(A) Application parameters
Parameters
5 - 362
●
The following shows the relationship between the input values of the analog input terminals and
set point, measured value and deviation. (Calibration parameter initial values)
Can be changed by Pr. 73 and Pr. 267 and the voltage/current input switch. (Refer to page 5-255.)
Multistage set point input (Pr. 1460 to Pr. 1466)
●
The set point can be selected by combining the ON/OFF status of the PDI1 to PDI3 signals. Up to
eight set points can be selected. Use Pr. 1460 "PID multistage set point 1" to Pr. 1466 "PID
multistage set point 7" to set the target values for selection.
●
When "9999" is set in the selected multistage set point parameter, PID control is performed
according to the Pr. 128, Pr. 609, and Pr. 133 settings.
When functions are not assigned to the input terminals, the signals are treated as OFF.
Input
terminal
Inspect
specification
Relationship with analog input
Calibration parameter
Set point
Result
Deviation
Terminal
2
0 to 5 V
0 V = 0%
5 V = 100%
0 V = 0%
5 V = 100%
0 V = 0%
5 V = 100%
Pr. 125, C2 to C4
0 to 10 V
0 V = 0%
10 V = 100%
0 V = 0%
10 V = 100%
0 V = 0%
10 V = 100%
0 to 20 mA
0 mA = 0%
20 mA = 100%
0 mA = 0%
20 mA = 100%
0 V = 0%
20 mA = 100%
Terminal
1
0 to ±5 V
–5 V to 0 V = 0%
5 V = +100%
–5 V to 0 V = 0%
5 V = +100%
–5 V = –100%
0 V = 0%
5 V = +100%
When Pr. 128 = "10",
Pr. 125, C2 to C4.
When Pr. 128
≥
"1000",
C12 to C15.
0 to ±10 V
–10 V to 0 V = 0%
10 V = +100%
–10 V to 0 V = 0%
10 V = +100%
–10 V = –100%
0 V = 0%
10 V = +100%
Terminal
4
0 to 5 V
0 V to 1 V = 0%
5 V = 100%
0 V to 1 V = 0%
5 V = 100%
0 V = –20%
1 V = 0%
5 V = 100%
Pr. 126, C5 to C7
0 to 10 V
0 V to 2 V = 0%
10 V = 100%
0 V to 2 V = 0%
10 V = 100%
0 V = –20%
1 V = 0%
10 V = 100%
0 to 20 mA
0 to 4 mA = 0%
20 mA = 100%
0 to 4 mA = 0%
20 mA = 100%
0 V = –20%
4 mA = 0%
20 mA = 100%
Tab. 5-170:
Relationship between the signals
NOTE
Always perform calibration after changing the voltage/input specification with Pr. 73, Pr. 267, and
the voltage/current input selection switch.
Selected set point
PDI1
PDI2
PDI3
Parameter for setting
⎯
OFF
OFF
OFF
As set in the Pr. 128 and Pr. 609 PID
settings.
As set Pr.1 33 when Pr. 133
≠
"9999".
Multistage set point 1
ON
OFF
OFF
Pr. 1460
Multistage set point 2
OFF
ON
OFF
Pr. 1461
Multistage set point 3
ON
ON
OFF
Pr. 1462
Multistage set point 4
OFF
OFF
ON
Pr. 1463
Multistage set point 5
ON
OFF
ON
Pr. 1464
Multistage set point 6
OFF
ON
ON
Pr. 1465
Multistage set point 7
ON
ON
ON
Pr. 1466
Tab. 5-171:
Multistage set point
Summary of Contents for FR-F820-00046
Page 2: ......
Page 4: ......
Page 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Page 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Page 900: ...Outline dimension drawings Specifications 8 26 ...
Page 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Page 930: ...EC Declarations of Conformity Appendix A 30 ...
Page 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Page 932: ...EC Declarations of Conformity Appendix A 32 ...
Page 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Page 934: ...EC Declarations of Conformity Appendix A 34 ...
Page 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Page 936: ...EC Declarations of Conformity Appendix A 36 ...
Page 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Page 938: ...EC Declarations of Conformity Appendix A 38 ...
Page 939: ......