Copying and verifying parameters
134
5.9.2
Parameter verification
NOTE
•
blinks... Why?
-The parameter settings may be different between the verification source converter unit and the verification destination
converter unit. To continue verification, press
.
• Whether the parameter settings of converter units are the same or not can be checked.
Operation
1.
Copy the parameter settings of the verification source converter unit to the operation panel according to the procedure on
2.
Move the operation panel to the converter unit to be verified.
3.
Screen at power-ON
The monitor display appears.
4.
Parameter setting mode
Press
to choose the parameter setting mode. (The parameter number read previously appears.)
5.
Selecting the parameter number
Turn
to
(parameter copy), and press
.
"
" appears.
6.
Parameter verification
Turn
to change to the setting value "
" (parameter copy verification mode).
Press
. Verification of the parameter settings copied to the operation panel and the parameter settings of the verification des-
tination converter unit is started. (It takes about 60 seconds to verify all the settings. During verification, "
" blinks.)
If there are different parameters, the different parameter number and "
" blink.
To continue verification, press
.
7.
"
" and "
" blink alternately after verification ends.