Parameter
Monitor display and monitor output signals
FR-D700 SC EC
6 - 109
6.10
Monitor display and monitor output signals
6.10.1
Speed display and speed setting (Pr. 37)
You can output RPM rates, speeds and throughput volumes based on the output frequency to
the displays of the operation panels, FR-PU04 and FR-PU07 parameter units or to the AM
output.
The above parameters can be set when Pr. 160 = 0.
The maximum value of the setting range differs according to the Pr. 1 "Maximum frequency"
(Parameter 18 "High speed maximum frequency") and it can be calculated from the following
formula:
Note that the maximum setting value of Pr. 37 is 9998 if the result of the above formula exceeds
9998.
To display the machine speed set Pr. 37 to the reference value for the speed to be shown at
60Hz. For example, if the speed is 55m/min at 60Hz set Pr. 37 to "55". The display will then show
"55" when the motor frequency is 60Hz.
Purpose
Parameters that must be set
Refer to
Section
Display motor speed
Set speed
Speed display and speed setting
Pr. 37
Change PU monitor display data
Monitor display/
PU main display data selection
Cumulative monitor clear
Pr. 52, Pr. 158,
Pr. 170, Pr. 171,
Pr. 268, Pr. 563,
Pr. 564, Pr. 891
Change of the monitor output from
terminal AM
Terminal AM function selection
Pr. 158
Set the reference of the monitor
output from terminal AM
Terminal AM standard setting
Pr. 55, Pr. 56
Adjust terminal AM outputs
Terminal AM calibration
Pr. 901
Pr.
No.
Name
Initial
Setting
Setting
Range
Description
Parameters referred to
Refer to
Section
37
Speed display
0
0
Frequency display, setting
1
18
52
Maximum
frequency
High speed maxi-
mum frequency
DU/PU main dis-
play data selection
0.01–9998 Set the machine speed at 60Hz.
Maximum setting value of Pr. 37
16777.215
60 [Hz]
×
Setting value of Pr. 1(Pr. 18) [Hz]
----------------------------------------------------------------------------------------
<
Summary of Contents for FR-D720S SC EC
Page 2: ......
Page 4: ......
Page 24: ...Description of the case Product checking and part identification 1 4 ...
Page 108: ...Operation panel Operation 4 20 ...
Page 436: ...Setting for the parameter unit and operation panel Parameter 6 286 ...
Page 484: ...Measurements on the main circuit Maintenance and inspection 8 14 ...
Page 504: ...Specification change Appendix A 20 ...
Page 505: ......
Page 506: ......
Page 510: ...Index Appendix A 24 ...
Page 511: ......