18
PARAMETER LIST
6 PARAMETER LIST
For simple variable-speed operation of the inverter, the initial setting of the parameters may be used. Set the necessary
parameters to meet the load and operational specifications. Parameter setting, change and check can be made from the
operation panel. For details of parameters, refer to the instruction manual.
REMARKS
y
indicates simple mode parameters. (initially set to extended mode)
y
The parameters surrounded by a black border in the table allow its setting to be changed during operation even if "0" (initial
value) is set in
Pr. 77 Parameter write selection
.
y
Pr. ...... Parameter number
Pr.
Name
Setting Range
Initial
Value
0 Torque boost
0 to 30%
6/4/3/2%
1 Maximum frequency
0 to 120Hz
120Hz
2 Minimum frequency
0 to 120Hz
0Hz
3 Base frequency
0 to 400Hz
60Hz
4
Multi-speed setting (high
speed)
0 to 400Hz
60Hz
5
Multi-speed setting (middle
speed)
0 to 400Hz
30Hz
6
Multi-speed setting (low
speed)
0 to 400Hz
10Hz
7 Acceleration time
0 to 3600/360s
5/10/15s
8 Deceleration time
0 to 3600/360s
5/10/15s
9 Electronic thermal O/L relay
0 to 500A
Rated
inverter
current
10
DC injection brake operation
frequency
0 to 120Hz
3Hz
11
DC injection brake operation
time
0 to 10s
0.5s
12
DC injection brake operation
voltage
0 to 30%
6/4/2%
13
Starting frequency
0 to 60Hz
0.5Hz
14
Load pattern selection
0 to 3
0
15
Jog frequency
0 to 400Hz
5Hz
16
Jog acceleration/deceleration
time
0 to 3600/360s
0.5s
17
MRS input selection
0, 2, 4
0
18
High speed maximum
frequency
120 to 400Hz
120Hz
19
Base frequency voltage
0 to 1000V,
8888, 9999
9999
20
Acceleration/deceleration
reference frequency
1 to 400Hz
60Hz
21
Acceleration/deceleration time
increments
0, 1
0
22
Stall prevention operation level 0 to 200%
150%
23
Stall prevention operation level
compensation factor at double
speed
0 to 200%, 9999
9999
24
Multi-speed setting (speed 4)
0 to 400Hz, 9999
9999
25
Multi-speed setting (speed 5)
0 to 400Hz, 9999
9999
26
Multi-speed setting (speed 6)
0 to 400Hz, 9999
9999
27
Multi-speed setting (speed 7)
0 to 400Hz, 9999
9999
29
Acceleration/deceleration
pattern selection
0, 1, 2
0
30
Regenerative function
selection
0, 1, 2
0
31
Frequency jump 1A
0 to 400Hz, 9999
9999
32
Frequency jump 1B
0 to 400Hz, 9999
9999
33
Frequency jump 2A
0 to 400Hz, 9999
9999
34
Frequency jump 2B
0 to 400Hz, 9999
9999
35
Frequency jump 3A
0 to 400Hz, 9999
9999
36
Frequency jump 3B
0 to 400Hz, 9999
9999
37
Speed display
0, 0.01 to 9998
0
40
RUN key rotation direction
selection
0, 1
0
41
Up-to-frequency sensitivity
0 to 100%
10%
42
Output frequency detection
0 to 400Hz
6Hz
43
Output frequency detection for
reverse rotation
0 to 400Hz, 9999
9999
44
Second acceleration/
deceleration time
0 to 3600/360s
5/10/15s
45
Second deceleration time
0 to 3600/360s,
9999
9999
46
Second torque boost
0 to 30%, 9999
9999
47
Second V/F (base frequency)
0 to 400Hz, 9999
9999
48
Second stall prevention
operation current
0 to 200%, 9999
9999
51
Second electronic thermal O/L
relay
0 to 500A, 9999
9999
52
DU/PU main display data
selection
0, 5, 7 to 12, 14,
20, 23 to 25, 52
to 57, 61, 62,
100
0
55
Frequency monitoring
reference
0 to 400Hz
60Hz
56
Current monitoring reference
0 to 500A
Rated
inverter
current
57
Restart coasting time
0, 0.1 to 5s,
9999
9999
58
Restart cushion time
0 to 60s
1s
59
Remote function selection
0, 1, 2, 3
0
60
Energy saving control
selection
0, 9
0
61
Reference current
0 to 500A, 9999
9999
Pr.
Name
Setting Range
Initial
Value