with the cord 

clamp.

6) Close the service panel securely.

Lead wire

Terminal block

Cord clamp

•  Make earth wire a little longer than 

others. (More than 100 mm)

•  For future servicing, give extra 

length to the connecting wires.

•  Be sure to attach each screw to 

its correspondent terminal when 
securing the cord and/or the wire 
to the terminal block.

Power supply cord 

(K)

35 mm

15 mm

Burr

Copper pipe

Spare reamer

Pipe cutter

Clutch type

Flaring tool

Fig. 4

Fig. 3

Wing nut type

Indoor/outdoor 

unit connecting 

wire (A)

3-4. INSULATION AND TAPING

1) Cover piping joints with pipe cover.
2) For outdoor unit side, surely insulate every piping including valves.
3) Using piping tape (G), apply taping starting from the entry of outdoor unit.

•  Stop the end of piping tape (G) with tape (with adhesive agent attached).
•  When piping have to be arranged through above ceiling, closet or where the tempera-

ture and humidity are high, wind additional commercially sold insulation to prevent 
condensation.

 WARNING

When installing the unit, securely connect the refrigerant 
pipes before starting the compressor.

Summary of Contents for JG79B249H01

Page 1: ...h national wiring regulations N Install an earth leakage breaker depending on the instal lation place If an earth leakage breaker is not installed it could cause electric shock N Perform the drainage piping work securely according to the installation manual If there is defect in the drainage piping work water could drop from the unit soaking and damaging household goods N Do not touch the air inle...

Page 2: ...ttle longer than others More than 60 mm Do not fold the excess wire or cram it into small space Take caution not to damage the wires Be sure to attach each screw to its correspond ent terminal when securing the cord and or the wire to the terminal block Note Do not place the wires between the in door unit and the installation plate 1 Damaged wire could cause heat generation or fire Wall Outdoor sid...

Page 3: ...in hose together then firmly apply piping tape G from the end 2 Insert the piping and the drain hose into the wall hole sleeve C and hook the upper part of the indoor unit on the installation plate 1 3 Check if the indoor unit is hooked securely on the installation plate 1 by moving the unit to left and right 4 Thrust the lower part of the indoor unit into the installation plate 1 Pipe diameter mm...

Page 4: ...or unit from the installation plate When releasing the corner part release both left and right bottom corner part of indoor unit and pull it downward and forward as shown in the figure on the right If the above method cannot be used Remove the panel Then insert hexagonal wrenches into the square holes on the left and right sides of the unit and push them up as shown in the following figure The botto...

Reviews: