2 - 4
2. CONNECTION TO IAI ROBOT CONTROLLER
2.2 System Configuration
2.2.2
System Configuration for connecting to PCON, ACON, SCON, ERC2
When connecting to one controller
(1) When using the RS232 connection
(a) PCON, ACON, SCON, ERC2 (SIO specifications), ERC2 (NP/PN specifications)
*1
Product manufactured by IAI Corporation. For details of the product, contact IAI Corporation.
*2
Use ERC2- - - - - -SE- - .
*3
Use the following models.
ERC2- - - - - -NP- - , ERC2- - - - - -PN- -
RS232C
conversion
unit
Communication
cable
PCON
ACON
SCON
ERC2
GOT
Connection cable
IAI ROBO CYLINDER
Communication driver
Controller
Connection cable
GOT
Number of
connectable
equipment
Model name
Communication
cable
RS232C
conversion unit
Communication
Type
Connection
diagram number
Max.
distance
Option device
Model
PCON
ACON
SCON
ERC2 (NP/PN
specifications)
*3
CB-RCA-SIO050
*1
(5m)
RCB-CV-MW
*1
(0.3m)
RS-232
-
-
-
(Built into GOT)
1 GOT for 1
Controller
GT15-RS2-9P
15m
-
(Built into GOT)
ERC2 (SIO
specifications)
*2
CB-ERC2-SIO020
*1
+
CB-ERC2-PWBIO
*1
or
CB-ERC2-PWBIO
-RB
*1
RCB-CV-MW
*1
(0.3m)
RS-232
-
-
-
(Built into GOT)
1 GOT for 1
Controller
GT15-RS2-9P
15m
-
(Built into GOT)
Summary of Contents for GOT 1000 Series
Page 2: ......
Page 76: ...1 46 1 PREPARATORY PROCEDURES FOR MONITORING 1 6 Checking for Normal Monitoring ...
Page 78: ......
Page 114: ...2 36 2 CONNECTION TO IAI ROBOT CONTROLLER 2 7 Precautions ...
Page 232: ...5 18 5 CONNECTION TO OMRON TEMPERATURE CONTROLLER 5 7 Precautions ...
Page 254: ...6 22 6 CONNECTION TO KEYENCE PLC 6 4 Device Range that Can Be Set ...
Page 404: ...14 14 14 CONNECTION TO PANASONIC SERVO AMPLIFIER 14 7 Precautions ...
Page 432: ...REVISIONS 3 ...
Page 435: ......