78
Class 0x2A Instance 1
Attribute ID Access Data type No. of data bytes
Definition
141
Get/Set
UINT
2
Faults history 1 (latest)
Faults history all clear
142
Get
UINT
2
Faults history 2 (second fault in past)
143
Get
UINT
2
Faults history 3 (third fault in past)
144
Get
UINT
2
Faults history 4 (fourth fault in past)
145
Get
UINT
2
Faults history 5 (fifth fault in past)
146
Get
UINT
2
Faults history 6 (sixth fault in past)
147
Get
UINT
2
Faults history 7 (seventh fault in past)
148
Get
UINT
2
Faults history 8 (eigth fault in past)
170
Get
UINT
2
Output frequency (0.01 Hz)
171
Get
UINT
2
172
Get
UINT
2
Output voltage (0.1 V)
174
Get
UINT
2
Frequency setting value (0.01 Hz)
175
Get
UINT
2
Running speed (1 r/min)
The setting values of
Pr.37, Pr.144, and Pr.811
are effective. (Refer to
176
Get
UINT
2
Motor torque (0.1%)
177
Get
UINT
2
Converter output voltage (0.1 V)
178
Get
UINT
2
Regenerative brake duty (0.1%)
179
Get
UINT
2
Electronic thermal relay function load factor (0.1%)
180
Get
UINT
2
Output current peak value (0.01 A/0.1 A)
181
Get
UINT
2
Converter output voltage peak value (0.1 V)
182
Get
UINT
2
183
Get
UINT
2
Output power (0.01 kW/0.1 kW)
184
Get
UINT
2
Input terminal status