2.7
Wiring
2.7.1
Power Supply
Power Supply Specifications
Grounding
The PLC should be grounded.
쎲
The grounding resistance should be 100
액
or less.
쎲
The grounding point should be close to the PLC. Keep the grounding wires as short as
possible.
쎲
Independent grounding should be performed for best results. When independent ground-
ing is not performed, perform "shared grounding" of the following figure.
쎲
The ground wire size should be at least 2 mm
2
.
The Hardware
Wiring
Training Manual GX IEC Developer
2 - 13
Specification
Units for DC Power Supply
Units for AC Power Supply
Rated voltage
12 to 24 V DC
24 V DC
100 to 240 V AC
Voltage range
10.2 to 26.4 V DC
20.4 to 26.4 V DC
85 to 264 V AC
Allowable momentary
power failure time
5 ms
20 ms
24 V DC
FX base unit
+
–
Connection of units with DC power supply
L
N
100 to 240 V AC
50/60 Hz
FX base unit
Connection of units with AC power supply
PLC
Another
equipment
PLC
Another
equipment
PLC
Another
equipment
Shared grounding
Good condition
Common grounding
Not allowed
Independent grounding
Best condition
Summary of Contents for FX2N-32CAN
Page 1: ...MITSUBISHI ELECTRIC FACTORY AUTOMATION Programmable Logic Controllers GX IEC Developer ...
Page 2: ......
Page 4: ......
Page 6: ......
Page 10: ...IV MITSUBISHI ELECTRIC ...
Page 18: ...Modular PLC Training Hardware Course Overview and Requirements 1 2 MITSUBISHI ELECTRIC ...
Page 176: ...Device Edit 8 4 MITSUBISHI ELECTRIC ...
Page 190: ...Assigning DUT Variables to Function Blocks Data Unit Types DUT 10 10 MITSUBISHI ELECTRIC ...
Page 198: ...Array Example Single Dimension Array Arrays 11 8 MITSUBISHI ELECTRIC ...
Page 219: ...Sequential Function Chart SFC SFC Elements Training Manual GX IEC Developer 14 3 ...
Page 230: ...Structured Text Program Example IEC Structured Text 16 4 MITSUBISHI ELECTRIC ...
Page 278: ...PLC Components Glossary Appendix A 18 MITSUBISHI ELECTRIC ...
Page 283: ......