Connection of stand-alone option unit
2.4.4
Connection of the power regeneration common converter (FR-CV)
When connecting the power regeneration common converter (FR-CV), connect the drive unit terminals (P/+, N/-) and power
regeneration common converter (FR-CV) terminals as shown below so that their symbols match with each other.
Keep input terminals (R/L1, S/L2, T/L3) open. Incorrect connection will damage the drive unit.
Do not insert an MCCB between the terminals P/+ and N/- (between P/L+ and P/+, between N/L- and N/-). Opposite polarity of terminals
N/- and P/+ will damage the drive unit.
Use
Pr.178 to Pr.184 (input terminal function selection)
to assign the terminals used for the X10, RES signal.
Always connect the power supply and terminals R/L11, S/L21, T/MC1.
Operating the drive unit without connecting them will damage the power regeneration common converter.
Be sure to connect terminal RDYB of the FR-CV to the X10 signal or MRS signal assigned terminal of the drive unit, and connect terminal
SE of the FR-CV to terminal SD of the drive unit. Without proper connecting, FR-CV will be damaged.
NOTE
The voltage phases of terminals R/L11, S/L21, T/MC1 and terminals R2/L1, S2/L2, T2/L3 must be matched.
Use sink logic (factory setting) when the FR-CV is connected. The FR-CV cannot be connected when source logic is
selected.
Do not connect a DC reactor (FR-HEL) to the drive unit when FR-CV is connected.
R/L
11
Dedicated stand-alone
reactor (FR-CVL)
S/L
21
T/L
31
R2/L
12
S2/L
22
T2/L
32
R2/L
1
S2/L
2
T2/L
3
R/L
11
S/L
21
T/MC1
P/L+
U
V
W
M
FR-CV type power
regeneration
common converter
Drive unit
PC
SD
X10
RES
SD
P24
SD
RDYB
RSO
SE
RDYA
N/L-
R/L1
S/L2
T/L3
P/+
N/-
Three-phase
AC power supply
MCCB
MC
1