FX

2N

-4AD SPECIAL FUNCTION BLOCK

USER’S GUIDE

JY992D65201C

This manual contains text, diagrams and explanations which will guide the reader in the correct installation
and operation of the FX

2N

-4AD and should be read and understood before attempting to install or use the

unit.
Further information can be found in the FX SERIES PROGRAMMING MANUAL(

ΙΙ

), FX

0N

/FX

1N

/FX

2N

/

FX

2NC

 SERIES HARDWARE MANUAL.

Guidelines for the Safety of the User and Protection of the FX

2N

-4AD 

special function block.

This manual should be used by trained and competent personnel. The definition of such a person or
persons is as follows:

a) Any engineer using the product associated with this manual, should be of a competent nature,

trained and qualified to the local and national standards. These engineers should be fully aware of
all aspects of safety with regards to automated equipment.

b) Any commissioning or service engineer must be of a competent nature, trained and qualified to

the local and national standards.

c)

All operators of the completed equipment should be trained to use this product in a safe and
coordinated manner in compliance to established safety practices.

Note: The term ‘completed equipment’ refers to a third party constructed device which contains or uses

the product associated with this manual.

Notes on the Symbols Used in this Manual

At various times throughout this manual certain symbols will be used to highlight points of information
which are intended to ensure the users personal safety and protect the integrity of equipment.

1) Indicates that the identified danger WILL cause physical and property damage.

2) Indicates that the identified danger could POSSIBLY cause physical and property

damage.

Under no circumstances will Mitsubishi Electric be liable or responsible for any consequential damage
that may arise as a result of the installation or use of this equipment.

All examples and diagrams shown in this manual are intended only as an aid to understanding the
text, not to guarantee operation. Mitsubishi Electric will accept no responsibility for the actual use of
the product based on these illustrative examples.

Owing to the very great variety in possible application for this equipment, you must satisfy yourself as
to its suitability for your specific application.

1. INTRODUCTION

The  FX

2N

-4AD analog special function block has four input channels. The input channels receive analog signals and

convert them into a digital value. This is called an A/D conversion. The FX

2N

-4AD has maximum resolution of 12 bits.

The selection of voltage or current based input/output is by user wiring. Analog ranges of -10 to 10V DC (resolution:
5mV), and/or 4 to 20mA, -20 to 20mA (resolution: 20 

µ

A) may be selected.

The  FX

2N

-4AD can be connected to the FX

0N

, FX

1N

, FX

2N

, and the FX

2NC

 series Programmable Controllers (PLC).

Data transfer between the FX

2N

-4AD and the main unit is by buffer memory exchange. There are 32 buffer memories

(each of 16 bits) in the FX

2N

-4AD.

The  FX

2N

-4AD occupies 8 I/O points on the FX

2N

 expansion bus. The 8 I/O points can be allocated from either inputs

or outputs. The FX

2N

-4AD draws 30mA from the 5V rail of the main unit or powered extension unit.

2. EXTERNAL DIMENSIONS

P O W E R

A / D

2 4 V

5 5 ( 2 . 1 7 )

90

(3

.5

4)

4 ( 0 . 1 6 )

8 7 ( 3 . 4 3 )

FX

2N

-4

A

D

5 5 ( 2 . 1 7 )

80

(3

.1

5)

I+

V

I-

V

+

I+

V

I-

C

H

4

C

H

3

C

H

2

C

H

1

V

+

I+

V

+

I+

V

+

24

+

24

-

V

I-

V

I-

FG

FG

FG

9 ( 0 . 3 5 )

M o u n t i n g  h o l e s

4 . 5 m m ( 0 . 1 8 ) d i a .

D I N  r a i l

M o u n t i n g  s l o t

3 5 m m ( 1 . 3 8 )

E x t e n s i o n  c a b l e

a n d  c o n n e c t o r

A / D  L E D

2 4 V  L E D

T e r m i n a l  s c r e w s  M 3 ( 0 . 1 2 )

C

H

1

V

+

24

+

24

-

V

I-

4 ( 0 . 1 6 )

Weight : Approx. 0.3 kg (0.66 lbs)

Dimensions : mm (inches)

3. WIRING

!

The analog input is received through a twisted pair
shielded cable. This cable should be wired separately
from power lines or any other lines which may induce
electrical noise.

"

If a voltage ripple occurs during input, or there is
electrically induced noise on the external wiring,
connect a smoothing capacitor of 0.1 to 0.47 

µ

F, 25V.

#

If you are using current input, connect the V+ and I+
terminals to each other.

$

If there is excessive electrical noise, connect the FG
(frame ground) terminal with the grounded terminal on
the FX

2N

-4AD. (In CH1, there is no FG terminal. Use

FG terminal of other channels.)

%

Connect the ground terminal on the FX

2N

-4AD unit

with the grounded terminal on the main unit. Use
grounding on the main unit, if available.

4. CONNECTION WITH PLC

1) Up to 4 FX

2N

-4AD units can connect to the FX

0N

 series PLC, up to 5 for FX

1N

, up to 8 for FX

2N

 or, up

to 4 for an FX

2NC

 series PLC, all with powered extension units.

However the following limitation exists when the undermentioned special function blocks are
connected.

FX

2N

:

Main unit and powered extension units of 32 I/O points or less. Current consumption
available for the undermentioned special function blocks 

 190mA

FX

2N

:

Main unit and powered extension units of 48 I/O points or more. Current consumption
available for the undermentioned special function blocks 

 300mA

FX

2NC

: Up to 4 undermentioned special function blocks can be connected regardless of the system

I/O.
When using an FX

2NC

, an FX

2NC

-CNV-IF is required.

FX

0N

/

1N

: Main unit and powered extension units. Up to 2 undermentioned special function blocks can

be connected regardless of the system I/O.

2) Each block occupies 8 I/O points (The 8 points can be allocated from either inputs or outputs).

3) FX

2N

-4AD consumes 30mA from the 5V DC bus.

The total 5V consumption of all special function blocks connected to either the FX

2N

 or FX

2NC

 main

unit or FX

2N

 extension unit must not exceed the 5V source capacity of the system.

4) The FX

2N

-4AD and main unit are connected by a cable on the right of the main unit.

5. SPECIFICATIONS

5.1 Environmental specification

5.2 Performance specification and others

Item

Specification

Environmental specifications

Same as those for the main unit

Dielectric withstand voltage

500V AC, 1min (between all terminals and ground)

Item

Specification

Analog circuits 

 24V DC ± 10%, 55mA
(external power supply from the main unit)

Digital circuits

5V DC, 30mA
(internal power supply from main unit)

Isolation

Photo-coupler isolation between analog and digital circuits.
DC/DC converter isolation of power from the main unit.
No isolation between analog channels.

Number of occupied I/O points

The analog block occupies 8 points.
(can be either inputs or outputs)

PLC

V +

F G

I +
VI-

Voltage input
-10V to +10V

V +

F G

I +
VI-

Current input
-20mA to +20mA

24-

24+

100K

!

100K

!

250

!

250

!

100K

!

100K

!

CH4

CH1

+15V

AG

-15V

AG

CH4

CH1

 1
Shielded

 2

 3

 4

 5

 1
Shielded

Grounding
(100

!

 or less)

Extension cable

FX

2N

-4AD

Analog Input Block

DC24V  55mA

DC/DC

converter

5.3 Performance specification

Analog Inputs

Analog Inputs continued...

NOTE: Preset ranges are selected by an appropriate setting in the buffer memory of the analog block.

Current/Voltage input selection must match the correct input terminal connections.

6. ALLOCATION OF BUFFER MEMORIES (BFM#)

6.1 Buffer memories

Item

Voltage input

Current input

Either voltage or current input can be selected with your choice of input terminal. 
Up to four input points can be used at one time.

Analog input 
range

DC -10V to +10V 
(input resistance: 200k

).

Warning: this unit may be damaged by an 
input voltage in excess of ± 15V.

DC -20mA to +20mA 
(input resistance: 250

). 

Warning: this unit may be damaged by an 
input currents in excess of ± 32mA.

Digital output

12-bit conversion stored in 16-bit 2’s complement form.
Maximum value: +2047 Minimum value: -2048

Resolution

5mV (10V default range 1/2000)

20

µ

A (20mA default range 1/1000)

Overall 
accuracy

± 1% (for the range of -10V to +10V) 

± 1% (for the range of -20mA to +20mA)

Conversion 
speed

15ms/channel (Normal speed), 6ms/channel (High speed)

Preset 0 (-10V to +10V)

 Preset 1 (+4mA to +20mA)

Preset 2 (-20mA to +20mA)

BFM

Contents

*#0

Channel selection Default = H0000

*#1

Channel 1

Contains the number of samples (1 to 4096) to be used for an 
averaged result.
The default setting is 8- normal speed. High speed operation 
can be selected with a value of 1.

*#2

Channel 2

*#3

Channel 3

*#4

Channel 4

 #5

Channel 1

These buffer memories contain the averaged input values for 
the number of samples entered for the channel in buffer 
memories #1 to #4 respectively.

 #6

Channel 2

 #7

Channel 3

 #8

Channel 4

 #9

Channel 1

These buffer memories contain the present value currently 
being read by each input channel.

 #10

Channel 2

 #11

Channel 3

 #12

Channel 4

 #13 - #14

Reserved

 #15

Selection of A/D 
conversion speed 
see note 2

When set to 0, a normal speed is selected of 15ms/ch (default)

When set to 1, a high speed is selected of 6ms/ch

 #16 - #19

Reserved

*#20

Reset to Defaults and Preset. 

Default = 0

*#21

Offset, Gain Adjust Prohibit. 

Default = (0, 1) Permit

*#22

Offset, Gain Adjust

b7

b6

b5

b4

b3

b2

b1

b0

G4 

 

 O4 G3

O3

G2 O2

G1

O1

*#23

Offset Value

Default = 0

*#24

Gain Value

Default = 5,000

 #25 - #28

Reserved

 #29

Error status

 #30

Identification code K2010

 #31

Cannot be used

Voltage input

Digital output

-2,000

-2,048

-10.240V

+2,000

+2,047

+

10.235V

+10V

-10V

+1,750

+1,000

Current input

Digital
output

+

32mA

+20mA

+4mA

0

Current input

Digital
output

-1,000

-1,600

-32mA

+1,000

+1,600

+

32mA

+20mA

-20mA