Function assignment of external terminals
Parameter
6 - 98
6.9.5
Output terminal function selection (Pr. 190, Pr. 192, Pr. 197)
You can change the functions of the open collector output terminal and relay output terminal.
The above parameter can be set when Pr. 160 = 0.
You can set the functions of the output terminals.
Refer to the following table and set the parameters:
0–99: Source logic
100–199: Sink logic
Pr.
No.
Name
Initial
Value
Initial Signal
Setting Range
Parameters referred to
Refer to
Section
190
RUN terminal
function selection
Open
collector
output
terminal
0
RUN (inverter running)
0/1/3/4/7/8/11–16/
25/26/46/47/64/70/
80/81/90/91/93/95/
96/98/99/100/101/
103/104/107/108/
111–116/125/126/
146/147/164//170/
180/181/190/191/
193/195/196/198/
199/9999
13
Starting
frequency
192
ABC terminal
function selection
Relay
output
terminal
99
ALM (alarm output)
0/1/3/4/7/8/11–16/
25/26/46/47/64/70/
80/81/90/91/95/96/
98/99/100/101/103/
104/107/108/111–
116/125/126/146/
147/164/170/180/
181/190/191/195/
196/198/199/9999
197
SO terminal
function selection
Open
collector
output
terminal
80
SAFE (Safety monitor
output)
0/1/3/4/7/8/11–16/
25/26/46/47/64/70/
80/81/90/91/93/95/
96/98/99/100/101/
103/104/107/108/
111–116/125/
126/146/147/164/
170/180/181/190/
191/193/195/196/
198/199
Setting
Terminal
Function
Operation
Related
Parameters
Refer to
Page
Source
Logic
Sink
Logic
0
100
RUN
Inverter running
Output during operation when
the inverter output frequency
rises to or above Pr. 13
"Starting frequency".
—
1
101
SU
Up to frequency
Output when the output fre-
quency is reached to the set
frequency.
Pr. 41
3
103
OL
Overload alarm
Output while stall prevention
function is activated.
Pr. 22, Pr. 23,
Pr. 66
4
104
FU
Output frequency detection
Output when the output
frequency reaches the
frequency setting in Pr. 42
(Pr. 43 for reverse rotation).
Pr. 42, Pr. 43
7
107
RBP
Regenerative brake prealarm
Output when 85% of the
regenerative brake duty set in
Pr. 70 is reached.
Pr. 70
Tab. 6-15:
Output terminal function assignment (1)
Summary of Contents for FR-D720S SC EC
Page 2: ......
Page 4: ......
Page 24: ...Description of the case Product checking and part identification 1 4 ...
Page 108: ...Operation panel Operation 4 20 ...
Page 436: ...Setting for the parameter unit and operation panel Parameter 6 286 ...
Page 484: ...Measurements on the main circuit Maintenance and inspection 8 14 ...
Page 504: ...Specification change Appendix A 20 ...
Page 505: ......
Page 506: ......
Page 510: ...Index Appendix A 24 ...
Page 511: ......