
Left or left-rear piping
Note:
Be sure to reattach the drain
hose and the drain cap in case
of left or left-rear piping.
Otherwise, it could cause drops
of water to drip down from the
drain hose.
1) Put the refrigerant piping and the drain hose together,
WKHQ¿UPO\DSSO\IHOWWDSHIURPWKHHQG
Felt tape (7) overlap width should be 1/3 the tape
width. Use a bandage stopper at the end of felt tape (7).
2) Pull out the drain cap at the rear right of the indoor unit.
(Fig. 1)
+ROGWKHFRQYH[VHFWLRQDWWKHHQGDQGSXOOWKH
drain cap.
3) Pull out the drain hose at the rear left of the indoor unit.
(Fig. 2)
+ROGWKHFODZPDUNHGE\WKHDUURZVDQGSXOORXWWKH
drain hose forward.
4) Put the drain cap into the section to which the drain
hose is to be attached at the rear of the indoor unit.
(Fig. 3)
• Insert not sharp-edged tools such as screwdrivers
into the hole at the end of the cap and insert the cap
IXOO\LQWRWKHGUDLQSDQ
,QVHUWWKHGUDLQKRVHIXOO\LQWRWKHGUDLQSDQDWWKHUHDU
right of the indoor unit. (Fig. 4)
&KHFNLIWKHKRVHLVKRRNHGVHFXUHO\WRWKHSURMHF
-
tion of its inserting part at the drain pan.
6) Insert the drain hose into wall hole sleeve (C), and
hook the upper part of indoor unit on installation plate
7KHQPRYHWKHLQGRRUXQLWFRPSOHWHO\WRWKHOHIWLQ
order to make placing the piping in the back space of
the unit easier.
&XWRXWDSLHFHRIFDUGERDUGIURPWKHVKLSSLQJER[UROO
it up, hook it onto the back rib, and use it as a spacer
to lift the indoor unit. (Fig. 5)
&RQQHFWWKHUHIULJHUDQWSLSLQJZLWKWKHH[WHQVLRQSLSH%
9) Thrust the lower part of the indoor unit into the installation plate (1).
3-1. CONNECTING WIRES FOR OUTDOOR UNIT
1) Open the service panel.
2) Loosen terminal screw, and connect indoor/outdoor unit connecting wire (A) from
WKHLQGRRUXQLWFRUUHFWO\RQWKHWHUPLQDOEORFN%HFDUHIXOQRWWRPDNHPLVZLULQJ)L[
WKHZLUHWRWKHWHUPLQDOEORFNVHFXUHO\VRWKDWQRSDUWRILWVFRUHLVDSSHDUHGDQGQR
H[WHUQDOIRUFHLVFRQYH\HGWRWKHFRQQHFWLQJVHFWLRQRIWKHWHUPLQDOEORFN
)LUPO\WLJKWHQWKHWHUPLQDOVFUHZVWRSUHYHQWWKHPIURPORRVHQLQJ$IWHUWLJKWHQLQJ
SXOOWKHZLUHVOLJKWO\WRFRQ¿UPWKDWWKH\GRQRWPRYH
&RQQHFWSRZHUVXSSO\FRUG.
)L[LQGRRURXWGRRUXQLWFRQQHFWLQJZLUH$DQGSRZHUVXSSO\FRUG.ZLWKWKHFRUG
clamp.
&ORVHWKHVHUYLFHSDQHOVHFXUHO\
3-2. FLARING WORK
&XW WKH FRSSHU SLSH FRUUHFWO\ ZLWK SLSH FXWWHU
(Fig. 1, 2)
&RPSOHWHO\UHPRYHDOOEXUUVIURPWKHFXWFURVVVHF
-
tion of pipe. (Fig. 3)
• Put the end of the copper pipe to downward direc-
WLRQDV\RXUHPRYHEXUUVLQRUGHUWRDYRLGWROHW
burrs drop in the piping.
3) Remove flare nuts attached to indoor and outdoor
units, then put them on pipe having completed burr
removal. (Not possible to put them on after flaring
work.)
)ODULQJ ZRUN )LJ )LUPO\ KROG FRSSHU SLSH LQ
the dimension shown in the table. Select A mm from
WKHWDEOHDFFRUGLQJWRWKHWRRO\RXXVH
5) Check
&RPSDUHWKHÀDUHGZRUNZLWK)LJ
,IÀDUHLVQRWHGWREHGHIHFWLYHFXWRIIWKHÀDUHGVHFWLRQDQGGRÀDULQJZRUN
again.
3-3. PIPE CONNECTION
)DVWHQÀDUHQXWZLWKDWRUTXHZUHQFKDVVSHFL¿HGLQWKHWDEOH
:KHQ IDVWHQHG WRR WLJKW ÀDUH QXW PD\ EUDNH DIWHU D ORQJ SHULRG DQG FDXVH UHIULJHUDQW
leakage.
Indoor unit connection
Connect both liquid and gas pipings to indoor unit.
$SSO\DWKLQFRDWRIUHIULJHUDWLRQRLO-RQWKHVHDWVXUIDFHRISLSH
)RUFRQQHFWLRQ¿UVWDOLJQWKHFHQWHUWKHQWLJKWHQWKH¿UVWWRWXUQVRIÀDUHQXW
• Use tightening torque table below as a guideline for indoor unit side union joint section,
DQGWLJKWHQXVLQJWZRZUHQFKHV([FHVVLYHWLJKWHQLQJGDPDJHVWKHÀDUHVHFWLRQ
Outdoor unit connection
Connect pipes to stop valve pipe joint of the outdoor unit in the
same manner applied for indoor unit.
• For tightening, use a torque wrench or spanner and use the
same tightening torque applied for indoor unit.
Rear, right, or downward piping
1) Put the refrigerant piping and the drain hose
WRJHWKHU WKHQ ILUPO\ DSSO\ SLSLQJ WDSH *
from the end.
2) Insert the piping and the drain hose into the
wall hole sleeve (C), and hook the upper part
of the indoor unit on the installation plate (1).
&KHFNLIWKHLQGRRUXQLWLVKRRNHGVHFXUHO\RQWKHLQVWDOODWLRQSODWHE\PRYLQJ
the unit to left and right.
4) Thrust the lower part of the indoor unit into the installation plate (1).
Pipe diameter
(mm)
Nut
(mm)
A (mm)
Tightening torque
&OXWFKW\SH
tool
for R410A
&OXWFKW\SH
tool
for R22
Wing nut
W\SHWRRO
for R22
N•m
kgf•cm
ø 6.35 (1/4”)
17
0 to 0.5
1.0 to 1.5
1.5 to 2.0
13.7 to 17.7 140 to 180
ø 9.52 (3/8”)
22
34.3 to 41.2 350 to 420
ø12.7 (1/2”)
26
2.0 to 2.5
49.0 to 56.4 500 to 575
ø15.88 (5/8”)
29
73.5 to 78.4 750 to 800
Drain Piping
,IWKHH[WHQVLRQGUDLQKRVHKDVWRSDVVWKURXJKDURRPEHVXUHWRZUDSLWZLWKFRP
-
PHUFLDOO\VROGLQVXODWLRQ
7KHGUDLQKRVHVKRXOGSRLQWGRZQZDUGIRUHDV\GUDLQÀRZ)LJ
• If the drain hose provided with the indoor unit is too short, connect it with drain hose (I)
WKDWVKRXOGEHSURYLGHGDW\RXUVLWH)LJ
:KHQFRQQHFWLQJWKHGUDLQKRVHWRWKHKDUGYLQ\OFKORULGHSLSHEHVXUHWRLQVHUWLW
VHFXUHO\LQWRWKHSLSH)LJ
Do not make drain piping as shown below.
Do not raise
Accumulated
drain water
Air
Waving
Water
leakage
Water
leakage
Water
leakage
Tip of drain
hose dipped
in water
Ditch
At least
50 mm
gap
Cut off in case of
right piping.
Cut off in case of
downward piping.
Copper
pipe
Good
Tilted Uneven Burred
No good
Fig. 1
Fig. 2
Burr
Copper pipe
Spare reamer
Pipe cutter
&OXWFKW\SH
Flaring tool
Fig. 4
Fig. 3
Smooth all
around
Even length
all around
Inside is shin-
LQJZLWKRXWDQ\
scratches.
Flare nut
Die
Fig. 5
Fig. 6
Downward
slope
Drain
hose
Soft hose
I.D. 15 mm
Drain hose
+DUGYLQ\OFKORULGH
pipe I.D. 30 mm
Insert
VHFXUHO\
Different
diameter joint
70 cm or
more
Fig. 1
Fig. 2
Fig. 3
Lead wire
Terminal block
Cord clamp
3RZHUVXSSO\
cord (K)
• Make earth wire a little longer
than others. (More than 60 mm)
)RU IXWXUH VHUYLFLQJ JLYH H[WUD
length to the connecting wires.
Drain cap
Drain cap
Drain hose
Cut off in case of left
piping.
Drain cap
Piping tape (G)
Drain hose
Fig. 1
Fig. 2
Fig. 3
Fig. 4
Fig. 5
Felt tape (7)
3. OUTDOOR UNIT INSTALLATION
Copper pipe
:LQJQXWW\SH
Indoor/outdoor unit
connecting wire (A)
3RZHUVXSSO\FRUG.
35 mm
15 mm
WARNING
When installing the unit, securely connect the refrigerant
pipes before starting the compressor.
3-4. INSULATION AND TAPING
1) Cover piping joints with pipe cover.
)RURXWGRRUXQLWVLGHVXUHO\LQVXODWHHYHU\SLSLQJLQFOXGLQJYDOYHV
8VLQJSLSLQJWDSH*DSSO\WDSLQJVWDUWLQJIURPWKHHQWU\RIRXWGRRUXQLW
• Stop the end of piping tape (G) with tape (with adhesive agent attached).
• When piping have to be arranged through above ceiling, closet or where the tempera-
WXUHDQGKXPLGLW\DUHKLJKZLQGDGGLWLRQDOFRPPHUFLDOO\VROGLQVXODWLRQWRSUHYHQW
condensation.