Mitsubishi Electric FX2N-4AD User Manual Download Page 2

HEAD OFFICE

: MITSUBISHI DENKI BLDG MARUNOUTI TOKYO 100-8310

TELEX : J24532 CABLE MELCO TOKYO

HIMEJI WORKS : 840, CHIYODA CHO, HIMEJI, JAPAN

In buffer memory locations (BFMs) marked with an “*” data can be written from the PLC using the TO
instruction.

For buffer memories (BFMs) without “*” mark, data can be read by the PLC using the FROM instruction.

Before reading from the analog special function block, ensure that the appropriate settings have been sent
to the analog special function block. Otherwise, the previous values held in the analog block will be used.

The buffer memory also gives a facility to adjust the offset and gain via software.

Offset (intercept): The analog input value when the digital output becomes 0.

Gain (slope): The analog input value when the digital output b1000.

1) Channel Selection

Channel selection is made by a 4 character HEX number HOOOO in buffer memory BFM #0.
The least significant character controls channel 1 and the 4th character controls channel 4.

Setting of each character is as follows:

O = 0: Preset range (-10V to +10V)

O = 2: Preset range (-20mA to +20mA)

O = 1: Preset range (+4mA to +20mA) 

O = 3: Channel OFF

Example: H3310

CH1

: Preset range (-10V to +10V)

CH2

: Preset range (+4mA to +20mA)

CH3, CH4: Channel OFF

2) Analog to Digital Conversion Speed Change

By writing 0 or 1 to BFM #15 of the FX

2N

-4AD, the speed at which A/D conversion is performed can be

changed.
However the following points should be noted:
To maintain a high speed conversion rate, use the FROM/TO instructions as seldom as possible.

NOTE: When a conversion speed change is made, BFM #1-#4 are set to their default values

immediately after the change. This is regardless of the values they held originally. Bear this in
mind if a speed change will be made as part of the normal program execution.

3) Adjusting Gain and Offset values

a) When buffer memory BFM #20 is activated by setting it to K1, all settings within the analog special

function block are reset to their default settings. This is a very quick method to erase any
undesired gain and offset adjustments.

b) If (b1, b0) of BFM #21 is set to (1,0), gain and offset adjustments are prohibited to prevent

inadvertent changes by the operator. In order to adjust the gain and offset values, bits (b1, b0)
must be set to (0,1). The default is (0,1).

c)

Offset and gain values of BFM #23 and #24 are sent respectively to the offset and gain resisters
in non-volatile memory of the specified input channels. Input channels to be adjusted are
specified by the appropriate G-O (gain-offset) bits of BFM #22.
Example:If bits G1 and O1 are set to 1, input channel 1 will be adjusted when BFM #22 is written 

to by a TO instruction.

d) Channels can be adjusted individually or together with the same gain and offset values.

e) Offset and gain values in BFM #23 and #24 are in units of mV or m A. Due to the resolution of the

unit the actual response will be in steps of 5mV or 20 m A.

4) Status Information BFM #29

NOTE:

b4 to b7, b9 and b13 to b15 are undefined.

Bit devices of BFM #29

ON

OFF

b0 : Error

When any of b1 to b4 is ON.
If any of b2 to b4 is ON, A/D 
conversion of all the channels is 
stopped.

No error

b1 : Offset/gain error

Offset/Gain data in the EEPROM 
is corrupted or adjustment error.

Offset/Gain data normal

b2 : Power source abnormality

24V DC power supply failure.

Power supply normal

b3 : Hardware error

A/D converter or other hardware 
failure.

Hardware Normal

b10 : Digital range error

Digital output value is less than 
-2048 or more than +2047

Digital output value is normal.

b11 : Averaging error

Number of averaging samples is 
4097 or more or 0 or less 
(default of 8 will be used)

Averaging is normal.
(between 1 and 4096)

b12 : Offset/gain adjust prohibit

Prohibit-(b1, b0) of BFM #21 is 
set to (1, 0)

Permit-(b1, b0) of BFM #21 is 
set to (0,1)

5) Identification Code BFM #30

The identification (or ID) code number for a Special Function Block is read using the FROM
instruction.
This number for the FX

2N

-4AD Special Function Block unit is K2010.

The user’s program in the PLC can use this facility in the program to identify the special function block
before commencing data transfer from and to the special function block.

CAUTION

Values of BFM #0, #23 and #24 are copied to the EEPROM memory of the FX

2N

-4AD.

BFM #21 and BFM #22 are only copied when data is written to the gain/offset command
buffer BFM #22. Also, BFM #20 causes the resetting of the EEPROM memory. The
EEPROM has a life of about 10,000 cycles (changes), so do not use programs which
frequently change these BFMs.

Due to the time needed to write to the EEPROM memory, a delay of 300 ms is required
between instructions that cause a write to the EEPROM.
Therefore, a delay timer should be used before writing to the EEPROM for a second time.

7. DEFINING GAIN AND OFFSET

Offset and gain can be set independently or together. Reasonable offset ranges are -5V to +5V or -20mA
to +20mA, and gain value - offset value = 1V to 15V or 4mA to 32mA. Gain and offset can be adjusted by
software in the main unit (see program example 2)

Bit device’s b1, b2 of the gain/offset BFM #21 should be set to 0, 1 to allow adjustment.

Once adjustment is completed these bit devices should be set to 1, 0 to prohibit any further changes.

8. EXAMPLE PROGRAM

8.1 Basic Program

In the following example, channels CH1 and CH2 are used as voltage inputs. The FX

2N

-4AD block is

connected at the position of special function block No. 0. The number of averaged samples is set at 4 and
data registers D0 and D1 of the main unit receive the averaged digital data.

G a i n   d e te r m i n e s  t h e   a n g l e   o r  s l o p e   o f   th e
calibration line, identified at a digital value of 1000.

Offset is the ’Position’ of the calibrated line,
identified at a digital value of 0.

a) Small gain value: Large steps in digital 

readings

b) Zero gain value: default (5V or 20mA)
c)

Large gain value: Small steps in digital 

readings

d) Negative offset
e) Zero offset: default (0V or 4mA)

f)

Positive offset

+1,000

Analog

Digital

Gain value

(a)

(b)

(c)

Gain

Analog

Digital

Offset value

(d)

(e)

(f)

Offset

0

M8002

initial
pulse

FROM      K0      K30      D4      K1

 CMP      K2010     D4      M0

TO        K0        K0      H3300   K1

P

M1

TO        K0        K1        K4       K2

FROM   K0       K29   K4M10    K1

M10 M20

FROM   K0        K5       D0        K2

NO

error

Digital output
value is normal

The ID code for the special function block at position "0" is
read from BFM #30 of that block and stored at D4 in the main
unit.
This is compared with K2010 to check that the block is a
FX

2N

-4AD, if OK M1 is turned ON. These two program steps

are not strictly needed to perform an analog read. They are
however a useful check and are recommended as good
practice.

The analog input channels (CH1, CH2) are setup by writing
H3300 to the BFM #0 of the FX

2N

-4AD.

The number of averaged samples for CH1 and CH2 is set to 4
by writing 4 to the BFM #1 and #2 respectively.
Do not execute the pulse form of the instruction.

The operational status of the FX

2N

-4AD is read from BFM #29

and output as bit devices of the main unit.

If there are no errors in the operation of the FX

2N

-4AD, then

the averaged data BFM's are read.
In the case of this example BFM #5 and #6 are read into the
main unit and stored in D0 and D1. These devices contain the
averaged data for CH1 and CH2 respectively.

8.2 Using gain and offset in a program

The following is an example of changing the offset value on input channel CH1 to 0V and the gain value to
2.5V.
The FX

2N

-4AD block is in the position of block No. 0 (i. e. closest to the main unit).

Example: Adjusting gain/offset by PLC programing

9. DIAGNOSTICS

9.1 Preliminary checks

I.

Check whether the input wiring and/or extension cables are properly connected on the FX

2N

-4AD

analog special function block

II.

Check that the PLC system configuration limits have not been exceeded, i. e. the number of special
function blocks, and the total system I/O are within the specified range.

III. Ensure that the correct operating range has been selected for the application.

IV. Check that there is no power overload on either the 5V or 24V power sources, remember the loading

on a main unit or a powered extension unit varies according to the number of extension blocks or
special function blocks connected.

V.

Make sure that the main unit has been switched to RUN.

9.2 Error checking

If the FX

2N

-4AD special function block does not seem to operate normally, check the following items.

Check the status of the POWER LED.
Lit

:The extension cable is properly connected.

Otherwise :Check the connection of the extension cable.

Check the external wiring.

Check the status of the “24V” LED (top right corner of the FX

2N

-4AD).

Lit

:FX

2N

-4AD is OK, 24V DC power source is OK.

Otherwise :Possible 24VDC power failure, if OK possible FX

2N

-4AD failure.

Check the status of the “A/D” LED (top right corner of the FX

2N

-4AD).

Lit

:A/D conversion is proceeding normally.

Otherwise :Check buffer memory #29 (error status). If any bits (b2 and b3) are ON, then this is why 

the A/D LED is OFF.

X010

               SET     M0

TO        K0        K0      H0000   K1

P

TO        K0       K21       K1       K1

P

TO        K0       K22       K0       K1

M0

TO

TO        K0       K23       K0       K1

P

TO        K0       K24     K2500   K1

P

TO        K0       K22     H0003   K1

TO

T1

TO        K0       K21       K2        K1

P

T1

                        RST     M0

P

K4

K4

P

Adjustment start.

(H0000) 

 BFM #0 (input channels selection)

(K1) 

 BFM #21

BFM #21 (gain/offset prohibition) must be set to permission
with (b1, b0) = (0,1).

(K0) 

 BFM #22 (offset/gain adjustment)

Reset adjustment bits.

(K0) 

 BFM #23 (offset)

(K2500) 

 BFM #24 (gain)

(H0003) 

 BFM #22 (offset/gain adjustment)

3 = 0011 i. e. O1 = 1, G1 = 1.
Channel 1 is adjusted.

End of adjustment.

(K2) 

 BFM #21

BFM #21 gain/offset prohibition.

Manual number : JY992D65201

Manual revision : C

Date

: SEPTEMBER 2002

Reviews: