14
Initial setting steps
Step 1: IP address setting
Step 2: Group setting
Step 3: Other settings
Step 4: Test run
Function list of GB-24A, and the Initial Setting Web.
*1: K transmission converter cannot be used. Select “Not used” for the K-control Units setting in the M-NET
Settings window.
Note
x
Initial setting can be set via the web through LAN. More functions can be set with the initial setting
web.
The functions that can be initialized using this unit are described in this manual. Refer to the initial
setting web operation manuals for more information.
x
The format in which the Web page address for each GB-24A is expressed on the Initial Setting
Web, as well as the default setting user name and password are shown below.
http:// [IP address of the GB-24A]/g-50/ administrator.html
Note: For example, type “http://192.168.1.1/g-50/administrator.html” if the GB-24A IP address is
[192.168.1.1].
Items
GB-24A
Initial Setting
Web
Remarks
M-NET address setting
The default value is 0.
IP address setting
(simple setting)
*The settings of the simple setting have
the priority over other settings.
Function selection
Presence/absence of K transmission
converter connection*1, local operation
prohibition setting, and external input
mode.
Group registration
Registration of interlocked
operation with the
ventilation unit
Service switch
Other settings
Available functions vary depending on
the tool.
7
Initial Setting
User
Default
user name
Default
password
Maintenance user
initial
init
√
√
√
√
√
√
√
√