Parameters
(C) Motor constant parameters
FR-F800
5 - 307
●
Set a given value as the motor constant parameter. The displayed increments of the read motor
constants can be changed with Pr. 684 "Tuning data unit switchover".
For the FR-F820-02330(55K) or lower and FR-F840-01160(55K or lower.
For the FR-F820-03160(75K) or higher and FR-F840-01800(75K) or higher.
First
motor
Pr.
Second
motor
Pr.
Name
Pr. 684 = 0 (initial value)
Pr. 684 = 1
Initial
value
Setting range
Setting
increments
Range indication
Unit
indication
82
455
Motor excitation
current
0 to ***, 9999
1
0 to 500 A, 9999
0.01 A
9999
0 to 3600 A, 9999
0.1 A
90
458
Motor constant (R1)
0 to 50 Ω, 9999
0.001 Ω
91
459
Motor constant (R2)
0 to 50 Ω, 9999
0.001 Ω
92
460
Motor constant (L1)/
d-axis inductance
(Ld)
0 to 6000 mH, 9999
0.1 mH
0 to 400 mH, 9999
0.01 mH
93
461
Motor constant (L2)/
q-axis inductance
(Lq)
0 to 6000 mH, 9999
0.1 mH
0 to 400 mH, 9999
0.01 mH
94
462
Motor constant (X)
0 to 100%, 9999
0.01%
859
860
Torque current/
Rated PM motor
current
0 to 500 A, 9999
0.01 A
0 to 3600 A, 9999
0.1 A
298
560
Frequency search
gain
0 to 32767, 9999
1
0 to 32767, 9999
1
Tab. 5-142:
Parameter setting ranges
NOTES
As the motor constants measured in the offline auto tuning have been converted into internal
data (****), refer to the following setting example when making setting:
Setting example:
To slightly increase the Pr. 90 value (5%)
If Pr. 90 = "2516" is displayed, the value is calculated with 2516 × 1.05 = 2641.8.
Therefore set Pr. 90 = "2642".
(The value displayed has been converted into a value for internal use. Hence, simple addition of a
given value to the displayed value has no significance.)
If "9999" is set, tuning data will be invalid and the constant values for Mitsubishi motors (SF-PR,
SF-JR, SF-HR, SF-JRCA, SF-HRCA and so on) are used.
Summary of Contents for FR-F800
Page 2: ......
Page 4: ......
Page 28: ...Related manuals Introduction 1 8 ...
Page 104: ...Connection of stand alone option units Installation and wiring 2 76 ...
Page 162: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 806: ...Outline dimension drawings Specifications 8 26 ...
Page 833: ......