2.2.5
One-pair Wiring
*1 R is the terminating resistance. Connect the terminating resistance (110
Ω
) between terminals SDA and SDB.
*2 Shield of connect the 485BD to shielded twist-pair cable must be connected to ground (100
Ω
or less).
When use parallel link, ground both side. When use no protocol or dedicated protocol, ground one side.
*3 Connect terminal FG to each terminal of the programmable controller main body grounded with resistance of 100
Ω
or
less. However, as for the computer link unit of the A series PC, see the manual of the computer link unit.
*4 When use RS232/485 or RS232/422 adapter, please the adapter use FX-485PC-IF.
Grounding of resistance 100 or less
R*1
SDA
SDB
RDA
RDB
SDA
SDB
RDA
RDB
SG
SDA
SDB
RDA
RDB
LINK
SG
*3
FG
SDA
SDB
RDA
RDB
SG
*3
FG
R*1
RS485 unit
485BD
FX
(ON)
-485ADP
A series programmable
controller
's computer link unit
SG
*2
2
FX
2N
-485-BD COMMUNICATION BOARD
MOUNTING AND WIRING