![Mitsubishi Electric FR-F820-00046 Instruction Manual Download Page 490](http://html.mh-extra.com/html/mitsubishi-electric/fr-f820-00046/fr-f820-00046_instruction-manual_1811886490.webp)
(C) Motor constant parameters
Parameters
5 - 318
For the FR-F820-02330(55K) or lower and FR-F840-01160(55K) or lower.
For the FR-F820-03160(75K) or higher and FR-F840-01800(75K) or higher.
Differs according to the voltage class. (200 V/400 V)
The setting range and unit change according to the Pr. 71 (Pr. 450) setting.
743
C206
Second motor maximum
frequency
9999
0 to 400 Hz
Set the maximum frequency of the
second motor.
9999
The maximum frequency of an MM-
EFS/MM-THE4 motor when MM-EFS/
MM-THE4 is selected.
The setting value of Pr. 457 is used for
non-MM-EFS/MM-THE4 motors.
744
C207
Second motor inertia
(integer)
9999
10 to 999, 9999
Set the inertia of the second motor.
9999: Uses MM-EFS/MM-THE4 inertia
for IPM motor MM-EFS/MM-THE4,
and MM-EFS inertia for non-MM-EFS/
MM-THE4 motors.
745
C208
Second motor inertia
(exponent)
9999
0 to 7, 9999
463
C210
Second motor auto tuning
setting/status
0
0, 101
No auto tuning for the second motor.
1
Performs offline auto tuning without
rotating the second motor (motor
other than the IPM motor MM-EFS/
MM-THE4).
11
Performs offline auto tuning without
rotating the motor (for IPM motor
MM-EFS/MM-THE4).
458
C220
Second motor constant (R1)
9999
0 to 50 Ω, 9999
Tuning data of the second motor
(The value measured by offline auto
tuning is automatically set.)
9999: Uses the MM-EFS/MM-THE4
constant for the IPM motor MM-EFS/
MM-THE4, and the inverter internal
data for a PM motor other than
MM-EFS/MM-THE4.
460
C222
Second motor constant (L1) /
d-axis inductance (Ld)
9999
0 to 500 mH, 9999
461
C223
Second motor constant (L2) /
q-axis inductance (Lq)
9999
0 to 500 mH, 9999
860
C226
Second motor torque current/
Rated PM motor current
9999
0 to 500 A, 9999
0 to 3600 A, 9999
738
C230
Second motor induced
voltage constant (phi f )
9999
Set this parameter according to the
PM motor specifications.
9999
Value calculated based on the tuning
data.
739
C231
Second motor Ld decay ratio
9999
0 to 100%, 9999
Tuning data of the second motor.
(The value measured by offline auto
is automatically set.)
9999: Uses the MM-EFS/MM-THE4
constant for the IPM motor MM-EFS/
MM-THE4, and the inverter internal
data for a PM motor other than
MM-EFS/MM-THE4.
740
C232
Second motor Lq decay ratio
9999
0 to 100%, 9999
741
C282
Second starting resistance
tuning compensation
9999
0 to 200%, 9999
742
C285
Second motor magnetic pole
detection pulse width
9999
0 to 6000 μs,
10000 to 16000 μs, 9999
746
C233
Second motor protection
current level
9999
100 to 500%
Set the maximum current (OCT) level
of the second motor.
9999
Uses the MM-EFS/MM-THE4 constant
for the IPM motor MM-EFS/MM-THE4,
and 200% for a PM motor other than
MM-EFS/MM-THE4.
Pr.
Name
Initial
value
Setting range
Description
Summary of Contents for FR-F820-00046
Page 2: ......
Page 4: ......
Page 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Page 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Page 900: ...Outline dimension drawings Specifications 8 26 ...
Page 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Page 930: ...EC Declarations of Conformity Appendix A 30 ...
Page 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Page 932: ...EC Declarations of Conformity Appendix A 32 ...
Page 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Page 934: ...EC Declarations of Conformity Appendix A 34 ...
Page 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Page 936: ...EC Declarations of Conformity Appendix A 36 ...
Page 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Page 938: ...EC Declarations of Conformity Appendix A 38 ...
Page 939: ......