This manual confers no industrial property rights or any rights of any other kind,
nor does it confer any patent licenses. Mitsubishi Electric Corporation cannot be
held responsible for any problems involving industrial property rights which may
occur as a result of using the contents noted in this manual.
Warranty
Exclusion of loss in opportunity and secondary loss from warranty liability
Regardless of the gratis warranty term, Mitsubishi shall not be liable for compensation to:
(1) Damages caused by any cause found not to be the responsibility of Mitsubishi.
(2) Loss in opportunity, lost profits incurred to the user by Failures of Mitsubishi products.
(3) Special damages and secondary damages whether foreseeable or not, compensation for
accidents, and compensation for damages to products other than Mitsubishi products.
(4) Replacement by the user, maintenance of on-site equipment, start-up test run
and other tasks.
For safe use
This product has been manufactured as a general-purpose part for general
industries, and has not been designed or manufactured to be incorporated in
a device or system used in purposes related to human life.
Before using the product for special purposes such as nuclear power, electric
power, aerospace, medicine or passenger movement vehicles, consult with
Mitsubishi Electric.
This product has been manufactured under strict quality control. However
when installing the product where major accidents or losses could occur if the
product fails, install appropriate backup or failsafe functions in the system.
•
•
•
HEAD OFFICE : TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
Side
A
Side
B
JAPANESE
ENGLISH
JY997D20801F
Side
B
Safety Precautions
(Read these precautions before use.)
This manual classifies the safety precautions into two categories:
and
.
Depending on the circumstances, procedures indicated by
may also
cause severe injury.
It is important to follow all precautions for personal safety.
Associated Manuals
Indicates that incorrect handling may cause hazardous
conditions, resulting in death or severe injury.
Indicates that incorrect handling may cause hazardous
conditions, resulting in medium or slight personal injury
or physical damage.
Manual name
Manual No.
Description
FX
3S
/FX
3G
/FX
3GC
/
FX
3U
/FX
3UC
Series
User's Manual
- Analog Control
Edition
JY997D16701
MODEL CODE:
09R619
Describes specifications for analog
control and programming method for
FX
3S
/FX
3G
/FX
3GC
/FX
3U
/FX
3UC
Series PLC.
FX
3S
/FX
3G
/FX
3GC
/
FX
3U
/FX
3UC
Series
Programming Manual
- B a s i c & A p p l i e d
Instruction Edition
JY997D16601
MODEL CODE:
09R517
Describes PLC programming for
basic/applied instructions and
devices.
FX
3G
Series
User's Manual
- Hardware Edition
JY997D31301
MODEL CODE:
09R521
Explains the FX
3G
Series PLC
specifications for I/O, wiring,
installation, and maintenance.
FX
3GC
Series
User's Manual
- Hardware Edition
JY997D45401
MODEL CODE:
09R533
Explains the FX
3GC
Series PLC
specifications for I/O, wiring,
installation, and maintenance.
FX
3U
Series
User’s Manual
- Hardware Edition
JY997D16501
MODEL CODE:
09R516
Explains the FX
3U
Series PLC
specifications for I/O, wiring,
installation, and maintenance.
FX
3UC
Series
User’s Manual
- Hardware Edition
JY997D28701
MODEL CODE:
09R519
Explains the FX
3UC
Series PLC
specifications for I/O, wiring,
installation, and maintenance.
MELSEC iQ-F FX5U
User’s Manual
(Hardware)
JY997D55301
MODEL CODE:
09R536
Explains the FX5U PLC
specifications for I/O, wiring,
installation, and maintenance.
MELSEC iQ-F FX5UC
User’s Manual
(Hardware)
JY997D61401
MODEL CODE:
09R558
Explains the FX5UC PLC
specifications for I/O, wiring,
installation, and maintenance.
How to obtain manuals
For product manuals or documents, consult with the Mitsubishi Electric dealer from
who you purchased your product.
Certification of UL, cUL standards
The following product has UL and cUL certification.
UL, cUL File Number:E95239
Models:
MELSEC FX
3U
series manufactured
FX
3U
-
4DA
Compliance with EC directive (CE Marking)
This note does not guarantee that an entire mechanical module produced in
accordance with the contents of this note will comply with the following standards.
Compliance to EMC directive and LVD directive for the entire mechanical module
should be checked by the user / manufacturer. For more details please contact the
local Mitsubishi Electric sales site.
Requirement for Compliance with EMC directive
The following products have shown compliance through direct testing (of the identified
standards below) and design analysis (through the creation of a technical construction
file) to the European Directive for Electromagnetic Compatibility (2014/30/EU) when
used as directed by the appropriate documentation.
Attention
This product is designed for use in industrial applications.
Type:
Programmable Controller (Open Type Equipment)
Models:
MELSEC FX
3U
series manufactured
from February 1st, 2006
FX
3U
-4DA
Caution for EC Directive
The FX
3U
-4DA have been found to be compliant to the European standards in
the aforesaid manual and directive. However, for the very best performance
from what are in fact delicate measuring and controlled output device Mitsubishi
Electric would like to make the following points;
As analog devices are sensitive by nature, their use should be considered care-
fully. For users of proprietary cables (integral with sensors or actuators), these
users should follow those manufacturers installation requirements.
Mitsubishi Electric recommend that shielded cables should be used. If NO other
EMC protection is provided, then users may experience temporary loss or
accuracy between ±10% in very heavy industrial areas.
However, Mitsubishi Electric suggest that if adequate EMC precautions are fol-
lowed for the users complete control system, users should expect accuracy as
specified in this manual.
•
Sensitive analog cable should not be laid in the same trunking or cable
conduit as high voltage cabling. Where possible users should run analog
cables separately.
•
Good cable shielding should be used. Ground the shield of the twisted
shielded cable at one point on the signal receiving side.
•
Please use FX
3U
-4DA while installed in a shielded enclosure. For the details,
refer to the following manual.
→
Refer to the FX
3G
Series User's Manual - Hardware Edition
→
Refer to the FX
3GC
Series User's Manual - Hardware Edition
→
Refer to the FX
3U
Series User's Manual - Hardware Edition
→
Refer to the FX
3UC
Series User's Manual - Hardware Edition
→
Refer to the MELSEC iQ-F FX5U User's Manual (Hardware)
→
Refer to the MELSEC iQ-F FX5UC User's Manual (Hardware)
Note for compliance with EN61131-2:2007
General note on the use of the power supply cable.
The FX
3U
-4DA unit requires that the cable used for power supply is 30 m or less.
1. Outline
The FX
3U
-4DA special function block for analog output converts digital values supplied
from PLC into analog values (voltage, current) and outputs those analog values from its
four output points.
1.1 Incorporated Items
Standard
Remark
EN61131-2:2007
Programmable controllers
- Equipment requirements and
tests
Compliance with all relevant aspects of the
standard.
EMI
• Radiated Emission
• Conducted Emission
EMS
• Radiated electromagnetic field
• Fast transient burst
• Electrostatic discharge
• High-energy surge
• Voltage drops and interruptions
• Conducted RF
• Power frequency magnetic field
Product
FX
3U
-4DA special function block for analog output
Accessories
•
Special unit/block No. label
•
Dust proof sheet
×
1
•
Installation manual (This manual)
1.2 External Dimensions, Part Names, and Terminal Layout
1.2.1
External Dimensions and Part Names
1.2.2 Terminal Layout
2. Installation
2.1 Arrangements
The product connects on the right side of an PLC main unit or extension units/blocks
(including special function units/blocks).
For connection to FX
3GC
/FX
3UC
Series PLC or FX
2NC
Series PLC extension block,
FX
2NC
-CNV-IF or FX
3UC
-1PS-5V is required.
For connection to FX5U/FX5UC PLC, FX5-CNV-BUS or FX5-CNV-BUSC is required.
For further information of installation arrangements, refer to the following manual.
→
For details, refer to the FX
3G
Series User's Manual - Hardware Edition.
→
For details, refer to the FX
3GC
Series User's Manual - Hardware Edition.
→
For details, refer to the FX
3U
Series User's Manual - Hardware Edition.
→
For details, refer to the FX
3UC
Series User's Manual - Hardware Edition.
→
For details, refer to the MELSEC iQ-F FX5U User's Manual (Hardware)
→
For details, refer to the MELSEC iQ-F FX5UC User's Manual (Hardware)
[1] Direct mounting hole:2 holes of
φ
4.5 (0.18") (mounting screw: M4 screw)
[2] Extension cable
[3] POWER LED (green):
Lit while 5V DC power is supplied from PLC.
[4] Terminal block for power supply (24V DC) (M3 terminal screw)
[5] Terminal block for analog output
[6] 24V LED (red):
Lit while 24V DC power is supplied properly to terminals [24+] and [24-].
[7] D/A LED (red): Flashes (at high speed) during D/A conversion.
[8] DIN rail mounting hook
[9] DIN rail mounting groove (35 mm (1.38") wide)
INSTALLATION
PRECAUTIONS
•
Use the product within the generic environment specifications described in PLC
main unit manual (Hardware Edition).
Never use the product in areas with excessive dust, oily smoke, conductive dusts,
corrosive gas (salt air, Cl
2
, H
2
S, SO
2
, or NO
2
), flammable gas, vibration or
impacts, or expose it to high temperature, condensation, or rain and wind.
If the product is used in such conditions, electric shock, fire, malfunctions,
deterioration or damage may occur.
•
Do not touch the conductive parts of the product directly.
Doing so may cause device failures or malfunctions.
•
Install the product securely using a DIN rail or mounting screws.
•
Install the product on a flat surface.
If the mounting surface is rough, undue force will be applied to the PC board,
thereby causing nonconformities.
•
When drilling screw holes or wiring, make sure that cutting and wiring debris do
not enter the ventilation slits of the PLC.
Failure to do so may cause fire, equipment failures or malfunctions.
•
Be sure to remove the dust proof sheet from the PLC's ventilation slits when
installation work is completed.
Failure to do so may cause fire, equipment failures or malfunctions.
•
Connect extension cables securely to their designated connectors.
Loose connections may cause malfunctions.
FX
3U
-4DA
FX
3U
-4DA
24V
D/A
[1]
[2]
[6]
[7]
[3]
[4]
[5]
[9]
[8]
80(3.15")
(mounting hole pitch)
90(3.55")
[Without top cover]
MASS(Weight) : Approx. 0.2kg(0.44lbs)
55(2.17")
87(3.43")
9(0.36")
4(0.16")
24+
24- V+
I+
VI-
V+
I+
V+
VI-
VI-
I+
V+
I+
VI-
CH1
CH2
CH3
CH4
Left side of the product
(Extension cable side)
2.2 Mounting
The product is mounted by the following method.
•
Direct mounting
•
DIN rail mounting
2.2.1
Direct Mounting
The product can be mounted with M4 screws by using the direct mounting holes.
Refer to the External Dimensions (section 1.2) for the product’s mounting hole
pitch information.
An interval space between each unit of 1 to 2 mm (0.04" to 0.08") is necessary.
For further information of direct installation, also refer to the following manual.
→
Refer to the FX
3G
Series User's Manual - Hardware Edition
→
Refer to the FX
3GC
Series User's Manual - Hardware Edition
→
Refer to the FX
3U
Series User's Manual - Hardware Edition
→
Refer to the FX
3UC
Series User's Manual - Hardware Edition
→
Refer to the MELSEC iQ-F FX5U User's Manual (Hardware)
→
Refer to the MELSEC iQ-F FX5UC User's Manual (Hardware)
2.2.2
DIN Rail Mounting
The product can be mounted on a DIN rail (DIN46227, 35mm width).
1) Fit the upper edge of the DIN rail mounting
groove (fig. A) onto the DIN rail.
2) Press the product against the DIN rail.
3) Connect the extension cable (fig. B) to the
main unit, input/output extension unit/block,
and special function unit/block on the left.
For the details of the extension cable con-
nection, refer to the following manual.
→
Refer to the FX
3G
Series User's
Manual - Hardware Edition
→
Refer to the FX
3GC
Series User's
Manual - Hardware Edition
→
Refer to the FX
3U
Series User's
Manual - Hardware Edition
→
Refer to the FX
3UC
Series User's
Manual - Hardware Edition
→
Refer to the MELSEC iQ-F FX5U User's
Manual (Hardware)
→
Refer to the MELSEC iQ-F FX5UC User's
Manual (Hardware)
3. Wiring
WIRING
PRECAUTIONS
•
Make sure to cut off all phases of the power supply externally before
attempting installation or wiring work.
Failure to do so may cause electric shock or damage to the product.
WIRING
PRECAUTIONS
•
Make sure to observe the following precautions in order to prevent
malfunctions under the influence of noise:
1) Do not bundle the power line or twisted shielded cable together with or
lay it close to the main circuit, high-voltage line, or load line.
Otherwise, noise disturbance and/or surge induction are likely to take
place. As a guideline, lay the control line 100mm (3.94") or more away
from the main circuit or high-voltage lines.
2) Ground the twisted shield cable at one point on the signal receiving side.
However, do not use common grounding with heavy electrical systems.
•
Make sure to properly wire to the terminal blocks in accordance with the
following precautions.
Failure to do so may cause electric shock, equipment failures, a short-circuit,
wire breakage, malfunctions, or damage to the product.
- The disposal size of the cable end should follow the dimensions
described in the manual.
- Tightening torque should follow the specifications in the manual.
- Tighten the screws using a Phillips-head screwdriver No.2 (shaft diameter
6mm (0.24") or less). Make sure that the screwdriver does not touch the
partition part of the terminal block.
1)
2)
A
3.1 Applicable Cable and Terminal Tightening Torque
The size of the terminal screws is M3.
The end disposal of the cable shows below.
Tighten the terminal to a torque of 0.5 to 0.8N
•
m.
Do not tighten terminal screws with a torque outside the abovementioned range.
Failure to do so may cause equipment failures of malfunctions.
•
When one wire is connected to one terminal
•
When two wires are connected to one terminal
3.2 Power Supply Wiring
For the power supply wiring, refer to the following manual.
→
Refer to the FX
3S
/FX
3G
/FX
3GC
/FX
3U
/FX
3UC
Series User’s Manual
- Analog Control Edition
3.3 Wiring of Analog Output
→
For the terminal layout, refer to Subsection 1.2.2
*1 For FX
3G
/FX
3U
/FX5U PLC (AC power type), the 24V DC service power
supply is also available.
*2 Leave the [
•
] terminal unconnected.
*3 Use a 2-core twisted shield wire for analog output line, and separate it from
other power lines or inductive lines.
*4 If there is ripple or noise in the output voltage, connect a capacitor of
approximately 0.1 to 0.47
µ
F 25 V in the vicinity of the signal receiving side.
*5 Ground the shielded wire at one point on the signal receiving side.
3.4 Grounding
Grounding should be performed as stated below.
•
The grounding resistance should be 100
Ω
or less.
•
Independent grounding should be performed for best results.
When independent grounding is not performed, perform "shared
grounding" of the following figure.
→
For details, refer to the FX
3G
Series User's Manual - Hardware Edition.
→
For details, refer to the FX
3GC
Series User's Manual - Hardware Edition.
→
For details, refer to the FX
3U
Series User's Manual - Hardware Edition.
→
For details, refer to the FX
3UC
Series User's Manual - Hardware Edition.
→
For details, refer to the MELSEC iQ-F FX5U User's Manual (Hardware)
→
For details, refer to the MELSEC iQ-F FX5UC User's Manual (Hardware)
•
The grounding wire size should be AWG 14 (2 mm
2
).
•
The grounding point should be close to the PLC, and all grounding wire
should be as short as possible.
φ
3.2 (0.13")
6.2 mm (0.24")
or less
Terminal
screw
Crimp
terminal
Terminal
6.2 mm (0.24")
or less
φ
3.2 (0.13")
6.3 mm (0.25")
or more
6.3 mm (0.25")
or more
Terminal
screw
Crimp
terminal
Terminal
6.2 mm (0.24")
or less
6.2 mm (0.24")
or less
φ
3.2 (0.13")
φ
3.2 (0.13")
FX
3U
-4DA
24V DC
+15V
I+
VI-
V+
24+
24-
*4
-15V
*2
I+
VI-
V+
External power
supply wiring
Using voltage output
Using current output
Grounding
(Ground resistance:
100
Ω
or less)
Shield *3
Shield *3
*1
ch : represents the channel number.
ch
ch
ch
ch
*5
*5
PLC
Another
equipment
PLC
Another
equipment
PLC
Another
equipment
Shared grounding
Good condition
Common grounding
Not allowed
Independent grounding
Best condition
4. Specifications
4.1 Applicable PLC
The version number can be checked by monitoring D8001 as the last three digits
indicate it.
*1 An FX
2NC
-CNV-IF or FX
3UC
-1PS-5V is necessary to connect the FX
3U
-4DA with
the FX
3GC
/FX
3UC
PLC.
*2 Up to 7 units can be connected to the FX
3UC
-32MT-LT(-2) PLC.
*3 An FX5-CNV-BUS or FX5-CNV-BUSC is necessary to connect the FX
3U
-4DA
with the FX5U/FX5UC PLC.
4.2 General Specifications
For the general specifications other than the following, refer to the manual of the PLC
main unit.
The items other than the following are equivalent to those of the PLC main unit.
→
Refer to the FX
3G
Series User's Manual - Hardware Edition
→
Refer to the FX
3GC
Series User's Manual - Hardware Edition
→
Refer to the FX
3U
Series User's Manual - Hardware Edition
→
Refer to the FX
3UC
Series User's Manual - Hardware Edition
→
Refer to the MELSEC iQ-F FX5U User's Manual (Hardware)
→
Refer to the MELSEC iQ-F FX5UC User's Manual (Hardware)
4.3 Power Supply Specifications
STARTUP AND
MAINTENANCE
PRECAUTIONS
•
Do not disassemble or modify the PLC.
Doing so may cause fire, equipment failures, or malfunctions.
* For repair, contact your local Mitsubishi Electric representative.
•
Do not drop the product or exert strong impact to it.
Doing so may cause damage.
DISPOSAL
PRECAUTIONS
•
Please contact a certified electronic waste disposal company for the
environmentally safe recycling and disposal of your device.
TRANSPORT AND
STORAGE PRECAUTIONS
•
The product is a precision instrument. During transportation, avoid impacts larger
than those specified in the general specifications by using dedicated packaging
boxes and shock-absorbing palettes.
Failure to do so may cause failures in the product.
After transportation, verify operation of the product and check for damage of the
mounting part, etc.
Model name
Applicability
FX
3G
Series PLC
Ver. 1.00 or later (from first production)
Up to 8 blocks can be extended
FX
3GC
Series PLC
*1
Ver. 1.40 or later (from first production)
Up to 8 blocks can be extended
FX
3U
Series PLC
Ver. 2.20 or later (from first production)
Up to 8 blocks can be extended
FX
3UC
Series PLC
*1
Ver. 1.30 or later (from the production manufactured in August,
2004 with SER No. 48
)
Up to 8 blocks can be extended
*2
FX5U PLC
*3
Ver. 1.000 or later (from first production)
Up to 8 blocks can be extended
FX5UC PLC
*3
Ver. 1.000 or later (from first production)
Up to 8 blocks can be extended
Item
Specification
Dielectric withstand
voltage
500V AC for one minute
Between all terminals and
ground terminal of PLC
main unit
Insulation resistance
5 M
Ω
o r h i g h e r b y 5 0 0 V D C
insulation resistance tester
Item
Specification
D/A conversion
circuit driving power
24V DC
±
10%, 160mA
(24V DC power is supplied from the power connector.)
CPU driving power
5V DC, 120mA
(5V DC power is supplied from the internal power supply of
main unit.)
4.4 Performance Specifications
*1 Change the offset and gain values to change the output characteristics.
However, the resolution doesn’t change even when the offset and gain values
change.
When analog value (mV,
µ
A) specification is enabled in the output mode 1 or 4,
the offset value and the gain value don’t change.
*2 The offset and the gain should satisfy the following condition:
1 V
≤
(Gain - Offset)
≤
10 V
*3 The offset and the gain should satisfy the following condition:
3 mA
≤
(Gain - Offset)
≤
30 mA
*4 When the external load is less than 30k
Ω
, please use the output corrective
function by load resistance (only in voltage output mode). Setting of output
corrective function by load resistance, refer to the following manual.
→
Refer to the FX
3S
/FX
3G
/FX
3GC
/FX
3U
/FX
3UC
Series User's Manual
- Analog Control Edition
*5 The output characteristics vary depending on the output mode to be used.
For the details of the output characteristics, refer to the following manual.
→
Refer to the FX
3S
/FX
3G
/FX
3GC
/FX
3U
/FX
3UC
Series User’s Manual
- Analog Control Edition
Item
Description
Voltage output
Current output
Analog output
range
-10 to +10V DC
(External load: 1k
Ω
to 1M
Ω
)
0 to 20mA, 4 to 20mA DC
(External load: 500
Ω
or less)
Offset
*1
-10 to +9V
*2
0 to 17mA
*3
Gain
*1
-9 to +10V
*2
3 to 30mA
*3
Digital input
With sign, 16bits, binary
15bits, binary
Resolution
0.32mV (20V/64000)
0.63
µ
A (20mA/32000)
Total
accuracy
*4
• ±
0.3% (
±
60mV) for full scale
of 20V (when ambient
temperature is 25
°
C
±
5
°
C)
• ±
0.5% (
±
100mV) for full scale
of 20V (when ambient
temperature is 0
°
C to 55
°
C)
• ±
0.3% (
±
60
µ
A) for full scale of
20mA (when ambient
temperature is 25
°
C
±
5
°
C)
• ±
0.5% (
±
100
µ
A) for full scale
of 20mA (when ambient
temperature is 0
°
C to 55
°
C)
A/D conversion
time
1ms (The number of selected channels will not affect this value.)
Output
characteristics
*5
Insulation
method
•
The photo-coupler insulates the analog output area from the
PLC.
•
The DC-DC converter insulates the analog output area from the
power supply unit.
•
Channels are not insulated from each other.
Occupied
points
8 point (Count either the input or output points of the PLC.)
Digital
value
+10
+10.2
-10.2
-10
-32000
+32000
+32640
-32640
Output mode 0
Output voltage(V)
0
20.32
4
32000
20
32640
Output mode 3
Output current(mA)
Digital value
Output mode 2
0
20.4
32000
20
32640
Output current(mA)
Digital value
4.5 Output characteristics
The output characteristics in each output mode are as follows.
Output
mode
Output mode
Analog output
range
Digital input
range
0
Voltage output mode
-10 to +10V
-32000 to +32000
1
Voltage output analog value
mV specification mode
-10 to +10V
-10000 to +10000
2
Current output mode
0 to 20mA
0 to 32000
3
Current output mode
4 to 20mA
0 to 32000
4
Current output analog value
µ
A specification mode
0 to 20mA
0 to 20000
Note: This symbol mark is for China only.
含有有害6物质的名称,含有量,含有部品
本产品中所含有的有害6 物质的名称,含有量,含有部品如下表
所示。
产品中有害物质的名称及含量
本表格依据SJ/T 11364的规定编制。
○:表示该有害物质在该部件所有均质材料中的含量均在GB/T 26572
规定的限量要求以下。
×:表示该有害物质至少在该部件的某一均质材料中的含量超出GB/T
26572规定的限量要求。
部件名称
有害物质
铅
(Pb)
汞
(Hg)
镉
(Cd)
六价铬
(Cr(VI))
多溴联苯
(PBB)
多溴
二苯醚
(PBDE)
可编程
控制器
外壳
印刷基板
○
○
○
○
○
○
○
○
○
○
○
×
「电器电子产品有害物质限制使用标识要求」的表示方式
基于中国标准法的参考规格:GB/T15969.2
FX
3U
-4DA
INSTALLATION MANUAL
This manual describes the part names, dimensions, mounting, and specifications
of the product. Before use, read this manual and the manuals of all relevant
products fully to acquire proficiency in handling and operating the product. Make
sure to learn all the product information, safety information, and precautions.
Store this manual in a safe place so that it can be taken out and read whenever
necessary. Always forward it to the end user.
Registration:
Phillips is a registered trademark of Phillips Screw Company.
The company and product names described in this manual are registered
trademarks or the trademarks of their respective companies.
Effective May 2018
Specifications are subject to change without notice.
©
2006 Mitsubishi Electric Corporation
Manual Number JY997D20801