Run command
The signal within parentheses is the initial setting. The description changes depending on
the setting of Pr. 180 to Pr. 182 "Input terminal function selection". (Refer to section 6.9.1.)
When Pr. 551 = 2 (PU Mode control source is PU connector), only forward rotation and
reverse rotation can be used.
Item
Instruction
Code
Bits
Description
Example
Run
command
HFA
8
b0: AU (current input
selection)
b1: Forward rotation start
b2: Reverse rotation start
b3: RL (low speed)
b4: RM (middle speed)
b5: RH (high speed)
b6: RT (second function
selection)
b7: MRS (output stop)
Run
command
(extended)
HF9
16
b0: AU (current input
selection)
b1: Forward rotation start
b2: Reverse rotation start
b3: RL (low speed)
b4: RM (middle speed)
b5: RH (high speed)
b6: RT (second function
selection)
b7: MRS (output stop)
b8 to b15:—
Tab. 6-62:
Run commands
Example 1: H02 (Forward rotation)
Example 2: H00 (Stop)
Example 1: H0002 (Forward rotation)
Example 2: H0020 low speed operation
(When Pr. 182 "RH terminal function selection" is set to "0")
Summary of Contents for FR-D720S SC EC
Page 2: ......
Page 4: ......
Page 24: ...Description of the case Product checking and part identification 1 4 ...
Page 108: ...Operation panel Operation 4 20 ...
Page 436: ...Setting for the parameter unit and operation panel Parameter 6 286 ...
Page 484: ...Measurements on the main circuit Maintenance and inspection 8 14 ...
Page 504: ...Specification change Appendix A 20 ...
Page 505: ......
Page 506: ......
Page 510: ...Index Appendix A 24 ...
Page 511: ......