73
7
If both Run1 and Run2 are turned ON, the start signal is not changed. (The previous status remains unchanged.)
The value cannot be written while the inverter is running.
After reset with 01 set, this value must be set to 00 before inverter reset may be performed.
The communication continues during the error reset of the inverter.
This data is only updated after inverter reset or power-ON reset.
When this ID is set, it is reflected to bit 7 to 11 of
Pr. 346
and Class 0x05 Instance 2 Attribute 7, 13, 14.
When this ID is set, it is reflected to bit 2 to 6 of
Pr. 346
and Class 0x05 Instance 2 Attribute 8, 15, 16.
8
Get
Running2
(reverse rotation
command)
BOOL
1
0
0
During stop
1
During reverse rotation
9
Get
Ready
BOOL
1
1
0
During reset or fault occurrence
1
Stop or running
10
Get
Faulted
BOOL
1
0
0
No fault present
1
Fault occurred (latched)
12
Get/Set
BOOL
1
0
0
Reset release at fault occurrence
1
Reset execution at fault occurrence
15
Get
CtrlFromNet
(operation command
source monitor)
BOOL
1
1
0
Other than DeviceNet communication
operation
1
DeviceNet communication operation
140
Get/Set
Instance ID of Input
Assembly
USINT
1
0x47
(71)
0x46
Input Instance 70
0x47
Input Instance 71
0xB0
Input Instance 176
0xB1
Input Instance 177
141
Get/Set
Instance ID of Output
Assembly
USINT
1
0x15
(21)
0x14
Output Instance 20
0x15
Output Instance 21
0x7E
Output Instance 126
0x7F
Output Instance 127
Class 0x29 Instance 1
Attribute
ID
Access
Name
Data
type
No. of
data bytes
Initial
value
Range
Definition