28
Control circuit specifications
(3) Safety stop function operation
∗1
At an internal safety circuit fault, E.SAF or E.CPU is displayed on the operation panel.
SA is displayed on the operation panel when both the S1 and S2 signals are in the open state without any internal safety circuit fault (E.SAF, E.CPU).
∗2
ON: Transistor used for an open collector output is conducted.
OFF: Transistor used for an open collector output is not conducted.
For more details,
refer to the Safety stop function instruction manual (BCN-A211508-000)
. (Please contact your sales representative
for the manual.)
Input power
Input signal
Internal
safety
circuit
Output signal
Inverter operation state
S1-SC
S2-SC
SAFE
SAFE2
OFF
-----
-----
-----
OFF
OFF
Output shutoff (Safe state)
ON
Short
Short
No failure
OFF
ON
Drive enabled
Failure
OFF
OFF
Output shutoff (Safe state)
Open
Open
No failure
ON
ON
Output shutoff (Safe state)
Failure
OFF
OFF
Output shutoff (Safe state)
Short
Open
N/A
OFF
OFF
Output shutoff (Safe state)
Open
Short
N/A
OFF
OFF
Output shutoff (Safe state)
" N/A " denotes a condition where circuit fault does not apply.
CAUTION
Do not connect the FR-E700-SC/NC/NF series together with the FR-D700 series. If connected together, the
safety stop function does not work properly.