3 SPECIFICATIONS
3.1 General Specifications
27
3
3
SPECIFICATIONS
3.1
General Specifications
*1 Includes the temperature inside the enclosure of the control panel on which the GOT is installed.
*2 If the ambient temperature exceeds 40°C, the absolute humidity must not exceed 90% RH at 40°C.
*3 Do not use or store the GOT under pressures higher than the atmospheric pressure of altitude 0m (0ft.). Failure to observe this
instruction may cause a malfunction. When the air inside the control panel is purged by pressurization, the surface sheet may be lifted
by high pressure. As a result, the touch panel may be difficult to press, and the sheet may be peeled off.
*4 This indicates the section of the power supply to which the equipment is assumed to be connected between the public electrical power
distribution network and the machinery within the premises. Category II applies to equipment for which electrical power is supplied from
fixed facilities. The surge voltage withstand level for up to the raged voltage of 300V is 2500V.
*5 This index indicates the degree to which conductive pollution is generated in the environment where the equipment is used. In pollution
degree 2, only non-conductive pollution occurs but temporary conductivity may be produced due to condensation.
Item
Specifications
Operating ambient temperature
*1
0 to 50°C
Storage ambient temperature
-20 to 60°C
Operating/Storage ambient humidity
10% RH to 90% RH, non-condensing
*2
Vibration resistance
Conforms to IEC
61131-2
Frequency
Acceleration
Half amplitude
Sweep Count
Under
intermittent
vibration
5 to 8.4Hz
-
3.5mm
10times each in
X, Y and Z
directions
8.4 to 150Hz
9.8m/s
2
-
Under
continuous
vibration
5 to 8.4Hz
-
1.75mm
-
8.4 to 150Hz
4.9m/s
2
-
Shock resistance
Conforms to IEC 61131-2 (147m/s
2
, 3 times each in the X, Y, and Z directions)
Operating atmosphere
No greasy fumes, corrosive gas, flammable gas, excessive conductive dust, and direct sunlight (as well as at storage)
Operating altitude
*3
2000m (6562ft) max.
Overvoltage category
*4
II or less
Pollution degree
*5
2 or less
Cooling method
Self-cooling
Grounding
Grounding with a ground resistance of 100
Ω
or less by using a ground cable that has a cross-sectional area of 2
mm
2
or more. If impossible, connect the ground cable to the control panel.
Summary of Contents for GOT SIMPLE Series
Page 1: ...GOT SIMPLE Series User s Manual GS21 model ...
Page 2: ......
Page 20: ...18 MEMO ...
Page 24: ...22 1 OVERVIEW 1 1 Features MEMO ...
Page 34: ...32 3 SPECIFICATIONS 3 4 GOT Connector Specifications MEMO ...
Page 40: ...38 4 PART NAME 4 3 Bottom MEMO ...
Page 62: ...60 7 WIRING 7 2 Wiring Inside and Outside the Panel MEMO ...
Page 76: ...74 10 LANGUAGE SETTING LANGUAGE 10 1 Display language setting MEMO ...
Page 130: ...128 12 DISPLAY AND OPERATION SETTINGS GOT SET UP 12 7 IP Filter Setting MEMO ...
Page 160: ...158 14 CLOCK SETTINGS TIME SETTING AND DISPLAY 14 1 Time Setting and Display MEMO ...
Page 268: ...266 16 GOT SELF CHECK DEBUG 16 3 FX3U ENET ADP Communication Setting Function MEMO ...
Page 274: ...272 17 MAINTENANCE 17 3 Clean MEMO ...
Page 280: ...278 20 ERROR MESSAGE LIST MEMO ...
Page 296: ...294 22 TROUBLESHOOTING 22 1 GOT Restoration Sheets MEMO ...
Page 298: ...296 23 CONNECTION MEMO ...
Page 305: ...24 APPENDIX 24 1 External Dimensions 303 24 MEMO ...
Page 309: ......