12
Inverter placement (Installation of Filterpack)
1.5.2
Installation of the inverter and Filterpack (for rear panel installation)
NOTE
When encasing multiple inverters, install them in parallel as a cooling
measure.
Install the inverter vertically.
For heat dissipation and maintenance, allow minimum clearance shown
in the figures below from the inverter to the other devices and to the
inner surface of the enclosure.
Allow 5cm or more clearance for 5.5K or higher.
When using the inverters at the surrounding air temperature of 40
C or less, the inverters can be installed without any clearance between
them (0cm clearance).
<0.4K to 3.7K>
Remove the front cover and wiring cover to attach the inverter.
<5.5K to 15K>
Remove the L-bracket installation screws from Filterpack (two for the 7.5K or lower, three for the 11K or higher), and attach
the included L-bracket to Filterpack with these screws.
Remove the front cover to attach the inverter.
V
e
rtical
Refer to the clearance
shown on the left.
10cm or more
10cm or more
Measurement
position
Measurement
position
5cm
5cm
5cm
-10 C to +50 C
(non-freezing)
1cm or
more
∗1, ∗2
1cm or
more
∗1, ∗2
1cm or
more
∗1
FR-F720PJ-1.5K to 3.7K
FR-F720PJ-0.4K to 0.75K
FR-F740PJ-0.4K to 3.7K
Screw for inverter rear
panel installation
Screw for inverter rear
panel installation
Front cover
Front cover
Wiring cover
Wiring cover
Screw for inverter rear
panel installation
Screw for inverter rear
panel installation
L-bracket installation screw
Screw for inverter
rear panel installation
Rear panel installation L-bracket
Screw for inverter rear panel installation
Summary of Contents for FR-F700PJ Series
Page 13: ...IX MEMO ...
Page 29: ...16 MEMO ...
Page 76: ...63 MEMO ...
Page 299: ...294 MEMO ...
Page 321: ...316 MEMO ...