Frequency setting by external terminals
Parameter
6 - 48
6.5
Frequency setting by external terminals
6.5.1
Multi-speed setting operation
(Pr. 4 to Pr. 6, Pr. 24 to Pr. 27, Pr. 232 to Pr. 239)
The frequency inverters have 15 fixed setting frequencies (speeds) which can be preset by the
user as required via parameters 4, 5, 6, 24 to 27 as well as via parameters 232 to 239.
Any speed can be selected by merely turning on-off the contact signals (RH, RM, RL, REX
signals).
The above parameters allow its setting to be changed during operation in any operation mode
even if "0" (initial value) is set in Pr. 77 "Parameter write selection".
The above parameters can be set when Pr. 160 = 0.
Purpose
Parameters that must be set
Refer to
Section
Make frequency setting by combina-
tion of terminals
Multi-speed operation
Pr. 4–Pr. 6,
Pr. 24–Pr. 27
Pr. 232–Pr. 239
Perform jog operation
Jog operatio
Pr. 15, Pr. 16
Infinitely variable speed setting by
terminals
Remote setting function
Pr. 59
Pr.
No.
Name
Initial
Value
Setting Range Description
Parameters referred to
Refer to
Section
4
Multi-speed setting
(high speed)
50Hz
0–400Hz
Set the frequency when RH
turns on.
15
59
79
178–182
JOG frequency
Remote function
selection
Operation mode
selection
Input terminal
function selection
5
Multi-speed setting
(middle speed)
30Hz
0–400Hz
Set the frequency when RM
turns on.
6
Multi-speed setting
(low speed)
10Hz
0–400Hz
Set the frequency when RL turns
on.
24
Multi-speed setting
(speed 4)
9999
0–400Hz/9999
Frequency from speed 4 to
speed 15 can be set according
to the combination of the RH,
RM, RL and REX signals.
9999: not selected
25
Multi-speed setting
(speed 5)
9999
0–400Hz/9999
26
Multi-speed setting
(speed 6)
9999
0–400Hz/9999
27
Multi-speed setting
(speed 7)
9999
0–400Hz/9999
232
Multi-speed setting
(speed 8)
9999
0–400Hz/9999
233
Multi-speed setting
(speed 9)
9999
0–400Hz/9999
234
Multi-speed setting
(speed 10)
9999
0–400Hz/9999
235
Multi-speed setting
(speed 11)
9999
0–400Hz/9999
236
Multi-speed setting
(speed 12)
9999
0–400Hz/9999
237
Multi-speed setting
(speed 13)
9999
0–400Hz/9999
238
Multi-speed setting
(speed 14)
9999
0–400Hz/9999
239
Multi-speed setting
(speed 15)
9999
0–400Hz/9999
Summary of Contents for FR-D720S SC EC
Page 2: ......
Page 4: ......
Page 24: ...Description of the case Product checking and part identification 1 4 ...
Page 108: ...Operation panel Operation 4 20 ...
Page 436: ...Setting for the parameter unit and operation panel Parameter 6 286 ...
Page 484: ...Measurements on the main circuit Maintenance and inspection 8 14 ...
Page 504: ...Specification change Appendix A 20 ...
Page 505: ......
Page 506: ......
Page 510: ...Index Appendix A 24 ...
Page 511: ......