(C) Motor constant parameters
Parameters
5 - 306
Before performing offline auto tuning
Check the following points before performing offline auto tuning:
●
A value other than "9999" is set in Pr. 80 and Pr. 81, and Advanced magnetic flux vector control.
●
A motor is connected. (The motor should not be rotated by the force applied from outside during
the tuning.)
●
For the motor capacity, the rated motor current should be equal to or less than the inverter rated
current. (It must be 0.4 kW or higher.) If a motor with substantially low rated current compared
with the inverter rated current is used, speed and torque accuracies may deteriorate due to torque
ripples, etc. Set the rated motor current to about 40% or higher of the inverter rated current.
●
The target motor is other than a high-slip motor, a high-speed motor, or a special motor.
●
The highest frequency is 400 Hz.
●
The motor may rotate slightly even if the offline auto tuning without motor rotation (Pr. 96 "Auto
tuning setting/status" = "1") is selected. (The slight motor rotation does not affect the tuning
performance.) Fix the motor securely with a mechanical brake, or before tuning, make sure that
it is safe even if the motor rotates. (Caution is required especially in vertical lift applications.)
●
Check the following points for the offline auto tuning with motor rotation (Pr. 96 "Auto tuning
setting/status" = "101").
Torque is not sufficient during tuning.
The motor can be rotated up to the speed close to the rated speed.
The mechanical brake is released.
●
Offline auto tuning is not performed correctly when the surge voltage suppression filter (FR-ASF-
H/FR-BMF-H) are inserted between the inverter and motor. Be sure to remove them before
performing tuning.
Setting
●
To perform tuning, set the following parameters about the motor.
Differs according to the voltage class. (200 V/400 V)
According to the Pr. 71 setting, the range of the motor constant parameter setting values and units
can be changed. Set the Pr. 71 "Applied motor setting" according to the motor to be used and the
motor constant setting range. (For other setting values of Pr. 71, refer to page 5-297.)
First
motor Pr.
Second
motor Pr.
Name
Initial value
Description
80
453
Motor capacity
9999 (V/F control) Set the motor capacity (kW).
81
454
Number of motor
poles
9999 (V/F control) Set the number of motor poles (2 to 12).
9
51
Electronic thermal O/L
relay
Inverter rated
current
Set the rated motor current (A).
83
456
Rated motor voltage
200 V/400 V
Set the rated motor voltage (V) printed on the
motor's rating plate.
84
457
Rated motor
frequency
9999
Set the rated motor frequency (Hz).
When the setting is "9999", the Pr. 3 "Base frequency"
setting is used.
71
450
Applied motor
0 (standard
motor)
Set this parameter according to the motor.
Three types of motor constant setting ranges, units
and tuning data can be stored according to settings.
96
463
Auto tuning setting/
status
0
Set "1" or "101".
1: Performs tuning without rotating the motor.
(Excitation noise occurs at this point.)
101: Performs tuning by rotating the motor. The
motor can rotate up to the speed near the rated
motor frequency.
Tab. 5-133:
Set the parameters before performing tuning
Summary of Contents for FR-F820-00046
Page 2: ......
Page 4: ......
Page 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Page 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Page 900: ...Outline dimension drawings Specifications 8 26 ...
Page 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Page 930: ...EC Declarations of Conformity Appendix A 30 ...
Page 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Page 932: ...EC Declarations of Conformity Appendix A 32 ...
Page 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Page 934: ...EC Declarations of Conformity Appendix A 34 ...
Page 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Page 936: ...EC Declarations of Conformity Appendix A 36 ...
Page 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Page 938: ...EC Declarations of Conformity Appendix A 38 ...
Page 939: ......