![Mitsubishi Electric FR-F800 Instruction Manual Download Page 636](http://html.mh-extra.com/html/mitsubishi-electric/fr-f800/fr-f800_instruction-manual_1811884636.webp)
(N) Operation via communication and its settings
Parameters
5 - 474
Operation command
The signal within parentheses ( ) is the initial status. The description changes depending on the
setting of Pr. 180 to Pr. 184, Pr. 187 (input terminal function selection) (page 5-279).
The inverter run enable signal is in the initial status for the separated converter type.
JOG operation/automatic restart after instantaneous power failure/start self-holding selection/
reset cannot be controlled over a network, so in the initial status bit8 to bit11 are invalid. To use
bit8 to bit11, change the signal by Pr. 185, Pr. 186, Pr. 188, or Pr. 189 (input terminal function
selection) (page 5-279). (A reset can be executed by the instruction code HFD.)
In RS-485 communication from the PU connector, only the forward rotation command and reverse
rotation command can be used.
Item
Instruc-
tion code
Bit
length
Description
Example
Operation com
m
and
HFA
8 bits
b0:
AU (Terminal 4 input selection)
b1:
Forward rotation command
b2:
Reverse rotation command
b3:
RL (Low-speed operation
command)
b4: RM
(Middle-speed
operation
command)
b5:
RH (High-speed operation
command)
b6:
RT (Second function selection)
b7:
MRS (Output stop)
Oper
a
ti
o
n c
o
mma
nd (e
x
tended)
HF9
16 bits
b0:
AU (Terminal 4 input selection)
b1:
Forward rotation command
b2:
Reverse rotation command
b3:
RL (Low-speed operation
command)
b4: RM
(Middle-speed
operation
command)
b5:
RH (High-speed operation
command)
b6:
RT (Second function selection)
b7:
MRS (Output stop)
b8: JOG
b9:
CS (No function)
b10: STP (STOP) (Start self-holding
selection)
b11: RES
(Inverter
b12 to b15:
⎯
Tab. 5-237:
Operation commands
0
0
0
0
0
0
1
0
b7
b0
0
0
0
0
0
0
0
0
b7
b0
[Example 1] H02 Forward rotation
[Example 2] H00 Stop
0
0
0
0
0
0
1
0
b0
0
0
0
0
0
0
0
0
b15
0
0
0
0
0
0
0
0
b0
0
0
0
0
1
0
0
0
b15
[Example 1] H0002 Forward rotation
[Example 2] H0800 low speed operation
(When Pr. 189 RES terminal function selection is set to "0")
Summary of Contents for FR-F800
Page 2: ......
Page 4: ......
Page 28: ...Related manuals Introduction 1 8 ...
Page 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Page 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 806: ...Outline dimension drawings Specifications 8 26 ...
Page 833: ......