Parameter list
Parameter list
52
P
ar
am
et
er
L
is
t
4.2 Parameter list
4.2.1
Parameter list
For simple variable-speed operation of the inverter, the initial setting of the parameters may be used as they are. Set the
necessary parameters to meet the load and operational specifications. Parameter setting, change and check are available
from the operation panel.
Symbol in the Remarks column.
...Specifications differ according to the date assembled.
to check the SERIAL number.
Symbols in the table indicate parameters which function when an option is mounted.
..........FR-A7NC E kit
These instruction codes are used for parameter read and write by using Mitsubishi inverter protocol with the RS-485 communication.
(
for RS-485 communication)
"
" indicates valid and "
" indicates invalid of "control mode-based correspondence table", "parameter copy", "parameter clear", and "all parameter clear".
Function Parameter
Name
Setting Range
Minimum
Setting
Increments
Initial
Value
Refer
to
Page
Customer
Setting
Parameter Remarks
Instruction Code
Motor/Control Mode Support Table
Parameter
S-PM
MM-GKR
Read Write Extended
Speed
Speed
position
Copy
Clear
All clear
Basi
c functi
ons
1
Maximum setting
0 to 4800r/min
1r/min
3000r/min
1
01
81
0
2
Minimum setting
0 to 4800r/min
1r/min
0r/min
2
02
82
0
4
Multi-speed setting (high speed)
0 to 4800r/min
1r/min
3000r/min
4
04
84
0
5
Multi-speed setting (middle speed)
0 to 4800r/min
1r/min
1500r/min
5
05
85
0
6
Multi-speed setting (low speed)
0 to 4800r/min
1r/min
300r/min
6
06
86
0
7
Acceleration time
0 to 360s
0.01s
5s
7
07
87
0
8
Deceleration time
0 to 360s
0.01s
5s
8
08
88
0
9
Electronic thermal O/L relay
0 to 500A
0.01A
Rated
motor
current
9
09
89
0
DC inj
ection
br
ake
10
Coasting speed
0 to 4800r/min
1r/min
90r/min
10
0A
8A
0
11
DC injection brake operation time
0 to 10s
0.1s
0.5s
11
0B
8B
0
13
Starting speed
0 to 4800r/min
1r/min
15r/min
13
0D
8D
0
JOG
o
peration
15
Jog speed setting
0 to 4800r/min
1r/min
150r/min
15
0F
8F
0
16
Jog acceleration/deceleration time
0 to 360s
0.01s
0.5s
16
10
90
0
17
MRS input selection
0, 2, 4
1
0
17
11
91
0
Acceleration/
dece
ler
ation
time
20
Acceleration/deceleration reference speed 12 to 4800r/min
1r/min
3000r/min
20
14
94
0
To
rque
lim
it
22
Torque limit level
0 to 200%, 9999
0.1%
200/150%
22
16
96
0
Multi-speed
setting
24
Multi-speed setting (speed 4)
0 to 4800r/min
, 9999
1r/min
9999
24
18
98
0
25
Multi-speed setting (speed 5)
0 to 4800r/min
, 9999
1r/min
9999
25
19
99
0
26
Multi-speed setting (speed 6)
0 to 4800r/min
, 9999
1r/min
9999
26
1A
9A
0
27
Multi-speed setting (speed 7)
0 to 4800r/min
, 9999
1r/min
9999
27
1B
9B
0
29
Acceleration/deceleration pattern selection 0, 1, 2
1
0
29
1D
9D
0
30
Regenerative function selection
0, 1
1
0
30
1E
9E
0
S
peed jump
31
Speed jump 1A
0 to 4800r/min
, 9999
1r/min
9999
31
1F
9F
0
32
Speed jump 1B
0 to 4800r/min
, 9999
1r/min
9999
32
20
A0
0
33
Speed jump 2A
0 to 4800r/min
, 9999
1r/min
9999
33
21
A1
0
34
Speed jump 2B
0 to 4800r/min
, 9999
1r/min
9999
34
22
A2
0
35
Speed jump 3A
0 to 4800r/min
, 9999
1r/min
9999
35
23
A3
0
36
Speed jump 3B
0 to 4800r/min
, 9999
1r/min
9999
36
24
A4
0
37
Speed display
0, 0.01 to 9998
0.001
0
37
25
A5
0
40
RUN key rotation direction selection
0, 1
1
0
40
28
A8
0
S
peed
detection
41
Up-to-speed sensitivity
0 to 100%
0.1%
10%
41
29
A9
0
42
Speed detection
0 to 4800r/min
1r/min
180r/min
42
2A
AA
0
43
Speed detection for reverse rotation
0 to 4800r/min
, 9999
1r/min
9999
43
2B
AB
0
REMARKS
indicates simple mode parameters. (initially set to extended mode)
The parameters surrounded by a black border in the table allow its setting to be changed during operation even if "0" (initial
value) is set in
Pr.77 Parameter write selection
.
Summary of Contents for FR-E700EX
Page 11: ...VII MEMO ...
Page 23: ...12 MEMO ...
Page 288: ...286 MEMO ...
Page 302: ...300 MEMO ...