CC-Link IE Field Network Basic
Parameter
6 - 352
– Remote register
햲
The above 8 bit is always H00 even if a value other than H00 is set.
햳
When Pr. 37 is not equal to "0", this will be machine speed display (1 increments).
햴
"n" indicates a value determined according to the station number setting.
●
When Pr. 544 = "1" (compatible with CC-Link Ver.1)
– Remote I/O (32 points)
Same as when Pr. 544 = 0 (Refer to page 6-351.)
– Remote register
햲
When Pr. 37 is not equal to "0", this will be machine speed display (1 increments).
햳
"n" indicates a value determined according to the station number setting.
Address
Description
Refer to
page
Upper 8 bits
Lower 8 bits
RWwn
Monitor code 2
Monitor code 1
RWwn+1
Set frequency (0.01 Hz increments)
RWwn+2
H00 (arbitrary)
Instruction code
RWwn+3
Write data
Tab. 6-146:
Remote write register
Address
Description
Refer to
page
Upper 8 bits
Lower 8 bits
RWrn
First monitor value
RWrn+1
Second monitor value
RWrn+2
Reply code
RWrn+3
Read data
Tab. 6-147:
Remote read register
Address
Description
Refer to
page
Upper 8 bits
Lower 8 bits
RWwn
Monitor code 2
Monitor code 1
RWwn+1
Set frequency (0.01 Hz increments)
RWwn+2
Link parameter
extended setting
Instruction code
RWwn+3
Write data
Tab. 6-148:
Remote write register
Address
Description
Refer to
page
Upper 8 bits
Lower 8 bits
RWrn
First monitor value
RWrn+1
Second monitor value
RWrn+2
Reply code 2
Reply code 1
RWrn+3
Read data
Tab. 6-149:
Remote read register
Summary of Contents for fr-e700 series
Page 2: ......
Page 4: ......
Page 20: ...Contents XVI ...
Page 112: ...Operation panel Operation 4 20 ...
Page 154: ...External operation Basic settings 5 42 ...
Page 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Page 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Page 606: ...A 30 Index Appendix ...
Page 607: ......