Mitsubishi Electric JG79A114H02 Installation Manual Download Page 3

Left or left-rear piping

Note:

Be sure to reattach the drain 
hose and the drain cap in case 
of left or left-rear piping.
Otherwise, it could cause drops 
of water to drip down from the 
drain hose.

1) Put the refrigerant piping and the drain hose together, 

WKHQ¿UPO\DSSO\IHOWWDSHIURPWKHHQG

Felt tape (7) overlap width should be 1/3 the tape 

width. Use a bandage stopper at the end of felt tape (7).

2) Pull out the drain cap at the rear right of the indoor unit. 

(Fig. 1)

‡ +ROGWKHFRQYH[VHFWLRQDWWKHHQGDQGSXOOWKH

drain cap.

3) Pull out the drain hose at the rear left of the indoor unit. 

(Fig. 2)

‡ +ROGWKHFODZPDUNHGE\WKHDUURZVDQGSXOORXWWKH

drain hose forward.

4) Put the drain cap into the section to which the drain 

hose is to be attached at the rear of the indoor unit. 
(Fig. 3)
• Insert not sharp-edged tools such as screwdrivers 

into the hole at the end of the cap and insert the cap 

IXOO\LQWRWKHGUDLQSDQ

,QVHUWWKHGUDLQKRVHIXOO\LQWRWKHGUDLQSDQDWWKHUHDU

right of the indoor unit. (Fig. 4)

‡ &KHFNLIWKHKRVHLVKRRNHGVHFXUHO\WRWKHSURMHF

-

tion of its inserting part at the drain pan.

6) Insert the drain hose into wall hole sleeve (C), and 

hook the upper part of indoor unit on installation plate 

7KHQPRYHWKHLQGRRUXQLWFRPSOHWHO\WRWKHOHIWLQ

order to make placing the piping in the back space of 
the unit easier.

&XWRXWDSLHFHRIFDUGERDUGIURPWKHVKLSSLQJER[UROO

it up, hook it onto the back rib, and use it as a spacer 
to lift the indoor unit. (Fig. 5)

&RQQHFWWKHUHIULJHUDQWSLSLQJZLWKWKHH[WHQVLRQSLSH%

9) Thrust the lower part of the indoor unit into the installation plate (1).

3-1. CONNECTING WIRES FOR OUTDOOR UNIT

1) Open the service panel.
2) Loosen terminal screw, and connect indoor/outdoor unit connecting wire (A) from 

WKHLQGRRUXQLWFRUUHFWO\RQWKHWHUPLQDOEORFN%HFDUHIXOQRWWRPDNHPLVZLULQJ)L[
WKHZLUHWRWKHWHUPLQDOEORFNVHFXUHO\VRWKDWQRSDUWRILWVFRUHLVDSSHDUHGDQGQR
H[WHUQDOIRUFHLVFRQYH\HGWRWKHFRQQHFWLQJVHFWLRQRIWKHWHUPLQDOEORFN

)LUPO\WLJKWHQWKHWHUPLQDOVFUHZVWRSUHYHQWWKHPIURPORRVHQLQJ$IWHUWLJKWHQLQJ

SXOOWKHZLUHVOLJKWO\WRFRQ¿UPWKDWWKH\GRQRWPRYH

&RQQHFWSRZHUVXSSO\FRUG.
)L[LQGRRURXWGRRUXQLWFRQQHFWLQJZLUH$DQGSRZHUVXSSO\FRUG.ZLWKWKHFRUG

clamp.

&ORVHWKHVHUYLFHSDQHOVHFXUHO\

3-2. FLARING WORK

&XW WKH FRSSHU SLSH FRUUHFWO\ ZLWK SLSH FXWWHU

(Fig. 1, 2)

&RPSOHWHO\UHPRYHDOOEXUUVIURPWKHFXWFURVVVHF

-

tion of pipe. (Fig. 3)
• Put the end of the copper pipe to downward direc-

WLRQDV\RXUHPRYHEXUUVLQRUGHUWRDYRLGWROHW

burrs drop in the piping.

3) Remove flare nuts attached to indoor and outdoor 

units, then put them on pipe having completed burr 
removal. (Not possible to put them on after flaring 
work.)

)ODULQJ ZRUN )LJ   )LUPO\ KROG FRSSHU SLSH LQ

the dimension shown in the table. Select A mm from 

WKHWDEOHDFFRUGLQJWRWKHWRRO\RXXVH

5) Check

‡ &RPSDUHWKHÀDUHGZRUNZLWK)LJ
‡ ,IÀDUHLVQRWHGWREHGHIHFWLYHFXWRIIWKHÀDUHGVHFWLRQDQGGRÀDULQJZRUN

again.

3-3. PIPE CONNECTION

‡ )DVWHQÀDUHQXWZLWKDWRUTXHZUHQFKDVVSHFL¿HGLQWKHWDEOH
‡ :KHQ IDVWHQHG WRR WLJKW ÀDUH QXW PD\ EUDNH DIWHU D ORQJ SHULRG DQG FDXVH UHIULJHUDQW

leakage.

Indoor unit connection

Connect both liquid and gas pipings to indoor unit.

‡ $SSO\DWKLQFRDWRIUHIULJHUDWLRQRLO-RQWKHVHDWVXUIDFHRISLSH
‡ )RUFRQQHFWLRQ¿UVWDOLJQWKHFHQWHUWKHQWLJKWHQWKH¿UVWWRWXUQVRIÀDUHQXW

• Use tightening torque table below as a guideline for indoor unit side union joint section, 

DQGWLJKWHQXVLQJWZRZUHQFKHV([FHVVLYHWLJKWHQLQJGDPDJHVWKHÀDUHVHFWLRQ

Outdoor unit connection

Connect pipes to stop valve pipe joint of the outdoor unit in the 
same manner applied for indoor unit.
• For tightening, use a torque wrench or spanner and use the 

same tightening torque applied for indoor unit.

Rear, right, or downward piping

1) Put the refrigerant piping and the drain hose 

WRJHWKHU WKHQ ILUPO\ DSSO\ SLSLQJ WDSH *

from the end.

2) Insert the piping and the drain hose into the 

wall hole sleeve (C), and hook the upper part 
of the indoor unit on the installation plate (1).

&KHFNLIWKHLQGRRUXQLWLVKRRNHGVHFXUHO\RQWKHLQVWDOODWLRQSODWHE\PRYLQJ

the unit to left and right.

4) Thrust the lower part of the indoor unit into the installation plate (1).

Pipe diameter 

(mm)

Nut

(mm)

A (mm)

Tightening torque

&OXWFKW\SH

tool

for R410A

&OXWFKW\SH

tool

for R22

Wing nut 

W\SHWRRO

for R22

N•m

kgf•cm

ø 6.35  (1/4”)

17

0 to 0.5

1.0 to 1.5

1.5 to 2.0

13.7 to 17.7 140 to 180

ø 9.52  (3/8”)

22

34.3 to 41.2 350 to 420

ø12.7  (1/2”)

26

2.0 to 2.5

49.0 to 56.4 500 to 575

ø15.88  (5/8”)

29

73.5 to 78.4 750 to 800

Drain Piping

‡ ,IWKHH[WHQVLRQGUDLQKRVHKDVWRSDVVWKURXJKDURRPEHVXUHWRZUDSLWZLWKFRP

-

PHUFLDOO\VROGLQVXODWLRQ

‡ 7KHGUDLQKRVHVKRXOGSRLQWGRZQZDUGIRUHDV\GUDLQÀRZ)LJ

• If the drain hose provided with the indoor unit is too short, connect it with drain hose (I) 

WKDWVKRXOGEHSURYLGHGDW\RXUVLWH)LJ

‡ :KHQFRQQHFWLQJWKHGUDLQKRVHWRWKHKDUGYLQ\OFKORULGHSLSHEHVXUHWRLQVHUWLW

VHFXUHO\LQWRWKHSLSH)LJ

Do not make drain piping as shown below.

Do not raise

Accumulated
drain water

Air

Waving

Water
leakage

Water
leakage

Water
leakage

Tip of drain 
hose dipped 
in water

Ditch

At least 
50 mm 
gap

Cut off in case of 
right piping.

Cut off in case of 
downward piping.

Copper
pipe

Good

Tilted Uneven Burred

No good

Fig. 1

Fig. 2

Burr

Copper pipe

Spare reamer

Pipe cutter

&OXWFKW\SH

Flaring tool

Fig. 4

Fig. 3

Smooth all 
around

Even length 
all around

Inside is shin-

LQJZLWKRXWDQ\

scratches.

Flare nut

Die

Fig. 5

Fig. 6

Downward
slope

Drain
hose

Soft hose 
I.D. 15 mm

Drain hose

+DUGYLQ\OFKORULGH

pipe I.D. 30 mm

Insert

VHFXUHO\

Different
diameter joint

70 cm or 
more

Fig. 1

Fig. 2

Fig. 3

Lead wire

Terminal block

Cord clamp

3RZHUVXSSO\

cord (K)

• Make earth wire a little longer 

than others. (More than 60 mm)

‡ )RU IXWXUH VHUYLFLQJ JLYH H[WUD

length to the connecting wires.

Drain cap

Drain cap

Drain hose

Cut off in case of left 
piping.

Drain cap

Piping tape (G)

Drain hose

Fig. 1

Fig. 2

Fig. 3

Fig. 4

Fig. 5

Felt tape (7)

3. OUTDOOR UNIT INSTALLATION

Copper pipe

:LQJQXWW\SH

Indoor/outdoor unit 
connecting wire (A)

3RZHUVXSSO\FRUG.

35 mm

15 mm

 WARNING

When installing the unit, securely connect the refrigerant
pipes before starting the compressor.

3-4. INSULATION AND TAPING

1) Cover piping joints with pipe cover.

)RURXWGRRUXQLWVLGHVXUHO\LQVXODWHHYHU\SLSLQJLQFOXGLQJYDOYHV
8VLQJSLSLQJWDSH*DSSO\WDSLQJVWDUWLQJIURPWKHHQWU\RIRXWGRRUXQLW

• Stop the end of piping tape (G) with tape (with adhesive agent attached).
• When piping have to be arranged through above ceiling, closet or where the tempera-

WXUHDQGKXPLGLW\DUHKLJKZLQGDGGLWLRQDOFRPPHUFLDOO\VROGLQVXODWLRQWRSUHYHQW

condensation.

Summary of Contents for JG79A114H02

Page 1: ...V FRXOG FDXVH WKH SLSHV WR EXUVW RU LQMXU N DVWHQ D ÀDUH QXW ZLWK D WRUTXH ZUHQFK DV VSHFL HG LQ this manual I IDVWHQHG WRR WLJKW D ÀDUH QXW PD EUHDN DIWHU D ORQJ SHULRG and cause refrigerant leakage N The unit shall be installed in accordance with national wiring regulations N Install an earth leakage breaker depending on the installa tion place If an earth leakage breaker is not installed it cou...

Page 2: ...J VFUHZ IRU î PP 2 to 5 G Piping tape 1 H 3XWW 1 I Drain hose or soft PVC hose 15 mm inner diameter or hard PVC pipe VP16 1 J Refrigeration oil 1 K 3RZHU VXSSO FRUG 1 8QLWV VKRXOG EH LQVWDOOHG E OLFHQVHG FRQWUDFWRU according to local code requirements Indoor terminal block Indoor outdoor unit connecting wire A Outdoor terminal block Earth wire JUHHQ HOORZ Make earth wire a little longer than other...

Page 3: ...W RI UHIULJHUDWLRQ RLO RQ WKH VHDW VXUIDFH RI SLSH RU FRQQHFWLRQ UVW DOLJQ WKH FHQWHU WKHQ WLJKWHQ WKH UVW WR WXUQV RI ÀDUH QXW Use tightening torque table below as a guideline for indoor unit side union joint section DQG WLJKWHQ XVLQJ WZR ZUHQFKHV FHVVLYH WLJKWHQLQJ GDPDJHV WKH ÀDUH VHFWLRQ Outdoor unit connection Connect pipes to stop valve pipe joint of the outdoor unit in the same manner appli...

Page 4: ...LGHV RI JDV SLSH DQG OLTXLG SLSH 2SHUDWLQJ ZLWKRXW IXOO RSHQLQJ ORZHUV WKH SHUIRUP ance and this causes trouble 8 Refer to 1 3 and charge the prescribed amount of refrigerant if needed Be sure to FKDUJH VORZO ZLWK OLTXLG UHIULJHUDQW 2WKHUZLVH FRPSRVLWLRQ RI WKH UHIULJHUDQW LQ WKH V VWHP PD EH FKDQJHG DQG DIIHFW SHUIRUPDQFH RI WKH DLU FRQGLWLRQHU 9 Tighten cap of service port to obtain the initial ...

Reviews: