162
Operation selection at power failure and instantaneous power failure
4.13 Operation selection at power failure and instantaneous power
failure
4.13.1 Automatic restart after instantaneous power failure/flying start
(Pr. 30, Pr. 57, Pr. 58, Pr. 96, Pr. 162, Pr. 165, Pr. 298, Pr. 299, Pr. 611)
Purpose
Parameter that should be Set
Refer to Page
At instantaneous power failure
occurrence, restart inverter without
stopping motor
Automatic restart operation
after instantaneous power
failure/flying start
Pr. 30, Pr. 57, Pr. 58, Pr. 96,
Pr. 162, Pr. 165, Pr. 298, Pr. 299,
Pr. 611
When undervoltage or a power
failure occurs, the inverter can be
decelerated to a stop.
Power failure-time
deceleration-to-stop
function
Pr. 261
You can restart the inverter without stopping the motor in the following cases:
When power comes back on after an instantaneous power failure
When motor is coasting at start
Parameter
Number
Name
Initial Value
Setting
Range
Description
30
Regenerative function
selection
0
0, 1
The motor starts at the starting frequency when MRS (X10) turns
ON then OFF
2
Restart operation is performed when MRS (X10) turns ON then
OFF
57
Restart coasting time
9999
0
1.5K or less ..... 1s
2.2K to 7.5K .... 2s
11K or more..... 3s
The above times are coasting time.
0.1 to 5s
Waiting time for inverter-triggered restart after an instantaneous
power failure.
9999
No restart
58
Restart cushion time
1s
0 to 60s
Voltage starting time at restart.
96
Auto tuning setting/status
0
0
Offline auto tuning is not performed
1
Advanced magnetic flux vector control
Offline auto tuning is performed without motor running (all motor
constants)
11
For General-purpose magnetic flux vector control
Offline auto tuning is performed without motor running (motor
constants (R1) only)
21
Offline auto tuning (tuning performed without motor running) for
V/F control and automatic restart after instantaneous power
failure (with frequency search)
162
Automatic restart after
instantaneous power
failure selection
1
0
With frequency search
1
Without frequency search (reduced voltage system)
10
Frequency search at every start
11
Reduced voltage at every start
165
Stall prevention
operation level for restart
150%
0 to 200%
Considers the rated inverter current as 100% and sets the stall
prevention operation level during restart operation.
298
Frequency search gain
9999
0 to 32767
When offline auto tuning is performed under V/F control,
frequency search gain necessary for frequency search for
automatic restart after instantaneous power failure is set as well
as the motor constants (R1).
9999
Uses the Mitsubishi motor (SF-JR, SF-HR, SF-JRCA, SF-HRCA)
constants
299
Rotation direction
detection selection at
restarting
0
0
Without rotation direction detection
1
With rotation direction detection
9999
When
Pr. 78
= 0,
With rotation direction detection
When
Pr. 78
= 1, 2
Without rotation direction detection
611
Acceleration time at a
restart
9999
0 to 3600s
Acceleration time to reach
Pr. 20 Acceleration/deceleration reference
frequency
at a restart.
9999
Acceleration time for restart is the normal acceleration time (e.g.
Pr. 7
)
The above parameters can be set when
Pr. 160 User group read selection
= "0".
....... Specifications differ according to the date assembled.
to check the SERIAL number.
Summary of Contents for FR-E710W-0.1K
Page 49: ...40 MEMO ...
Page 65: ...56 MEMO ...
Page 288: ...288 MEMO ...
Page 310: ...310 MEMO ...
Page 334: ...334 MEMO ...
Page 348: ...4 4 BCN C22005 679 MEMO BCN C22005 679 fm 4 ページ 2014年11月7日 金曜日 午前11時58分 ...