(E) Environment setting parameters
91
5
GROUP
E
5.2.7
Password function
When
Pr.297
= "0, 9999", writing is always enabled, but setting is disabled. (The display cannot be changed.)
Parameter reading/writing restriction level (Pr.296)
• The level of the reading/writing restriction using the operation panel or via RS-485 communication can be selected with
Pr.296
.
If the parameter writing is restricted by the
Pr.77
Parameter write selection
setting, those parameters are unavailable for writing even when
"
" is indicated.
Registering a password (Pr.296, Pr.297)
• The following section describes how to register a password.
1) Set the parameter reading/writing restriction level. (
Pr.296
"9999")
During
Pr.296
= any of "100 to 103, 105 or 106", if password unlock error has occurred five times, correct password will not unlock the
restriction. All parameter clear can unlock the restriction. (In this case, the parameters are returned to their initial values.)
2) Write a four-digit number (1000 to 9998) to
Pr.297
as a password. Writing is disabled when
Pr.296
= "9999".) When a
password is registered, parameter reading/writing is restricted with the restriction level set in
Pr.296
until unlocking.
NOTE
• After registering a password, the read value of
Pr.297
is always one of "0" to "5".
•
appears when a password restricted parameter is read/written.
• Even if a password is registered, the parameters, which the converter unit itself writes, such as converter unit parts life are
overwritten as needed.
Registering a 4-digit password can restrict parameter reading/writing.
Pr.
Name
Initial value
Setting range
Description
296
E410
Password lock level
9999
0 to 3, 5, 6,
100 to 103, 105, 106
Select restriction level of parameter
reading/writing when a password is
registered.
9999
No password lock
297
E411
Password lock/unlock
9999
1000 to 9998
Register a 4-digit password.
(0 to 5)
Displays password unlock error count.
(Reading only) (Valid when
Pr.296
= "100
to 103, 105 or 106")
9999
No password lock
Pr.296
setting
Operation panel
RS-485 communication
Read
Write
Read
Write
9999
0, 100
1, 101
2, 102
3, 103
5, 105
6, 106
: Enabled,
: Disabled
Pr.296 setting
Password unlock error
restriction
Pr.297 display
0 to 3, 5, 6
No restriction
Always displays 0
100 to 103, 105, 106
Restricted at fifth error
Displays the error count (0 to 5)