Parameters
(N) Operation via communication and its settings
FR-F800
5 - 475
Inverter status monitor
The signal within parentheses ( ) is the initial status. The description changes depending on the
setting of Pr. 190 to Pr. 196 (output terminal function selection).
No function is assigned in the initial status for the separated converter type.
Item
Instruction
code
Bit
Length
Description
Example
In
v
e
rt
e
r s
ta
tu
s m
o
n
it
o
r
H7A
8 bits
b0:
RUN (Inverter running)
b1: During
forward
rotation
b2:
During reverse rotation
b3:
SU (Up to frequency)
b4:
OL (Overload warning)
b5:
IPF (Instantaneous power
failure/undervoltage)
b6:
FU (Output frequency
detection)
b7: ABC1
(Fault)
In
v
e
rt
e
r s
ta
tus
m
o
n
it
o
r
(ex
tended)
H79
16 bits
b0:
RUN (Inverter running)
b1: During
forward
rotation
b2:
During reverse rotation
b3:
SU (Up to frequency)
b4:
OL (Overload warning)
b5:
IPF (Instantaneous power
failure/undervoltage)
b6:
FU (Output frequency
detection)
b7: ABC1
(Fault)
b8: ABC2
(
⎯
)
b9: Safety
monitor
output
b10 to b14:
⎯
b15: Fault
occurrence
Tab. 5-238:
Inverter status monitor
0
0
0
0
0
0
1
0
b7
b0
1
0
0
0
0
0
0
0
b7
b0
[Example 1] H02 ••• During forward rotation
[Example 2] H80 ••• Stop at fault occurrence
0
0
0
0
0
0
0
0
0
0
0
0
0
b15
1
0
0
0
0
1
0
0
0
0
0
0
0
b15
[Example 1] H0002 ••• During forward rotation
[Example 2] H8080 ••• Stop at fault occurrence
Summary of Contents for FR-F800
Page 2: ......
Page 4: ......
Page 28: ...Related manuals Introduction 1 8 ...
Page 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Page 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 806: ...Outline dimension drawings Specifications 8 26 ...
Page 833: ......