3 WIRING
CAUTION
• To prevent a malfunction due to noise, keep the signal cables more than 10cm away from the power cables. Also separate
the main circuit wire of the input side and the output side.
• After wiring, wire offcuts must not be left in the inverter.
Wire offcuts can cause an alarm, failure or malfunction. Always keep the inverter clean.
When drilling mounting holes in a control box etc., take care not to allow chips and other foreign matter to enter the inverter.
• Set the voltage/current input switch correctly. Different setting may cause a fault, failure or malfunction.
Three-phase AC
power supply
MCCB
Jumper
R/L1
S/L2
T/L3
R1/L11
S1/L21
PC
10E
(+10V)
10
(+5V)
2
3
1
1
4
Control input signals (No voltage input allowed)
Jumper
Motor
Relay output 1
(Fault output)
C1
B1
A1
U
V
W
AM
5
*1
Main circuit terminal
Control circuit terminal
MC
Main circuit
Control circuit
C2
B2
A2
Relay output 2
Relay output
IM
AU
PTC
TXD+
TXD-
RXD+
RXD-
SG
SINK
SOURCE
Terminal functions
vary with the output
terminal assignment
(
Pr. 195, Pr. 196)
Terminal functions
vary with the output
terminal assignment
(
Pr. 190 to Pr. 194)
Terminal functions vary
with the input terminal
assignment
(
Pr. 178 to Pr. 189
)
*3
STF
STR
STOP
RH
RM
RL
JOG
RT
MRS
RES
AU
CS
SD
RUN
SU
IPF
OL
FU
SE
EMC filter
ON/OFF
connector
ON
OFF
VCC
Frequency setting signal (Analog)
Frequency setting
potentiometer
1/2W1k
Ω
Auxiliary
input
(+)
(-)
2
(Analog common)
0 to 5VDC
0 to 10VDC
selected
0 to 20mADC
*4
5
PU
connector
Terminal
4 input
(Current
input)
Terminating
resistor
Connector
for plug-in option
connection
*5. It is recommended to use
2W1k
Ω
when the
frequency setting signal is
changed frequently.
(+)
(-)
0 to 5VDC
0 to 10VDC
selected *4
GND
RS-485 terminals
Data transmission
Data reception
4 to 20mADC
*4
selected
0 to
±5VDC
0 to
±10VDC
(-)
(+)
(0 to 10VDC)
Analog signal output
Frequency detection
Open collector output common
Sink
/source common
Running
Up to frequency
Instantaneous
power failure
Overload
Open collector output
Terminal 4 input selection
(Current input selection)
Selection of automatic restart
after instantaneous
power failure
Output stop
Reset
*3. AU terminal can be
used as PTC input
terminal.
Middle speed
High speed
Low speed
Jog mode
Second function selection
Multi-speed
selection
Forward
rotation
start
Reverse
rotation
start
Start self-holding selection
PR
*7
PX
*7
Jumper
*7.
*5
(Permissible load
current 100mA)
5V
*2. To supply power to the
control circuit separately,
remove the jumper across
R1/L11 and S1/L21.
*2
Do not use PR and PX terminals.
Please do not remove the jumper
connected to terminal PR and PX.
Initial
value
Initial
value
Initial value
*4. Terminal input specifications
can be changed by analog
input specifications switchover
(
Pr. 73, Pr. 267
). Set the
voltage/current input switch in
the OFF position to select
voltage input (0 to 5V/0 to
10V) and ON to select current
input (0 to 20mA).
ON
4 2
OFF
Voltage/current
input switch
*4
Resistor unit
(Option)
Brake unit
(Option)
CN8
*6
N/-
P/+
Option connector 1
P1
Sink logic
Ground
Ground
Ground
(0 to 20mADC)
(-)
(+)
CA
(0 to 20mADC)
(-)
(+)
CA
(0 to 20mADC)
Analog current outpu
(-)
(+)
CA
24VDC power supply
(Common for external power supply transistor)
Contact input common
*6. A CN8 (for MT-BU5) connector is
provided for the FR-F720-03160
(FR-F740-01800) or more.
*1.
DC reactor (FR-HEL)
Be sure to connect the DC reactor
supplied with the FR-F720-03160
(FR-F740-01800) or more.
When a DC reactor is connected to
the 02330 (FR-F740-01160) or less,
remove the jumper across P1-P/+.
*8. The 200V class 00046 and 00077
are not provided with the ON/OFF
connector EMC filter.
*8
(Refer to the Instruction
Manual (applied) chapter4.)
Refer to the
Instruction Manual
(applied) chapter4.
(Refer to the Instruction
Manual (applied) chapter4.)
Refer to the
Instruction Manual
(applied) chapter4.