4
WIRING
3 WIRING
CAUTION
To prevent a malfunction due to noise, keep the signal cables more than 10cm away from the power cables.
After wiring, wire offcuts must not be left in the inverter.
Wire offcuts can cause an alarm, failure or malfunction. Always keep the inverter clean.
When drilling mounting holes in a control box etc., take care not to allow chips and other foreign matter to enter the inverter.
MCCB
R/L1
S/L2
T/L3
R1/L11
S1/L21
PC
10E(+10V)
10(+5V)
2
3
1
1
4
C1
B1
A1
U
V
W
P1
AM
5
*1
MC
C2
B2
A2
AU
PTC
TXD+
TXD-
RXD+
RXD-
SG
SINK
SOURCE
*3
STF
STR
STOP
RH
RM
RL
JOG
RT
MRS
RES
AU
CS
SD
RUN
SU
IPF
OL
FU
SE
ON
OFF
VCC
(+)
(-)
2
*4
5
(+)
(-)
*4
GND
*4
(-)
(+)
PR
PX
5V
N/-
P/+
CN8
*6
(-)
(+)
CA
Source logic
Main circuit terminal
Control circuit terminal
Jumper
Jumper
Jumper
*1. DC reactor (FR-HEL)
Remove the jumper
for the
01160 or less if a DC reactor
is connected. The DC reactor
supplied with the 01800 or
more should be connected to
these terminals.
*2
Earth
*6. The CN8 connector
is provided with the
01800 or more
Earth
Motor
*2. To supply power to the
control circuit separately,
remove the jumper across R1/
L11 and S1/L21.
3-phase AC
power supply
Connector for
with/without internal
EMC filter
Main circuit
Control circuit
Terminal functions
vary with the input
terminal assignment
(
Pr. 178 to Pr. 189
)
Control input signals (No voltage input allowed)
Forward
rotation
start
Reverse
rotation
start
Start self-holding selection
High speed
Middle speed
Low speed
Multi-speed
selection
Jog mode
Second function selection
Output stop
Reset
Current input selection
Selection of automatic restart
after instantaneous
power failure
Contact input common (Sink*)
*3. AU terminal
can be used
as PTC input
terminal.
24VDC power supply/
max. 100mA load current
Contact input common(Source*)
*(Common for external power supply transistor)
Frequency setting signal (Analog)
*5
Auxiliary input
Terminal 4 input
(Current input)
0 to 5VDC
0 to ±10VDC
4 to 20mADC
0 to 10VDC
4 to 20mADC
selected
0 to ±5VDC
selected
selected
0 to 5VDC
0 to 10VDC
PU
connector
Connector
for plug-in option
connection
Option connector 1
Terminating
resistor
*4. The input area can be set via
parameters. The setting
within the frame is pre-set at
the factory.
(
Pr. 73, Pr. 267
)
.
*5. It is recommended to use
2W1k
Ω
when the
frequency setting signal is
changed frequently.
Relay output 1
(Alarm output)
Relay output 2
Running
Instantaneous
power failure
Up to frequency
Overload
Terminal functions
vary with the output
terminal assignment
(
Pr. 195, Pr. 196
)
Terminal functions
vary with the output
terminal assignment
(
Pr. 190 to Pr. 194
)
Frequency detection
Open collector output common
Sink/source common
Analog current output
(0 to 20mADC)
Analog signal output
(0 to 10VDC)
RS-485 terminal
Data transmission
Data reception
(Permissible load
current 100mA)
Frequency setting
potentiometer
1/2W1k
Ω
M
3~
Earth